OSD + Spillway Spreadsheet
OSD + Spillway Spreadsheet
Dtails :
i) Kuala Lumpur (Klang) falls under region 1 = west cost
ii) Project area = 2341 m2
= 0.23 ha
iii) terrain = mild
iv) % of impervious area = 90%
Calculation references
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.014 m3/s
Based on Table 5.A4 : Intlet pipe = 286.5 mm diameter with inflow =0.055
Provide pipe size = 300 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 240.4 mm diameter with PSD =0.014
Provide pipe size = 300 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.014 m3/s
= 14.0 l/s
Depth= 1.00 m
- end -
PROJECT : SEKOLAH INTEGRASI KAFA AL-HIDAYAH Date: 14/5/2018
Dtails :
i) Kuala Lumpur (Klang) falls under region 1 = west cost
ii) Project area = 2341 m2
= 0.23 ha
iii) terrain = mild
iv) % of impervious area = 90%
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.014 m3/s
Based on Table 5.A4 : Intlet pipe = 286.5 mm diameter with inflow =0.055
Provide pipe size = 300 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 240.4 mm diameter with PSD =0.014
Provide pipe size = 300 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.014 m3/s
= 14.0 l/s
Depth= 1.65 m
- end -
PROJECT : NURI PAGOH Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 16416.52 m2 = 1.64 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.103 m3/s
Based on Table 5.A4 : Intlet pipe = 635 mm diameter with inflow =0.362
Provide pipe size = 650 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 342.14 mm diameter with PSD =0.103
Provide pipe size = 350 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.103 m3/s
PSD = 103.0 l/s
SIZING OF OUTLET
SIZING OF OVERFLOW
According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.9 m
Spillway discharge Coefficient, Csp = 1.58
- End -
PROJECT : NURI PAGOH Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 14583.13 m2 = 1.46 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.092 m3/s
Based on Table 5.A4 : Intlet pipe = 589.645 mm diameter with inflow =0.323
Provide pipe size = 600 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 317.3 mm diameter with PSD =0.092
Provide pipe size = 350 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.092 m3/s
PSD = 92.0 l/s
SIZING OF OUTLET
According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.9 m
Spillway discharge Coefficient, Csp = 1.61
- End -
PROJECT : NURI PAGOH - OSD 1 Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 16919.141 m2 = 1.692 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.107 m3/s
Based on Table 5.A4 : Intlet pipe = 648.87 mm diameter with inflow =0.374
Provide pipe size = 650 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 345.7 mm diameter with PSD =0.107
Provide pipe size = 350 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.107 m3/s
PSD = 107.0 l/s
SIZING OF OUTLET
SIZING OF OVERFLOW
According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.8 m
Spillway discharge Coefficient, Csp = 1.47
- End -
PROJECT : NURI PAGOH - OSD 2 Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 6845.7898 m2 = 0.68 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.043 m3/s
Based on Table 5.A4 : Intlet pipe = 394.75 mm diameter with inflow =0.15
Provide pipe size = 400 mm diameter Mild Terrain
Based on Table 5.A4 : outlet pipe = 273.3 mm diameter with PSD =0.043
Provide pipe size = 280 mm diameter Mild Terrain
Summary :
PSD (whichever is smaller from Table 5.A1 and A2) = 0.043 m3/s
PSD = 43.0 l/s
SIZING OF OUTLET
According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation 2.10 of
Chapter 2 - MSMA 2nd Edition
Effective Head of Spillway Crest, H = 0.6 m
Spillway discharge Coefficient, Csp = 1.396
- End -
PROJECT : NURI PAGOH P3A - OSD 1 Date: ###
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 15125.87 m2 = 1.513 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.095 m3/s
Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 866.5 m3
Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.334 m3/s
PSD (Outflow) = 0.334 m3/s
Inlet Pipe = 568.5 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300
Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.095 m3/s
PSD (Outlet flow) = 0.095 m3/s
Outlet Pipe = 236.55 mm
According to Manning's Equation, use = 300 mm Dia, 1: 100
SIZING OF OUTLET
SIZING OF OVERFLOW
According to Table 2.7 and Equation 2.10 of MSMA Chapter 2, From Table 2.7 and Equation
2.10 of Chapter 2 - MSMA 2nd
Effective Head of Spillway Crest, H = 0.8 m Edition
Spillway discharge Coefficient, Csp = 1.47
- End -
PROJECT : NURI PAGOH P3A - OSD 2 Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 4985.94 m2 = 0.50 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.032 m3/s
Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 286.4 m3
Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.111 m3/s
PSD (Outflow) = 111.0 l/s
Inlet Pipe = 350.65 mm
According to Manning's Equation, use Pipe Culvert = 450 mm Dia, 1: 300
Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.032 m3/s
PSD (Outlet flow) = 32.0 l/s
Outlet Pipe = 137.5 mm
According to Manning's Equation, use Pipe Culvert = 300 mm Dia, 1: 300
SIZING OF OUTLET
- End -
PROJECT : NURI PAGOH P3B - OSD 1 Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 11023.97 m2 = 1.103 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.070 m3/s
Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 631.7 m3
Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.244 m3/s
PSD (Outflow) = 0.244 m3/s
Inlet Pipe = 501.4 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300
Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.070 m3/s
PSD (Outlet flow) = 0.070 m3/s
Outlet Pipe = 203.294 mm
According to Manning's Equation, use = 300 mm Dia, 1: 300
SIZING OF OUTLET
SIZING OF OVERFLOW
- End -
PROJECT : NURI PAGOH P3B - OSD 2 Date: 3/13/2020
Details :
i) Region = Region 5 - Southern Coast
ii) Project area = 9076.47 m2 = 0.908 ha
Calculation References
Smaller PSD value computed based on Table 5.A1 and 5.A2 is adopted for sizing of outlet pipe
Thus, PSD adopted = 0.057 m3/s
Based on Table 5.A4 : Intlet pipe = 452.45 mm diameter with inflow =0.201
Mild Terrain
Based on Table 5.A4 : outlet pipe = 288.7 mm diameter with PSD =0.057
Mild Terrain
Summary :
SSR (whichever is larger from Table 5.A1 and A2) = 520.0 m3
Inflow / Overflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.201 m3/s
PSD (Outflow) = 0.201 m3/s
Inlet Pipe = 452.45 mm
According to Manning's Equation, use = 600 mm Dia, 1: 300
Outflow:
PSD (whichever is smaller from Table 5.A1 and A2) = 0.057 m3/s
PSD (Outlet flow) = 0.057 m3/s
Outlet Pipe = 185.76 mm
According to Manning's Equation, use = 300 mm Dia, 1: 300
SIZING OF OUTLET
SIZING OF OVERFLOW
- End -