BAYARD-VT-XGS SYSTEM
MAIN VALVE
BAYARD-VT-XGS
The Series VT-XGS system offers a range of automatic control valves based on the association of the hydraulically
operated, diaphragm actuated main valve and the combination of one or several suitable pilot valves. Fully tested
and suitable for potable water, most common applications are for level control (high low & modulating and electrical
solenoid control) and pressure control (reducing & relief-sustaining).
2
Plug : Stainless Steel
Bolts and Washer : Stainless Steel
Diaphragm : EPDM
Gasket : EPDM
O-ring : EPDM
Body : Ductile Iron
1a 2 1b 1a 2 1b 1a 2 1b
C
C C
A B A B A B
Chamber C is linked to inlet area A The 3-way valve (2) is adjusted to The 3-way-valve (2) is adjusted to
through tube (1a) by adjusting the 3- stop the flow through (1a) and the mid-position to isolate Chamber
way valve (2) allowing the inlet connect Chamber C to outlet area B C, holding the volume of water in it
pressure into Chamber C. The larger through tube (1b). This results in a which prevents water from entering
surface area of the diaphragm over higher pressure below the and exiting the chamber, thereby
the valve disc resulted in a higher diaphragm assembly which forces it fixing the position of the valve
pressure at Chamber C, closing the and the valve disc to be lifted up, opening.
valve. opening the valve.
3
Technical Data
• Compliant with EN 12266
• Seating: class A according to standard ISO 5208-2
Body test pressure : 1.5 PN
Seat test pressure : 1.1 PN
• Face-to-face dimensions according to standards EN 558-1 series 1 and ISO 5752 series 1
• Flange drilling according to standards EN 1092-2 and ISO 7005-2: ISO PN 16 for DN50 to 300 (other drillings,
please consult us)
The diameter of the valve must be chosen according to the flow rate conditions and the pressure on the valves.
Generally two cases can be considered :
Case 1 : The available head or the static pressure is ≤ 1 bar, therefore, the head loss of the valve has to be as low
as possible (2m to 5m according to the DN and design).
Case 2 : The available static pressure is high, so higher velocities can be omitted (beforehand, check that the
available static pressure is higher than the head loss through the fully open valve at the maximum
considered flow rate).
Recommended flow rates (l/s)
Size 2” 2-1/2” 3” 4” 6” 8”
Type XGS Design
VE* 50 65 80 100 150 200
Minimum flow rate 0.2 m/s 0.4 0.7 1 1.6 3.5 6.3
Case 1
Max permanent flow rate 2.0 m/s 3.9 6.6 10.4 16 35 63
Minimum flow rate 0.4 m/s 0.8 1.3 2 3.1 7.1 13
Case 2
Max permanent flow rate 4.0 m/s 7.7 13.6 20 31.2 71 126
VE* (m/s) = Equivalent velocity: average velocity in the inlet section (DN)
These values don’t apply to flow limiting, overspeed and different functions
4
Hydraulic Characteristic
This diagram helps to check the working conditions of
the valve.
mm mm mm mm Kv kg
50 230 82.5 139 85 28 10
65 290 92.5 159 95.0 50 14.8
80 310 100 179 102 72 19.2
D
A1
5
FLOAT OPERATED VALVE
VT-XGS-FT
The high/low VT-XGS-FT pilot operated valve opens fully when the water level in a water tank reaches the pre-set
low point and shuts off (drip tight) when the water reaches the high level. The rotary 3-port stainless steel pilot is
equipped with a stainless steel vertical rod which allows the float to rise and lower to the adjustable stainless steel
upper and lower level stops.
The modulating VT-XGS-FT float valve maintains a constant level in storage tanks and reservoirs. Valve controlled
flow into tank is proportional to discharge flow, keeping the tank full at all times.
Pilot float valve is remote mounted (unless specified valve mounted for high/low pilot). It is recommended to provide
a stilling well around the float if water surface is subject to turbulence and ripples.
Functions
High/Low Level with Float Pilot
• Closes completely at a constant adjustable top level
• Opens completely at a constant lower level after consumption of an adjustable water depth
• Manually controlled opening and closing speed controller can be added as an option to avoid any hydraulic shock
on request
• Adjustment Range
The differential level of the water is adjustable by pre-setting the 2 pieces of stainless steel collars along the
stainless steel rod for low level (open) and high level (close) positions
6
VT-XGS-FT Dimensions
C A2 E B
D
A1
Optional :
• Constant Level Float Modulating Valve with
patented lock system for for a guaranteed
perfect lock.
• Body: SS304
• Float: SS304
• Seat Seal: NBR (Buna-N)
• Range: DN10 to DN32
• Max Working Pressure: 10 bar
7
VAL-TECHNIK PTE LTD
No. 40 Ubi Crescent 01-05
Singapore 408567
Val-Technik makes every effort to maintain the accuracy & quality of the information provided in this catalogue, however we cannot guarantee & assume
no legal liability for the accuracy or completeness of the information. We reserve the rights to make changes without prior notice. November 2018