Professional Documents
Culture Documents
Interpack2007 33574 Final
Interpack2007 33574 Final
net/publication/267597649
CITATIONS READS
10 1,842
3 authors, including:
All content following this page was uploaded by A. Radmehr on 27 April 2015.
IPACK2007-33574
Suhas V. Patankar
Innovative Research, Inc.
Plymouth, MN, USA
1. The velocity of the airflow jet from perforated tile These are reasonable assumptions, which lead to more
2. The server position in the rack conservative results.
3. The server fan characteristics
4. The server internal flow resistance THE COMPUTATIONAL MODEL
The mathematical model is formulated from the
The first two factors determine the server inlet and exhaust incompressible form of the Navier-Stokes equations, together
pressures. The last two factors determine the server response to with the k-ε turbulence model. The flow is assumed to be
the variation of the inlet and exhaust pressure. A server with steady.
high internal resistance needs powerful fans and its airflow is
not very sensitive to the changes in the inlet and exhaust The governing equations are solved using the
pressures. A server with little internal resistance, on the other Computational Fluid Dynamics software package COMPACT
hand, has rather weak fans and its airflow will be susceptible to [1]. COMPACT is based on the finite-volume method described
the changes in these pressures. by Patankar [2]. In the finite-volume method, the calculation
domain is divided into a number of finite or control volumes. A
To the authors' knowledge, there have been no studies to grid point at the center of each control volume denotes the
address this concern. The objective of this paper is to find the location of the unknown dependent variable (e.g., velocity
effect of the high-velocity airflow jet discharging from components and pressure). The partial differential equation for
perforated tiles on the amount of airflow passing through the dependent variable is integrated over the control volume,
servers at various heights in a front-to-rear server rack. Also, and the resulting integrals are approximated in terms of grid
we want to provide a simple tool for data center professionals geometry and values of variables at surrounding grid points to
to estimate the airflow reduction for servers in the rack. obtain an algebraic equation. The solution of these algebraic
equations, one for each grid point, provides the values of the
A computational model based on the CFD technique is dependent variables at all grid points in the calculation domain.
used to analyze the flow field around the server rack and
calculate the airflow taken by the servers. Two cases are The servers inside the rack are modeled as a volume
studied. In one case, a server rack from a row of racks in a comprising a row of fans at the inlet and a distributed flow
prefect hot aisle-cold aisle arrangement is considered. The resistance throughout the volume. The fans and distributed
boundary conditions around such a rack are completely flow resistance contribute respectively as source and sink terms
symmetrical. In the other case, a single rack in a room with to the momentum equation in the flow direction. The
asymmetrical boundary conditions is analyzed. The servers computational grid is refined several times to make sure the
inside the rack are modeled as a combination of a fan and a grid independent results are obtained.
flow resistance. The characteristics of the fan and resistance are
taken from typical servers manufactured by IBM. DEMONSTRATING THE POTENTIAL PROBLEM
This paper is arranged as follows. First, we present the The effect of the high-velocity jet on the airflow taken by
details of the computational model, with special emphasis on servers in the rack depends on the velocity of the jet, the
the treatment of servers inside the rack. Then we use the position of the server in the rack, the characteristics of the fans
computational model to demonstrate the potential problem of used in the servers, and the server flow resistance (impedance).
the possible starvation of the servers at the bottom of the rack. The higher the velocity of the jet, the lower the inlet pressure to
Next, we use the computational model to see how typical real- the servers, which leads to lower airflow through them.
life servers under practical operating conditions response to the
high-velocity jet. We demonstrate the effect of the high- To demonstrate the effect of a high-velocity jet on the
velocity jet on racks that accommodate various numbers of airflow through the servers, two hypothetical 2U servers
servers. Finally, we use the insight provided by the (Server A and Server B) are considered. Both of them demand
computational analysis to develop a simplified model for about 137 CFM for proper cooling. Server A has a very high
estimating the reduction of airflow for servers placed at the internal resistance and strong fans, while server B has low
bottom of the rack. internal resistance and weaker fans. Table 1 summarizes the
Table 1. Flow rate and internal pressure drop for 2U servers ANALYSIS OF RACKS HOUSING REAL-LIFE
SERVERS UNDER PRACTICAL CONDITIONS
Flow rate at Internal pressure drop at In this section two real-life servers are considered. The
Server operating point operating point characteristics of these servers (fan performance curve and
(CFM) (in wg) server impedance) are provided by IBM and are representative
A 137 1.3 of realistic high-end 1U and 2U serves manufactured by IBM.
2U 24 36 155 0.54
The airflow analysis for the two cases is performed. Fig. 1
shows the comparison of the flow distribution for servers at
different heights in the rack for the two cases. Servers of type A The location of a rack in the data center and the
are receiving almost the same flow rate irrespective of their environment around it affect the pressure distribution at inlet
position in the rack. On the other hand, servers of type B are and exhaust sides of the rack. In order to generalize the
very sensitive to their position in the rack. Those at the bottom findings of this study, two extreme cases are considered, which
receive as little as 50% of the required airflow. The airflow for are described below.
the servers on the top of the rack is close to the needed airflow.
This exercise shows that the combination of high-velocity jets Case 1: In this case, the server rack is considered in the
and low resistance servers can create a critical situation for middle of a row of racks in a perfectly hot aisles-cold aisles
servers at the bottom of the rack. arrangement as shown in Fig. 2. The boundary conditions
around the rack are symmetrical. Fig. 3 shows the solution
domain for such a rack.
Server A Server B
160
Flow Rate (CFM)
120
80
40
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Rack's Bottom Server Position Rack's Top
Figure 3. Solution domain for the rack in the middle of a row Figure 4. Solution domain for a stand-alone rack
The front, back, and two sides of the solution domain have
symmetry boundary conditions. The airflow is supplied from
Case 1 Case 2
the perforated tile in front of the rack. The exhaust is located at
the top of the hot aisle. In this case, the supply airflow jet is 50
40
rack. There is no space for the jet to expand. Similarly, the
airflow discharged from servers is contained in the rectangular 30
120
rack can be examined. Such a model can represent a stand-
alone rack, a rack at the end of a row, and any other 80
asymmetrical conditions that may exists in a data center.
40
Fig. 5 shows the airflow distribution through 1U servers in
a rack for the two cases. The rack is full; there are 40 servers in 0
the rack. The data is shown for servers on the odd locations to 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
make the graph more readable. It can be seen that for case 2 the Server Position
servers receive almost the same airflow. However, for case 1, Figure 6. Airflow distribution through 2U servers in a rack
are presented for the server at the bottom of the rack since it 2%
pressure is PC2.
14%
Perforated
Tile
Server
PC1, V PH1 , 0
1
PH 1 − PH 2 = ρV 2 (2)
2
Figure 10. Pressure and velocity distribution across the rack
The pressure at the top of the rack is nearly uniform:
To develop a simple model to estimate the amount of the
PC 2 = PH 2 (3) flow reduction for the server placed at the bottom of the rack,
many scenarios with different types of servers and different
number of servers in the rack were analyzed. The following
Using equations 1, 2, and 3 the theoretical pressure
dimensionless variables are defined:
difference across the server at the bottom of the rack is:
Velocity Head of the Flow Discharging from Tile
PH 1 − PC1 = ρV 2 (4) H=
Nominal Pressure Drop across the Server
0.4 ACKNOWLEDGMENTS
0.00 0.05 0.10 0.15 0.20 0.25 0.30
The authors would like to thank Dr. Madhusudan Iyengar
and Dr. Roger Schmidt from IBM for providing us with the
H typical characteristics of the 1U and 2U servers.
Figure 11. Flow fraction for bottom server as a function of
dimensionless velocity head REFERENCES
[1] Compact User’s Manual, Innovative Research, Inc.,
The line fit shown in Fig. 11 can be expressed as the 3025 Harbor Lane N., Suite 300, Plymouth, MN 55447.
follows:
[2] S.V. Patankar, Numerical Heat Transfer and Fluid Flow,
F = 1 − 1.84 H (5) Hemisphere, 1980.