PROJECT : SEKOLAH INTEGRASI KAFA AL-HIDAYAH Date: 5/12/2016

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Dtails :
i) Kuala Lumpur (Klang) falls under region 1 = west cost
ii) Project area = 2341 m2
= 0.23 ha
iii) terrain = mild
iv) % of impervious area = 90%

Calculation references

Permissible Site Discharge (PSD/ha) = 65.5 liter/s/ha From Table 5.A1


Project area = 0.23 ha
PSD = 65.5 x 0.23
= 15.065 liter/s
= 0.015 m3/s

Site Storage Requirement (SSR/ha) = 540.4 m3/ha From Table 5.A1


Project area = 0.23 ha
SSR = 124.3 m3

Inlet Flow/ha = 240 liter/s/ha From Table 5.A2


Project area = 0.23 ha
Inlet Flow = 55.20 liter/s
= 0.055 m3/s

PSD/ha = 62.3 liter/s/ha From Table 5.A2


Project area = 0.23 ha
PSD = 14.329 liter/s
= 0.014 m3/s

SSR/ha = 529.7 m3/s From Table 5.A2


Project area = 0.23 ha
SSR = 121.8 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.014 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 251.7 mm diameter For Region 1, Mild terrain,
Provide pipe size = 300 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 286.5 mm diameter with inflow =0.055
Provide pipe size = 300 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 92.55 mm diameter For Region 1, Mild terrain,
Provide pipe size = 100 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 240.4 mm diameter with PSD =0.014
Provide pipe size = 300 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.014 m3/s
= 14.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 124.3 m3

SIZING OF OSD TANK


Storage required = 124.3 m3
Area 126.00 m

Depth= 1.00 m

Storage provided = 126 m3

Overflow / Inlet pipe= 300 mm


Outlet pipe = 100 mm

- end -
PROJECT : SEKOLAH INTEGRASI KAFA AL-HIDAYAH Date: 14/5/2018

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Dtails :
i) Kuala Lumpur (Klang) falls under region 1 = west cost
ii) Project area = 2341 m2
= 0.23 ha
iii) terrain = mild
iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 65.5 liter/s/ha From Table 5.A1


Project area = 0.23 ha
PSD = 65.5 x 0.23
= 15.065 liter/s
= 0.015 m3/s

Site Storage Requirement (SSR/ha) = 540.4 m3/ha From Table 5.A1


Project area = 0.23 ha
SSR = 124.3 m3

Inlet Flow/ha = 240 liter/s/ha From Table 5.A2


Project area = 0.23 ha
Inlet Flow = 55.20 liter/s
= 0.055 m3/s

PSD/ha = 62.3 liter/s/ha From Table 5.A2


Project area = 0.23 ha
PSD = 14.329 liter/s
= 0.014 m3/s

SSR/ha = 529.7 m3/s From Table 5.A2


Project area = 0.23 ha
SSR = 121.8 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.014 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 251.7 mm diameter For Region 1, Mild terrain,
Provide pipe size = 300 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 286.5 mm diameter with inflow =0.055
Provide pipe size = 300 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 92.55 mm diameter For Region 1, Mild terrain,
Provide pipe size = 100 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 240.4 mm diameter with PSD =0.014
Provide pipe size = 300 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.014 m3/s
= 14.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 124.3 m3

SIZING OF OSD TANK


Storage required = 124.3 m3
Area 80.00 m

Depth= 1.65 m

Storage provided = 132 m3 Area, mm2

Overflow / Inlet pipe= 300 mm 70685.835


Outlet pipe = 100 mm 7853.9816

- end -
PROJECT : NURI PAGOH Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 16416.52 m2 = 1.64 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 1.64 ha
PSD = 63.1 x 1.64
= 103.484 liter/s
= 0.103 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 1.64 ha
SSR = 939.2 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 1.64 ha
Inlet Flow = 362.44 liter/s
= 0.362 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 1.64 ha
PSD = 103.484 liter/s
= 0.103 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 1.64 ha
SSR = 939.2 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.103 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 577.866 mm diameter For Region 1, Mild terrain,
Provide pipe size = 600 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 635 mm diameter with inflow =0.362
Provide pipe size = 650 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 247 mm diameter For Region 1, Mild terrain,
Provide pipe size = 250 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 342.14 mm diameter with PSD =0.103
Provide pipe size = 350 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.103 m3/s
PSD = 103.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 939.2 m3

SIZING OF OSD TANK

Storage required = 939.2 m3


Length = 48.00 m
Width = 10.00 m
Area = 480 m2

Depth (Internal Depth) = 2.00 m

Storage provided = 960.00 m3 OK!

Overflow / Inlet pipe= 600 mm


Outlet pipe = 250 mm

SIZING OF OUTLET

Outlet Opening Area = 49087.385 mm2


No of Outlets = 2 Outlets
1 Outlet Area = 24543.693 mm2
Outlet Square Opening = 156.66427 mm x 156.66427 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW

Overflow Weir Length = 1884.9556 mm


No of Exposed Sides = 2 Sides
1 Exposed side Length = 471.2389 mm = 480 mm
Total Exposed Length = 960 mm
Square Overflow Weir = 471.2389 mm x 471.2389 mm

Approximate Min Overflow Length = 480 mm x 480 mm


Used Overflow Length = 500 mm x 500 mm OK!

Weir Base Width, B = 1.0 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.9 m
Spillway discharge Coefficient, Csp = 1.58

Emergency Spillway Discharge, Q = 1.349 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 1.3284 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 14583.13 m2 = 1.46 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 1.46 ha
PSD = 63.1 x 1.46
= 92.126 liter/s
= 0.092 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 1.46 ha
SSR = 836.1 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 1.46 ha
Inlet Flow = 322.66 liter/s
= 0.323 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 1.46 ha
PSD = 92.126 liter/s
= 0.092 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 1.46 ha
SSR = 836.1 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.092 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 564.46 mm diameter For Region 1, Mild terrain,
Provide pipe size = 570 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 589.645 mm diameter with inflow =0.323
Provide pipe size = 600 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 232.12 mm diameter For Region 1, Mild terrain,
Provide pipe size = 250 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 317.3 mm diameter with PSD =0.092
Provide pipe size = 350 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.092 m3/s
PSD = 92.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 836.1 m3

SIZING OF OSD TANK

Storage required = 836.1 m3


Length = 42.00 m
Width = 10.00 m
Area = 420.00 m2

Depth (Internal Depth) = 2.00 m

Storage provided = 840.00 m3 OK!

Overflow / Inlet pipe= 570 mm


Outlet pipe = 250 mm

SIZING OF OUTLET

Outlet Opening Area = 49087.385 mm2


No of Outlets = 2 Outlets
1 Outlet Area = 24543.693 mm2
Outlet Square Opening = 156.66427 mm x 156.66427 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW SUMP

Overflow Weir Length = 1790.7078 mm


No of Exposed Sides = 2 Sides
1 Exposed side Length = 447.67695 mm = 450 mm
Total Exposed Length = 900 mm
Square Overflow Weir = 447.67695 mm x 447.67695 mm

Approximate Min Overflow Length = 450 mm x 450 mm


Used Overflow Length = 450 mm x 450 mm OK!

Weir Base Width, B = 0.9 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.9 m
Spillway discharge Coefficient, Csp = 1.61

Emergency Spillway Discharge, Q = 1.237 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 1.1826 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH - OSD 1 Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 16919.141 m2 = 1.692 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 1.692 ha
PSD = 63.1 x 1.692
= 106.765 liter/s
= 0.107 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 1.692 ha
SSR = 969 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 1.692 ha
Inlet Flow = 373.93 liter/s
= 0.374 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 1.692 ha
PSD = 106.765 liter/s
= 0.107 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 1.692 ha
SSR = 969 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.107 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 581.52 mm diameter For Region 5, Mild terrain,
Provide pipe size = 600 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 648.87 mm diameter with inflow =0.374
Provide pipe size = 650 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 251.05 mm diameter For Region 5, Mild terrain,
Provide pipe size = 250 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 345.7 mm diameter with PSD =0.107
Provide pipe size = 350 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.107 m3/s
PSD = 107.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 969.0 m3

SIZING OF OSD TANK

Storage required = 969.0 m3


Length = 45.00 m
Width = 13.50 m
Area = 608 m2

Depth (Internal Depth) = 1.60 m

Storage provided = 972.00 m3 OK!

Overflow / Inlet pipe= 600 mm Assume gradient = 1:200,


Outlet pipe = 250 mm Assume gradient = 1:200,

SIZING OF OUTLET

Outlet Opening Area = 49087.385 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 16362.462 mm2
Outlet Square Opening = 127.91584 mm x 127.91584 mm

Approximate Max 1 Outlet Area = 120 mm x 120 mm


Used Single Outlet Area = 120 mm x 120 mm OK!

SIZING OF OVERFLOW

Overflow Weir Length = 1884.9556 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 471.2389 mm = 480 mm
Total Exposed Length = 1440 mm
Square Overflow Weir = 471.2389 mm x 471.2389 mm

Approximate Min Overflow Length = 480 mm x 480 mm


Used Overflow Length = 500 mm x 500 mm OK!

Weir Base Width, B = 1.5 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.8 m
Spillway discharge Coefficient, Csp = 1.47

Emergency Spillway Discharge, Q = 1.578 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 1.37052 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH - OSD 2 Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 6845.7898 m2 = 0.68 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 0.68 ha
PSD = 63.1 x 0.68
= 42.908 liter/s
= 0.043 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 0.68 ha
SSR = 389.4 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 0.68 ha
Inlet Flow = 150.28 liter/s
= 0.150 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 0.68 ha
PSD = 42.908 liter/s
= 0.043 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 0.68 ha
SSR = 389.4 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.043 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 438.07 mm diameter For Region 1, Mild terrain,
Provide pipe size = 450 mm diameter 90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 394.75 mm diameter with inflow =0.15
Provide pipe size = 400 mm diameter Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 161.152 mm diameter For Region 1, Mild terrain,
Provide pipe size = 150 mm diameter 90% Impervious project area

Based on Table 5.A4 : outlet pipe = 273.3 mm diameter with PSD =0.043
Provide pipe size = 280 mm diameter Mild Terrain

Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.043 m3/s
PSD = 43.0 l/s

SSR (whichever is larger from Table 5.A1 and A2) = 389.4 m3

SIZING OF OSD TANK

Storage required = 389.4 m3


Length = 25.00 m
Width = 10.00 m
Area = 250.00 m2

Depth (Internal Depth) = 1.60 m

Storage provided = 400.00 m3 OK!

Overflow / Inlet pipe= 400 mm Assume gradient = 1:200,


Outlet pipe = 150 mm Assume gradient = 1:200,

SIZING OF OUTLET

Outlet Opening Area = 17671.459 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 5890.4862 mm2
Outlet Square Opening = 76.749503 mm x 76.749503 mm

Approximate Max 1 Outlet Area = 70 mm x 70 mm


Used Single Outlet Area = 70 mm x 70 mm OK!

SIZING OF OVERFLOW SUMP

Overflow Weir Length = 1256.6371 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 314.15927 mm = 320 mm
Total Exposed Length = 960 mm
Square Overflow Weir = 314.15927 mm x 314.15927 mm

Approximate Min Overflow Length = 320 mm x 320 mm


Used Overflow Length = 350 mm x 350 mm OK!

Weir Base Width, B = 1.1 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.6 m
Spillway discharge Coefficient, Csp = 1.396

Emergency Spillway Discharge, Q = 0.681 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 0.5508 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH P3A - OSD 1 Date: ###

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 15125.87 m2 = 1.513 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 1.513 ha
PSD = 63.1 x 1.513
= 95.47 liter/s
= 0.095 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 1.513 ha
SSR = 866.5 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 1.513 ha
Inlet Flow = 334.37 liter/s
= 0.334 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 1.513 ha
PSD = 95.47 liter/s
= 0.095 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 1.513 ha
SSR = 866.5 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.095 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 568.5 mm diameter For Region 5, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : Intlet pipe = 603.1 mm diameter with inflow =0.334
Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 236.55 mm diameter For Region 5, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : outlet pipe = 332.25 mm diameter with PSD =0.095
Mild Terrain

Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 866.5 m3

Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.334 m3/s
PSD (Outflow) = 0.334 m3/s
Inlet Pipe = 568.5 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300

Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.095 m3/s
PSD (Outlet flow) = 0.095 m3/s
Outlet Pipe = 236.55 mm
According to Manning's Equation, use = 300 mm Dia, 1: 100

SIZING OF OSD TANK

Storage required = 866.5 m3


Length = 53.00 m
Width = 15.00 m
Area = 795 m2

Depth (Internal Depth) = 1.10 m

Storage provided = 874.50 m3 OK!

SIZING OF OUTLET

Outlet Opening Area = 70685.83463 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 23561.94488 mm2
Outlet Square Opening = 153.4990061 mm x 153.499006 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW

Overflow Weir Length = 1884.95559 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 471.2388975 mm = 480 mm
Total Exposed Length = 1440 mm
Square Overflow Weir = 471.2388975 mm x 471.238898 mm

Approximate Min Overflow Length = 480 mm x 480 mm


Used Overflow Length = 500 mm x 500 mm OK!

Weir Base Width, B = 1.5 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation
2.10 of Chapter 2 - MSMA 2nd
Effective Head of Spillway Crest, H = 0.8 m Edition
Spillway discharge Coefficient, Csp = 1.47

Emergency Spillway Discharge, Q = 1.578 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 1.22553 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH P3A - OSD 2 Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 4985.94 m2 = 0.50 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 0.5 ha
PSD = 63.1 x 0.5
= 31.55 liter/s
= 0.032 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 0.5 ha
SSR = 286.4 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 0.5 ha
Inlet Flow = 110.50 liter/s
= 0.111 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 0.5 ha
PSD = 31.55 liter/s
= 0.032 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 0.5 ha
SSR = 286.4 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.032 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 373.5 mm diameter For Region 1, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : Intlet pipe = 350.65 mm diameter with inflow =0.111
Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 137.5 mm diameter For Region 1, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : outlet pipe = 260.8 mm diameter with PSD =0.032
Mild Terrain

Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 286.4 m3

Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.111 m3/s
PSD (Outflow) = 111.0 l/s
Inlet Pipe = 350.65 mm
According to Manning's Equation, use Pipe Culvert = 450 mm Dia, 1: 300

Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.032 m3/s
PSD (Outlet flow) = 32.0 l/s
Outlet Pipe = 137.5 mm
According to Manning's Equation, use Pipe Culvert = 300 mm Dia, 1: 300

SIZING OF OSD TANK

Storage required = 286.4 m3


Length = 23.00 m
Width = 13.00 m
Area = 299.00 m2

Depth (Internal Depth) = 1.00 m

Storage provided = 299.00 m3 OK!

SIZING OF OUTLET

Outlet Opening Area = 70685.835 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 23561.945 mm2
Outlet Square Opening = 153.49901 mm x 153.49901 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW SUMP

Overflow Weir Length = 1413.7167 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 353.42917 mm = 360 mm
Total Exposed Length = 1080 mm
Square Overflow Weir = 353.42917 mm x 353.42917 mm

Approximate Min Overflow Length = 360 mm x 360 mm


Used Overflow Length = 400 mm x 400 mm OK!

Weir Base Width, B = 1.2 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2,


From Table 2.7 and Equation 2.10
of Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.6 m
Spillway discharge Coefficient, Csp = 1.452

Emergency Spillway Discharge, Q = 0.810 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 0.405 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH P3B - OSD 1 Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 11023.97 m2 = 1.103 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 1.103 ha
PSD = 63.1 x 1.103
= 69.599 liter/s
= 0.070 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 1.103 ha
SSR = 631.7 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 1.103 ha
Inlet Flow = 243.76 liter/s
= 0.244 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 1.103 ha
PSD = 69.599 liter/s
= 0.070 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 1.103 ha
SSR = 631.7 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.070 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 538.48 mm diameter For Region 5, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : Intlet pipe = 501.4 mm diameter with inflow =0.244
Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 203.294 mm diameter For Region 5, Mild terrain,
90% Impervious project area
Based on Table 5.A4 : outlet pipe = 303.5 mm diameter with PSD =0.07
Mild Terrain

Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 631.7 m3

Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.244 m3/s
PSD (Outflow) = 0.244 m3/s
Inlet Pipe = 501.4 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300

Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.070 m3/s
PSD (Outlet flow) = 0.070 m3/s
Outlet Pipe = 203.294 mm
According to Manning's Equation, use = 300 mm Dia, 1: 300

SIZING OF OSD TANK

Storage required = 631.7 m3


Length = 45.00 m
Width = 15.00 m
Area = 675 m2

Depth (Internal Depth) = 1.00 m

Storage provided = 675.00 m3 OK!

SIZING OF OUTLET

Outlet Opening Area = 70685.835 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 23561.945 mm2
Outlet Square Opening = 153.49901 mm x 153.499006 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW

Overflow Weir Length = 1884.9556 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 471.2389 mm = 480 mm
Total Exposed Length = 1440 mm
Square Overflow Weir = 471.2389 mm x 471.238898 mm

Approximate Min Overflow Length = 480 mm x 480 mm


Used Overflow Length = 500 mm x 500 mm OK!

Weir Base Width, B = 1.5 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2,


From Table 2.7 and Equation 2.10
of Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.6 m
Spillway discharge Coefficient, Csp = 1.46

Emergency Spillway Discharge, Q = 1.018 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 0.89343 m3/s Since emergency spillway covers Q10, OK!

- End -
PROJECT : NURI PAGOH P3B - OSD 2 Date: 3/13/2020

SIZING OF ON-SITE DETENTION (OSD) STORAGE SYSTEM


Reference : MASMA 2nd Edition 2012 - Chapter 5 : On-Site Detention

Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 9076.47 m2 = 0.908 ha

iii) Terrain = Low-lying


iv) % of impervious area = 90%

Calculation References

Permissible Site Discharge (PSD/ha) = 63.1 liter/s/ha From Table 5.A1


Project area = 0.908 ha
PSD = 63.1 x 0.908
= 57.295 liter/s
= 0.057 m3/s

Site Storage Requirement (SSR/ha) = 572.7 m3/ha From Table 5.A1


Project area = 0.908 ha
SSR = 520 m3

Inlet Flow/ha = 221 liter/s/ha From Table 5.A2


Project area = 0.908 ha
Inlet Flow = 200.67 liter/s
= 0.201 m3/s

PSD/ha = 63.1 liter/s/ha From Table 5.A2


Project area = 0.908 ha
PSD = 57.295 liter/s
= 0.057 m3/s

SSR/ha = 572.7 m3/s From Table 5.A2


Project area = 0.908 ha
SSR = 520 m3

Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.057 m3/s

Selection of Inlet & Overflow Pipe ( whichever is smaller )


Based on Table 5.A3 : Intlet pipe = 505.13 mm diameter For Region 5, Mild terrain,
90% Impervious project area

Based on Table 5.A4 : Intlet pipe = 452.45 mm diameter with inflow =0.201
Mild Terrain

Selection of Outlet Pipe ( whichever is smaller )


Based on Table 5.A3 : outlet pipe = 185.76 mm diameter For Region 5, Mild terrain,
90% Impervious project area

Based on Table 5.A4 : outlet pipe = 288.7 mm diameter with PSD =0.057
Mild Terrain

Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 520.0 m3

Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.201 m3/s
PSD (Outflow) = 0.201 m3/s
Inlet Pipe = 452.45 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300

Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.057 m3/s
PSD (Outlet flow) = 0.057 m3/s
Outlet Pipe = 185.76 mm
According to Manning's Equation, use = 300 mm Dia, 1: 300

SIZING OF OSD TANK

Storage required = 520.0 m3


Length = 33.00 m
Width = 16.00 m
Area = 528 m2

Depth (Internal Depth) = 1.00 m

Storage provided = 528.00 m3 OK!

SIZING OF OUTLET

Outlet Opening Area = 70685.835 mm2


No of Outlets = 3 Outlets
1 Outlet Area = 23561.945 mm2
Outlet Square Opening = 153.49901 mm x 153.49901 mm

Approximate Max 1 Outlet Area = 150 mm x 150 mm


Used Single Outlet Area = 150 mm x 150 mm OK!

SIZING OF OVERFLOW

Overflow Weir Length = 1884.9556 mm


No of Exposed Sides = 3 Sides
1 Exposed side Length = 471.2389 mm = 480 mm
Total Exposed Length = 1440 mm
Square Overflow Weir = 471.2389 mm x 471.2389 mm

Approximate Min Overflow Length = 480 mm x 480 mm


Used Overflow Length = 500 mm x 500 mm OK!

Weir Base Width, B = 1.5 m

According to Table 2.7 and Equation 2.10 of MSMA Chapter 2,


From Table 2.7 and Equation 2.10
of Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.6 m
Spillway discharge Coefficient, Csp = 1.46

Emergency Spillway Discharge, Q = 1.018 m3/s

Q10 = C*i*A = 0.81 A


360

Q10 = 0.73548 m3/s Since emergency spillway covers Q10, OK!

- End -