Address Map ZR90 - A1 Gen 1 Gateway Mod (S904899)
Coils
Name Coil
Stopped/Running 1
Unload/Load 2
General Warning 3
General ShutdownWarning 4
General Shutdown 5
General Service 6
General StartFailure 7
Emergency Stop 8
Manual/Automatic 9
Local/Remote 10
Counters Registers
Value = (65536 x W2) + W1
Name Unit
Value W2 Value W1
Running Hours s 1001 1002
Loaded Hours s 1003 1004
Motor Starts Count 1005 1006
Load Relay Count 1007 1008
Dryer Starts Count 1009 1010
Module Hours s 1013 1014
Fast Starts Count 1015 1016
Emergency Stops Count 1017 1018
General Status
Register 703
Name Bit
PreWarning 0
General Warning 1
General Shutdown Warning 2
General Shutdown 3
General Service 4
General Start Failure 5
Emergency Stop 6
Manual/Automatic 7
Local/Remote 8
Week Timer 9
PreWarning Service Running Hours 10
- 11
PreWarning Service Analog Input 12
PrePermissive 13
Test Mode 14
ESi Status
Register 709
Name Value
PowerUp ES 8209
Local Operation ES 8225
Central Stop ES 8242
Shutdown ES 8337
Automatic Operation ES 24594
Pressure Band Selection
Pressure Band 1 - Load 862 mBar n/a
Pressure Band 1 - Unload 863 mBar n/a
Pressure Band 2 - Load 864 mBar n/a
Pressure Band 2 - Unload 865 mBar n/a
Commands
Name Register Value Read Value Write Info
Start 2001 n/a 1 Start the main machine
Stop 2001 n/a 2 stop the main machine
Load 2001 n/a 3
Unload 2001 n/a 4
StartES 2001 n/a 5
StopES 2001 n/a 6
LocalES 2001 n/a 7
Load50 2001 n/a 8
0/1
Triggered / OK
Stopped / Running
Unload / Load
Local / Remote
Pressure Band 1 / Pressure Band 2
Triggered / OK
Open / Closed
Water / No Water
Water / No Water
Water / No Water
Water / No Water
Description
PreWarning
Warning
ShutdownWarning
Shutdown
Service
Permissive
Sensor Error
Set/Not set
SPM valid measurement
PrePermissive
Value Interpretation
Description
Sensor Error
Set/Not set
Valid Measurement
0/1
Stopped / Running
Open / Closed
Open / Closed
Unload / Load
No / Yes
Yes / No
Yes / No
Open / Closed
Open / Closed
Open / Closed
Open / Closed
Description
PreWarning
Warning
Shutdown
the main machine
the main machine