Professional Documents
Culture Documents
Design Guide Structural Brick Veneer Wscpa PDF
Design Guide Structural Brick Veneer Wscpa PDF
FOR
Prepared for:
Submitted by:
The Design Guide for Structural Brick Veneer was sponsored by Western States Clay
Products Association and written by KPFF Consulting Engineers. Principal-in-Charge
for KPFF was John G. Tawresey. The preparation of the report was directed by the
Technical Committee of the Western States Clay Products Association. The authors are
appreciative of the help provided by Jim Anderegg, Mutual Materials Company, James
Amrhein, Gregg Borchelt, Brick Institute of America, Jeff Elder, Interstate Brick
Company and Don Wakefield.
John G. Tawresey, KPFF Consulting Engineers prepared the 2004 Second Edition.
The material presented in this publication, including technical and engineering data,
figures, drawings and tables, is for general information only. It should not under any
circumstances be relied upon for specific applications of the Structural Brick Veneer
without independent evaluation by a licensed design professional familiar with its
specific use and application. Anyone making use of this material does so at their own
risk and assumes any and all liability resulting from such use.
All rights reserved. No part of this publication may be reproduced, stored in a computer or retrieval
system or transmitted in any form or by any means, electronic, mechanical, photocopy, fax, recording or
otherwise, without the prior written consent of the author or Western States Clay Products Association.
Summary
Structural Brick Veneer is a unique approach to the design and construction of brick
exterior walls. Strengthening the brick with steel reinforcement provides new opportuni-
ties for reducing the cost of the wall, increasing design flexibility and improving wall
performance. In use for more than thirty years, the approach has been used extensively
in the Pacific Northwest.
The Structural Brick Veneer system is similar to conventional brick veneer except that
the brick is reinforced to allow it to span further between ties and supports. The system
allows the architect a variety of opportunities to create traditional walls or dramatic brick
forms. Sloping windowsills, brick soffits, lintels without exposed ledger angles and
precast concrete bands and inserts are only a few examples of the design opportunities
available.
In areas of high seismic exposure, the Structural Brick Veneer system can be easily
isolated from the primary structure making “immediate occupancy” performance more
cost effective.
The following document will provide the structural engineer and the architect with an
introduction to the design and specification of the Structural Brick Veneer system. It
includes some design examples and dialogue on our experiences with the system over
the past 20 years.
List of Figures
FIGURE 1 TYPICAL HOLLOW BRICK ...............................................................................................................................8
FIGURE 2 TYPICAL STRUCTURAL BRICK VENEER CONNECTOR ......................................................................................8
FIGURE 3 BRICK SUPPORTED ON A LEDGER....................................................................................................................8
FIGURE 4 TYPICAL STRUCTURAL BRICK VENEER DEADLOAD CONNECTOR ...................................................................8
FIGURE 5 DEAD LOAD ON THE FOUNDATION ..................................................................................................................9
FIGURE 6 FLEXIBLE CONNECTORS..................................................................................................................................9
FIGURE 7 SLOPING SILL BRICK SOFFITS .......................................................................................................................10
FIGURE 8 BRICK SOFFIT ...............................................................................................................................................10
FIGURE 9 PRECAST IN STRUCTURAL BRICK VENEER ....................................................................................................11
FIGURE 10 BRICK EXPANDING RESISTED BY THE REINFORCEMENT .............................................................................12
FIGURE 11 CRACKED BRICK .........................................................................................................................................17
FIGURE 12 DIFFERENTIAL VERTICAL DEFLECTION.......................................................................................................18
FIGURE 13 HORIZONTAL DRIFT JOINT ..........................................................................................................................18
FIGURE 14 CORNER CONNECTED TO THE STRUCTURE ..................................................................................................19
FIGURE 15 CORNER NOT CONNECTED TO THE STRUCTURE ..........................................................................................19
FIGURE 16 HOSPITAL - PROJECT 1 ................................................................................................................................21
FIGURE 17 PROJECT 1 – PIER CONCEPT BETWEEN WINDOWS ......................................................................................22
FIGURE 18 LATERAL CONNECTION...............................................................................................................................22
FIGURE 19 DRIFT JOINT BEFORE LEDGER INSTALLATION ............................................................................................23
FIGURE 20 LEDGER INSTALLATION ..............................................................................................................................23
FIGURE 21 PROJECT 2...................................................................................................................................................23
FIGURE 22 HOSPITAL WITH MANY CORNERS ...............................................................................................................24
FIGURE 23 TEMPORARY RIGID FOAM BOARD SUPPORT ...............................................................................................24
FIGURE 24 CONSTRUCTION SEQUENCE .........................................................................................................................25
FIGURE 25 BUILDING WITH ANTICIPATED DIFFERENTIAL SETTLEMENT .......................................................................25
FIGURE 26 CONCEPT FOR SETTLEMENT ........................................................................................................................26
FIGURE 27 STIFFNESS OF BRICK MASONRY ..................................................................................................................27
FIGURE 28 STRIP SYSTEM EXAMPLE ............................................................................................................................29
FIGURE 29 SUPPORT FOR THE WALL ............................................................................................................................29
FIGURE 30 BRICK USED IN THE EXAMPLE ....................................................................................................................30
FIGURE 31 PLAN VIEW OF CONNECTOR........................................................................................................................32
FIGURE 32 SIMPLE LATERAL CONNECTOR ...................................................................................................................34
FIGURE 33 FINAL DESIGN .............................................................................................................................................36
FIGURE 34 LOCATION OF CONNECTORS .......................................................................................................................36
FIGURE 35 PLAN VIEW OF CONNECTOR........................................................................................................................37
FIGURE 36 DEAD LOAD CONNECTOR ...........................................................................................................................38
FIGURE 37 DEAD LOAD MOMENT ................................................................................................................................38
FIGURE 38 RESISTING MOMENT ...................................................................................................................................39
FIGURE 39 WARPING CORNER ......................................................................................................................................41
FIGURE 40 FLUID GROUT .............................................................................................................................................43
FIGURE 41 PROTRUDING FLASHING DETAIL .................................................................................................................45
FIGURE 42 FLUSH FLASHING DETAIL ...........................................................................................................................45
FIGURE 43 VARIATION OF FIELD MORTAR TESTS ........................................................................................................54
FIGURE 44 MORTAR 7 DAY AND 28 DAY TESTS ...........................................................................................................54
FIGURE 45 VARIATION OF FIELD GROUT TESTS ...........................................................................................................54
FIGURE 46 SEVEN DAY AND 28 DAY GROUT STRENGTH ..............................................................................................55
3.0 Design................................................................................................................................................................12
3.1 Who Designs the Wall? ..............................................................................................................................12
3.2 Design Criteria .............................................................................................................................................13
3.3 Designing the Wall ......................................................................................................................................21
3.4 Design Examples ........................................................................................................................................29
The Structural Brick Veneer system is The purpose of this guide is to provide
similar to conventional brick veneer the architect, structural engineer and
because it supports no gravity loads owner with information about the design
other than its own weight, the weight of and construction of Structural Brick
windows, and possibly other miscella- Veneers. It is intended to be easily
neous loads. The difference is that in understood by someone experienced
the Structural Brick Veneer system the with reinforced brick masonry design
masonry is reinforced to allow the brick and construction. For those not familiar
to span further between ties and provide with the design of reinforced brick
structural capacity to create more intri- masonry, the Western States Clay
cately shaped walls. Products Publication, “Notes on the
Selection, Design and Construction of
Structural Brick Veneer can be laid in Reinforced Hollow Clay Masonry” is
place similar to conventional brick ve- recommended.
neer, or they can be prefabricated at
another location and lifted and installed As the design and construction of
to their final position. reinforced brick masonry varies from
location to location, so does the design
The system has many advantages over and construction of Structural Brick
conventional brick veneer. Some of Veneer vary from location to location.
these advantages are: The information and recommendations
in this guide are based on the design
1. Greater design flexibility. and construction of projects in the
2. Reduced backup requirements. Pacific Northwest and are not intended
3. Enhanced design life through heav- to replace local experience and engi-
ier connections. neering judgment.
4. Reduced tie connections, which
provides more continuous moisture 1.2 History of the System
barrier.
5. Greater seismic resistance and The origin of Structural Brick Veneer
more ductility. dates back to the early sixties. In 1962,
6. Less restrictive deflection require- a mechanical equipment penthouse was
ments of the backup structure. built on top of the nine-story United
7. Reduced cost of the backup system. Fund office building in Denver,
8. Often lower construction cost. Colorado. The 15-foot high, load
bearing, 4-inch thick clay brick This thinner reinforceable, hollow clay
prefabricated panels supported long unit was more economical, ductile,
span, prestressed, twin-tee concrete flexible and more predictable; thus
slabs that were the roof structure of the expanding its use in commercial cur-
penthouse. This construction was made tainwall systems as well as load-bearing
possible by the use of a new "tensile residences, four-story load-bearing
strength intensive" exotic mortar and apartment buildings, and prefabricated
some backup steel reinforcing. panels.
This 4-inch brick and exotic mortar During the 1970's, a similar system was
system was used for several years developed and perfected by Barkshire
thereafter in the Colorado area in Panel Systems, Seattle, WA. Bark-
prefabricated and in situ, hand-laid brick shire’s system used a 3 1/2-inch thick
panel and curtainwall applications on hollow clay brick similar to the one
many commercial buildings designed by mentioned earlier and verified by testing
George Hanson, P.E. of the firm of conducted by Western States Clay
Sallada & Hanson, Engineers. This Products Association under the direction
strong thin-wall system intrigued the of John G. Tawresey.
designers who used this system on hori-
zontal soffits, cantilevered balcony The secret to Barkshire’s system was
railings, post-tensioned panels, load- advancements in the connections to the
bearing and non-load-bearing walls on frame, and the technical knowledge of
schools, office buildings, hospitals, the the overall building's physical needs.
walls in vehicular tunnels, highway rest
area toilet modules and picnic shelters. As a consequence, the system is found
Even though this brick curtainwall on multi-story high-rise office buildings,
system was very successful, it was rela- schools, apartment buildings, resi-
tively expensive due to the use of the dences and many other applications
high tensile strength mortar. throughout the Northwest.
plate
plate
embed
angle
structural chapters of the code, height The design of the Structural Brick
limitations are generally more liberal. Veneer is based on the following princi-
ples:
loading, the designer has more choices Brick soffits can be designed and
to configure and attach the wall. The constructed similar to the conditions at a
number of different forms is controlled sloping sill.
only by the designer’s imagination.
will shrink with drying and expand with The Structural Brick Veneer System
moisture. Extra reinforcement may be provides two methods of weather
added to reduce the impact of this ef- protection. The exterior brick veneer,
fect. caulking, and windows act as the
primary barrier. The interior cavity,
Brick with Precast Concrete flashing, weeps, window channels and
other elements act as the secondary
Precast concrete window sills and barrier.
heads as well as accents can be suc-
cessfully included in a Structural Brick The system performance depends to a
Veneer System. Where the precast large extent on the prevention of water
elements are small, they can be added leakage through the reinforced brick.
by providing holes through the precast Reinforced brick is more water-resistant
for the reinforcement. Large precast than unreinforced brick. The most
components may require separate obvious reason is that the cracks are
connectors to the building frame or to smaller and more evenly distributed due
the Structural Brick Veneer. to the resistance provided by the rein-
forcement.
Caulk joint at
the end of the Another reason is that brick expands
precast
with age. When the brick is made, it
contains no water. With time, the brick
absorbs water and reaches equilibrium
with its moist environment. The clay
expands (just like unfired clay). The
moisture can come from the humidity in
the air. This expansion can take years.
There are two concepts used to control 3.1 Who Designs the Wall?
the water. The first is the drainage wall,
and the second is the “rainscreen” Structural Brick Veneer, like other wall
principle. systems, can be designed by either the
design team and bid, or it can be speci-
A drainage wall consists of a secondary fied as a bidder-designed item. It is done
method of removing the moisture once it both ways.
Some owners complain to their architect the design of curtainwall systems is not
that the design is incomplete without considered part of Basic Services. It is
drawings and specifications to bid the considered Additional Services under
exterior wall. It is like “buying a car Special Services. Unfortunately, the
without the wheels.” Yet, contractors document does not provide us with help
design most exterior walls because they for the bracing and stiffening problem.
have special knowledge necessary to Nor does it show where to draw the line
complete the task. of responsibility between the contractor
and the structural engineer of record.
Questions that should be addressed
early in the design of any wall system No matter who designs the wall, the
include the following. How much of the contractor or the engineer of record, the
design of the wall should be shown on following information about the design
the design drawings? Where does the criteria and methods applies.
designer of record’s responsibilities end
and the contractor’s responsibilities 3.2 Design Criteria
begin?
The design criteria for Structural Brick
Often, the structural engineer of record Veneer includes the applicable code
does not show bracing because he is sections, the appropriate design life,
unaware of the wall system to be used seismic performance, loads, allowable
and the method of attachment is left to stresses, code prescriptive requirements
the contractor. The designer should and special connection requirements.
clearly identify on the drawings the
responsibility for the design and 3.2.1 The Applicable Code Sections
construction of each component of the
wall system, including bracing. The term “Structural Brick Veneer” may
cause some confusion when applying
In some locations, it is common for brick the building code. The use of the term
veneer supports to be shown on the “Veneer” implies “non-structural”. How-
design drawings. In Seattle, it is common ever, the structural analysis of the
for the structural engineer of record to Structural Brick Veneer uses the
design precast concrete panels as part of structural portions of the masonry
the “standard services”. In most loca- design codes. But, they are used in
tions, including Seattle, the contractor combination with the performance
prepares the design of Structural Brick criteria of the masonry veneer sections
Veneer. of the code.
The NEHRP provisions also distinguish criteria, Structural Brick Veneer offers
between building uses by assigning each significant advantages. If high seismic
structure a Seismic Use Group. performance criteria are combined with
a complex geometry, sills, soffits and
1. Group III are essential facilities re- articulated surfaces, it is likely that
quiring post-earthquake use. Structural Brick Veneer will be the least
2. Group II are facilities with a large costly system.
number of occupants.
3. Group I are all other facilities.
3.2.4 Design Loads
Combining the performance classification
Loads applied to a Structural Brick
with the occupancy distinction results in
Veneer include dead load, wind load,
the following chart describing expected
and seismic load. The Structural Brick
seismic performance.
Veneer should support no vertical load
Immediate
other than its own weight. In normal prac-
Operational
Occupancy
Life Safety Near Collapse
tice, it may also support the weight of
Frequent Performance for Group I buildings window systems, small air handling units
Earthquakes (50% in
50 years and possibly some ornamentation.
Design Earthquake
Most modern building codes contain two
(2/3 of MCE)
Performance for Group II buildings levels of loading, service loads (allowable
stress design) and ultimate loads
Maximum
Considered
Performance for Group III buildings
(strength design). Both levels of loading
Earthquake (2% in 50
years) are used in the design of Structural Brick
Veneer. Local jurisdictions must be
consulted for the correct design load
The building code is not specific about
criteria.
the seismic performance of curtainwall
and Structural Brick Veneer. Judgment is
3.2.5 Design Assumptions and Allow-
required on the part of the engineer to
able Stresses
develop appropriate seismic criteria
based on the project performance objec-
Working Stress Design
tive. For example, failure of a Structural
Brick Veneer over the firehouse door
Working stress design methods are
during a major earthquake is not accept-
recommended. Strength or limit states
able. Whereas, complete separation of a
design methods are still in the develop-
Structural Brick Veneer from the frame
ment stage and have not been exten-
on a suburban office building with
sively used for the design of structural
surrounding planters may be acceptable.
brick or Structural Brick Veneer. The ACI
530-02/ASCE 5-02/TMS 402-02 Build-
Because of the nature of the connec-
ing Code Requirements for Masonry
tions, Structural Brick Veneer can be
Structures contains a new strength
designed to perform to a higher seismic
design section, Chapter 3. It may offer
performance level than conventional
less conservative designs for Structural
veneer. For buildings with operational
Brick Veneers resisting out-of-plane
performance or immediate occupancy
wind and seismic loading particularly 4. The concrete shear friction equation
when compared to allowable stress is assumed to apply with a friction
design that does not allow a one-third factor of 0.4, (Av.= Vu / I Fy ). The
increase in allowable stress for load ultimate shear is taken as 2.0 times
combinations, including wind or seismic the design shear.
loading.
5. The tension allowable stress of the
Allowable Stresses brick mortar interface is typically
neglected.
The allowable stresses permitted in the
Structural Brick Veneer are the same as 6. The tensile capacity of the brick is
those allowed for structural reinforced assumed to be 10% of the com-
masonry. The one-third increase in pression capacity. The allowable
allowable stress is typically used for load stress is determined by applying an
combinations, including wind and seismic appropriate factor of safety for the
loads. load condition being considered. This
allowable is for the brick, not the
The design of connectors requires addi- masonry. The code provides allow-
tional allowable stresses not typically able tension values for the masonry
included in the building codes. These in tension parallel and perpendicular
additional required allowables are as to the bed joints and for different
follows: bonding patterns and mortars.
1. The shear cone capacity of masonry 7. The allowable bond stress to plane
for pull-out is typically taken as the steel is assumed to be 60 psi. or the
beam allowable shear stress (1.0 x same value as the allowable bond
(f ’m)1/2 d50 psi). stress to plane bars.
the wall, while seemingly static, is in fact Horizontal Isolation in the Plane of the
subject to a variety of different move- Wall
ments in all three directions.
Lateral forces from wind and seismic
Vertical Isolation loading cause horizontal movement of
the building frame. When one floor
The vertical movement can result from moves horizontally relative to the adja-
several different sources. The following cent (higher or lower) floor, the wall sys-
figure shows one source. tem must accommodate the movement.
If the Structural Brick Veneer is attached
to both floors, then the veneer would
resist the lateral forces and possibly fail.
The amount of differential horizontal
movement can be large; up to four
inches is common in areas of high
seismic activity.
v e r tic a l is o la tio n
Vertical Steel or Differential L/600 <0.60 inch 1/4s Compensation channel at the win-
concrete application dow head
Floors of live load
Concrete Shrinkage (2) (3) 1/16s Allow the concrete to dry and cure
with drying before installing the veneer
Vertical Steel Differential (2) (3) (3) Only applies to high-rise buildings
elastic where the veneer is installed prior
Columns shortening to finishing the building frame
Concrete Shrinkage (2) (3) 1/16s Allow the concrete to dry and cure
before installing the veneer
Lateral Frame of Wind (2) .0025H 3/8s Usually absorbed elastically in the
steel or system
concrete
Per analy-
Seismic sis Depends on 21/2 TO Compensation channel at the win-
Minimum occupancy 3s dow head
½s
Per analy-
Seismic sis Depends on 1/4 TO Compensation channel at the win-
Minimum occupancy 1/2 s dow head
½”
1. This table should not be used for design. Each project has unique requirements.
2. No known values.
3. Depends on the structure.
The discussion describing the design of A hospital project was in the contract
a Structural Brick Veneer wall will be document phase of design. The archi-
divided into four parts: tect’s concept for the wall was brick
veneer over metal studs. Unfortunately,
1. The layout or configuration. the design had assumed only a 9-inch
2. The design of the wall for code pre- thickness for the wall: Three and one half
scribed loading. inches of brick, a 1-1/2 inch cavity and 4s
3. The design of the wall to prevent deep steel studs. The floor height was
cracking of the brick. 14c-8s
4. The design of the connections.
to support the wallboard without thicken- Lateral bracing at the floor consists of
ing the wall. The solution was to provide galvanized 1/8-inch thick plate with
a 4" thick (specified thickness is 3.5") holes for vertical reinforcement. This
Structural Brick Veneer wall system brace is flexible in the vertical direction
supported as shown in the following and stiff in both horizontal directions.
Figure.
The seismic or drift joint is located at the
window head, below the ledger. The
drift joint at the window head joint directly below the ledger is a caulk
joint. Another lateral brace is located
below the ledger. This brace is stiff
perpendicular to the plane of the wall
window
angle
girt
side
plates
lateral brace
Figure 17 Project 1 – Pier Con-
cept Between Windows
Figure 18 Lateral Connection
The brick masonry is supported on
continuous angles located at the window This configuration reduced the spans
head. These angles, or ledgers, are sufficiently to allow the 4" brick to resist
supported on a girt system suspended the applied loading.
from hangers with kickers framing back
to the underside of the slab. The stud wall was 26-gauge steel studs
and was used only for the support of the
water barrier and air barrier, and interior
wallboard.
Project 2
Figure 21 Project 2
Figure 20 Ledger Installation
This Structural Brick Veneer was de-
signed to accommodate a large lateral
brace
foam board was placed on the brick.
Brick was then laid on top of the foam
seismic
joint board for a height of two feet above the
floor. This masonry engaged the dead
floor lateral
connector load connector. At this time, the wall
was grouted and allowed to cure for
three days. Masonry was then laid to
several courses above the window head
and the process repeated for each floor.
floor dead load connector
Caulk was placed over the face of the
foam board that was left in the wall.
Figure 22 Hospital with Many
Corners
d e a d lo a d
c o n n ec tor
The corners of the box resisted the wind
and seismic loading perpendicular to the
surfaces of the wall. The reaction of the
wind and seismic load occurs in the
dead load anchors as shear and over-
turning. Where corners were spaced too
rig id f o a m
far apart to span between them, braces
were added to the underside of the slab
for the floor above at a sufficient dis- s e is m ic jo in t
Project 3
floor 4
A final example is a combination of laid-
in-place Structural Brick Veneer and
seismic joint
prefabricated Structural Brick Veneer or
brick panels. Brick panels are similar to
second grout pour
window
constructed of reinforced brick instead of
reinforced concrete. The project was built
on fill with friction piling used to support
the load. The foundation design was
such that ½ inch of differential settlement
first grout pour
tively few.
panels were hung off the Structural Brick simple configurations or at connectors for
Veneer columns with connectors that cantilevered configurations. Both hori-
allowed them to pivot while being stiff for zontal and vertical reinforcement should
loads perpendicular to the surface. be provided because most walls behave
as plates with moments in both direc-
The columns were constructed of 8" brick tions. The design often proceeds,
and reinforced. They supported the however, by assuming simple spans with
entire dead load of the wall, but the full loading in each direction.
lateral connectors to the building were
flexible in the vertical directions so that Maximum spacing of reinforcement
none of the building dead load was sup- should be less than 4 feet with 3 feet a
ported on the brick. The panels were common value. Typically, bar sizes are
constructed of 4" brick. They were No. 3 and 4 bars in 4 inch walls and No.
shipped 600 miles from the fabrication 3, 4 and 5 bars in 5 inch and 6 inch walls.
yard to the building location.
In areas of high shear, additional
reinforcement may be required.
panel Reinforcement should also surround
connectors and openings.
ties often (to the untrained eye) appear to rigid and moves with the floor to which it
oversize the connections. is attached.
U = As / bd
3.5”
Where As is the area of flexural rein-
forcement, b is the width or thickness of
the masonry and d is the depth of the
flexural element from the extreme
compression fiber to the centroid of the
reinforcement.
Figure 30 Brick Used in the Ex-
ample U = .22 in2 /(3.5 x (78 - 4))
expression for the location of the neutral However, as will be seen later, the
axis can be obtained: lateral support (for wind and seismic
loading) will need to be 10 foot. Thus,
k = [(nU)2+2nU]1/2 - nU the hanger could be spaced at 20c, but
the braces back to the underside of the
k = .12 slab will need to be at 10c.
A convenient term “j” is defined as: The wind load on the wall is 30 psf. This
load acts perpendicular to the surface of
j = (1 -k / 3) = .96 the brick and the window.
The moment capacity limited by the Assume floor connections are spaced at
allowable reinforcement stress is 10 foot at the same location as the
defined as: lateral support of the ledger.
Mc = 3.5 x 742 x .12 x .96 x The moment about the ledger due to the
1333/(2x12) wind loading on the brick is:
By summing forces perpendicular to the Where the design depth is one-half the
surface of the brick, the ledger lateral wall thickness (1.75 inches), and the
reaction is: stress has been increased by 1/3 for
wind short duration loading.
RL = 12.5 ft x 30 psf x 10 ft - RF
Try (4) #4 bars. The brick module is 6
RL = 703 lbs inches. The code allows an effective
width for bending of six times the thick-
Drawing the shear and moment dia- ness of the wall. The width for design
grams reveals that the maximum can be obtained by laying out the bars in
moment occurs at the floor and is equal the brick cells:
to the moment on the brick due to the
window sill load plus the moment on the
brick due to the wind on the brick:
Mw = 30 psf x 3 ft x2.5 ft
Mw = 225 lb-ft/ft
Ma = Mw + Mb
Figure 31 Plan View of Connector
Thus:
And:
Ma = 318.75 lb-ft/ft
U = As / bd
and over the 10 foot spacing becomes:
U = 4 x.2 in2 /(1.75 in x 39 in)
Ma = 3187.5 lb-ft
U = .0117
An estimate of the required reinforce-
ment can be obtained as follows: nU = .113 , k = .37 j = .87
Mt = As j d Fs Mw = 30 psf x 3 ft x 102 /8
The condition of inertia seismic and I = (78/2) x 3.53 /12 = 139.3 in4
dead load is also satisfied by inspection
since the inertia seismic load was The stress is:
assumed less than the 30 psf wind load.
This conclusion by inspection can easily V = Mc/I
be made when designing the veneer,
but should not be so easily made when V = 1782 x 12 x 1.75 / 139.3
designing connectors. This is because
most seismic codes have special load V = 269 psi
factors and additional criteria for seismic
connector design that are not typical for The brick unit should have a tensile
the wind design of a connector. strength in excess of 269 psi times the
factor of safety. If 1.25 is used, then the
The final check is for cracking of the tensile strength needs to exceed 335 psi.
brick.
According to an unpublished test and
Assume a service load of 15 psf. The experience, to achieve an f ’m of 4000 psi
value selected should relate to the the brick strength probably exceeds
design life and the performance criteria 10,000 psi. Using the 10% rule of thumb,
selected for the project. the expected tensile strength of the brick
is 1000 psi.
The uniform horizontal loading of the
strip between the connectors is a result A simple lateral connector at the floor is
of the wind load acting on the windows shown in the following figure. It consists
and brick. The moment is estimated as: of an embedded WT 4 x 5 with a coupler
welded to the flange for the attachment
Mw = 15 psf x 3 ft x 10 2 / 8 of a rod.
Mw = 562.5 lb-ft
Mb = 15 psf x 6.5 ft x 10 2 / 8
co up le r
Mb = 1218.7 lb-ft
rod
Ma = Mw + Mb
Ma = 1782 lb-ft
Assuming a 20 degree slope at the edge The shear friction check results in:
of the cone, the approximate surface
area of the cone is: Av.= Vu / I Fy
or
A = Length x width x 2 Vu.= I Av Fy
20 '
12.5 '
2.5 '
3.0 '
#4 typ.
Limited testing of connectors has been The veneer is assumed to have a verti-
conducted. One recent test conducted by cal expansion joint at 20 feet on center.
Western States Clay Products Associa- From the previous example, the horizon-
tion validated the design methods for the tal span of the brick is limited to less
connection shown above. Other tests than 10 feet. Thus, a lateral anchor at
specific to special connections on the floor and a brace will be required at
projects have been conducted. They are the mid point of the panel.
unpublished, but also verify the above
methods. The design dead load, after the wall is
constructed, is the same as the previous
3.4.2 Example 2 example.
The same strip window system is used Placing the dead load anchors away
for Example 2 except that the dead load from the columns will avoid interference
support is now on separated connectors with the building structure and make the
located at the floor. Shoring will be used installation easier. Assume the dead
to construct the wall. The design exam- load anchors are placed at 2 feet from
ple is for the in-place condition only. In the column line. A vertical expansion
actual practice, the designer of the joint is assumed at the column. The 2
Structural Brick Veneer would design feet dimension was chosen as the
the system for the shoring conditions as center of the head joint so that the
well as the in-place condition. connector is centered on the head joint
and an even number of bars will pass
The following figure presents the new through the connector. If an odd number
layout of the connections. of bars passes through the connector,
then the anchor would be located at the
center of a cell. Two feet three inches or
two feet nine inches from the expansion Summing forces perpendicular to the
joint would be examples. veneer results in the horizontal brace
` force:
The reaction load on the dead load
connector is: Rbrace = 30 x 12.5 - 281 = 94 lb/ft
R=wxL/2
The maximum moment again occurs at
R = 296 x 20 ft / 2 = 2960 lbs the floor line and is:
From the previous example, the wall can Ma = 318 x 6 = 1908 lf-ft
support this load.
The layout of the connector at the
The bending out of plane on the wall column is shown in the following figure
due to wind is assumed reacted by and results in 5 contributing #4 bars.
braces one foot above the bottom of the
brick and at the floor. The reaction at the
floor can be found by summing
moments about the location of the brace
as follows:
2.5”
tolerance
1”1”
Ma = 2960 x 5.75 in
Ma = 17,202 lb-in
The shear friction method can also be The bearing of the brick wall on the
used: horizontal leg of the angle is seldom
Av.= Vu / I Fy limiting in design and is satisfied here by
or inspection.
Vu.= I Av Fy
Now check assuming the moment is in
Vu = .4 x 6x.2 x 60,000 the floor. By inspection, the brick veneer
is adequate. The design of the plate,
Vu = 28,800 lbs welds and embedded plate is all that is
required. Assume the worst situation of
P = 28,800 / 2 = 14,400 lbs ok the tolerance for the edge of slab results
is 3 inches of connection between the
The 2003 International Building Code slab embed and the plate.
requires the fasteners and body of the
connector to be designed to equation The analysis is the same as would be
9.6.1.3-2 which is a maximum value. performed for a precast concrete panel
Lower values are likely for many or other wall system. Examples can be
structures using equation 9.6.1.3-1. found in many references.
the design level is: Notice that the size of the weld exceeds
the thickness of the plate. This is
F = 49.6 psf /1.4 = 36 psf. because the design factors of safety for
the weld loaded by seismic forces was
This is higher than the design wind load assumed larger than that required for
of 30 psf and controls. the body of the connection.
The resulting stress in the brick is: yield strength should be compared to the
ultimate cracking strength since this part
V=Mc/I of the design is for ultimate seismic.
V = 1186 x 120 x 1.75 / 134
4.0 Specification
V = 1860 psi
The Structural Brick Veneer System
If the entire wall height were assumed to consists of several components that
resist the displacement, the stress would must be specified and detailed. The
not change because the stiffness following discussion should help in this
increases in proportion. Because the process.
stress exceeds the likely tensile capacity
of the brick, the wall will crack. 4.1 Quality Control and Assurance
4.2 Masonry
http://www.bia.org/html/frmset_thnt.htm,
Technical Note 41 Hollow Brick
Masonry.
masonry, the important property of the other available shapes. Connectors may
grout is to fill all of the space and voids, be shop-painted for Level 2 (commer-
and to make the connection between cial) installations. Connectors for Level
the reinforcement and the brick unit. The 1 (institutional) installations should be
strength is of secondary importance, hot-dip galvanized to meet ASTM A 123
since the brick unit compression Grade 65 requirements. Connectors that
strengths typically exceed 8000 psi. are not protected can possibly corrode,
stain the brick, and ultimately fail to
If an additive other than the Sika Grout resist the loading. Damage to galva-
Aid is used, a test should be performed nized coatings by welding or other field
to assure filling of the space and bond- installation practices should be repaired
ing to the units and reinforcement. This using cold galvanizing compounds.
likely means the preparing of a grout
sample panel and cutting it after curing The use of 300 series stainless steel is
to visually confirm the performance. generally not necessary and may be
subject to galvanic corrosion if placed in
The reinforcement is usually specified contact with galvanized steel.
as ASTM A 615 Grade 60. Deformed
bars are required and sizes are limited 4.4 Flashing/Weeps
by the thickness of the wall. Generally,
bars larger than No. 5 are not used. Continuous flashing is necessary for the
When reinforcement is to be welded, removal of water that enters the cavity
ASTM A706 bars should be specified. It space. In masonry, water enters the
is slightly more expensive but it can be surface of the wall and then gravity pulls
welded without becoming brittle. ASTM it downward. When the masonry is inter-
A706 bars can be identified by a “W” rupted by openings that provide a
mark on the bar. horizontal discontinuity, flashing is
required to intercept the water and direct
Joint Reinforcement is not recom- it out of the building.
mended for Level 1 projects. Experience
with galvanized metal in masonry on the Flashing material for the Structural Brick
exterior walls indicates a life of 30 years Veneer System is the same as the
or less. materials used in other types of brick
wall construction.
Reinforcement bars grouted into bond
beams will have an expected life greater Pea gravel, proprietary meshes or
than 30 years. screens above the flashing will help to
prevent mortar droppings from clogging
4.3 Steel for Connectors weep holes. Weep holes should be
spaced no more than 32 inches apart.
Connectors can be designed and Open head joint weep holes are
constructed in many forms. Most are recommended. Weep tubes and cotton
made from ASTM A 36 structural steel wicks often fail to function when they
angles, plate, rods, channels, tees and become clogged or damaged. Screens
water flow
the surface of the wall is in all directions,
a flashing that protrudes from the
surface intercepts the flow at caulk joint.
This is the weakest point for water to
penetrate the wall.
Figure 42 Flush Flashing Detail
4.5 Sealants
rain. By reducing the water that enters process, a conversion occurs in the
the wall, the repellent provides several repellent material that fully develops the
benefits, both aesthetic and related to hydro phobic (water repellent) proper-
engineering performance that would ties.
justify their use. Some of these
attributes are: An additional benefit to the manner in
which these repellents function is that
1. Efflorescence control. they tend to bond along the pore linings
rather than build films across the pore
2. Reduction of algae growth as a openings. This ensures that sufficient
result of the absence of moisture in vapor transmission can occur to main-
the pores and capillaries of the tain “breathability” in the assembly.
masonry. Repellent manufacturers state a repel-
lent life of up to 10 years, but there are
3. Atmospheric pollutants that are numerous projects in the Pacific North-
dissolved in precipitation are not west that have never had to have a
absorbed into the masonry. second application.
number of years, under the same type each floor, fire safing is required to stop
of exposure. Demand that the repellent smoke and heat from moving between
manufacturer’s application instructions floors. The safing can act as a bridge for
be followed. water to enter the building. Flashing
over the safing should be provided.
4.7 Backup Wall
4.9 Expansion Joints
Structural Brick Veneer installations do
not require a separate backup wall. A Expansion joints need to be provided at
backup wall is sometimes constructed various strategic locations in the
as a second air and water vapor barrier. Structural Brick Veneer wall system.
Many Level 2 (commercial) buildings do Expansion joint placement is dictated by
not require the extra water and air two considerations. First, expansion
protection since a well-designed joints may be provided in locations
drainage wall is often sufficient. where the brick wythe is likely to crack
and second, to provide isolation from
If a back-up wall is used, many options building movement. In Structural Brick
are available including metal studs with Veneer systems, the spacing of vertical
sheathing. The studs are typically not joints can be increased over that of
designed for the wind loading since the conventional veneers because the
brick wythe is structurally designed to reinforcement provides additional resis-
resist the wind. tance to cracking.
The joint size should be a minimum of need to prepare shop drawings detailing
twice the calculated amount to meet the the installation.
limitations of the compressibility of the
sealant. As a minimum, it is recom- Most mason contractors do not normally
mended that the joint not be less than prepare shop drawings for reinforcement.
3/8 inch. Thus, the responsibility for providing an
adequate set of shop drawings can
4.10 Window Anchorage become lost in the process of bidding.
The general contractor thinks the mason
Windows are usually anchored to the will prepare the shop drawings and the
Structural Brick Veneer and not to the mason thinks the general contractor will
backup wall. In some installations, prepare the shop drawings.
connectors are included in the design to
make the attachment. In other installa- Often, the mason contractor does not
tions, powder-actuated fasteners shot supply the reinforcement for the wall. The
into the masonry have been used to general contractor supplies it. The design
make the connection. The choice de- team should become aware of who will
pends on the loading and local practice. supply the reinforcement. It will have
some influence on how the project
5.0 Construction proceeds.
Several construction trades construct Once the general contractor and the
structural Brick Veneer. The dead load mason subcontractor have been
support angle (or connectors) and lateral selected, the engineer should verify the
braces are usually installed by the steel mason’s qualifications with the local
erector or the general contractor. These masonry institute and the local material
trades prefer to complete their work with suppliers. This information will be helpful
the completion of the building structural for determining the amount of time and
frame. But if this is done, the mason is effort that will be needed during
constrained by constructing the brick to construction.
match the installed connectors.
At an appropriate time, usually at least
For example, for a Structural Brick two months before the start of masonry
Veneer supported on a continuous construction, arrange for a
ledger, if the ledgers are all installed prior preconstruction conference to discuss
to the laying of the brick, it is nearly the masonry construction. Attendees
impossible to place the vertical should include:
reinforcement and grout the wall. It is
usually necessary to delay installation of 1. The mason contractor and foreman.
the ledgers until after the brick below is 2. The general contractor and
completed. superintendent.
3. The building official.
If a backup wall is constructed, it is 4. The architect.
usually installed by a different contractor 5. The special inspector, when required.
and at a different time than the Structural 6. The engineer.
Brick Veneer. Normal choices for the 7. The owner’s representative.
inside wall include masonry, concrete or 8. The brick supplier.
steel studs. For a Structural Brick Veneer 9. The window supplier.
System, however, the masonry and 10. The dry-wall installer.
concrete choices are unlikely because
the stiffness and strength of the backup Subjects for discussion include:
wall are no longer required.
1. Brick:
When metal studs are used, it is
common to sheath the outside face of Determine the availability and delivery
the stud to provide additional water and schedule of the selected brick. If the unit
air infiltration protection. The sheathing strength method is used to verify
must be installed before the Structural required masonry strength, verify that the
Brick Veneer. Thus, the connectors brick will meet the required strength.
typically penetrate the sheathing. This
requires additional coordination between
the trades.
Often the grouting demonstration panel Normally, test reports and inspection
can also be used as a color and quality reports go to the general contractor; then
control panel for the architect. to the architect; and then to the engineer.
Deviations from this normal procedure
3. Testing During Construction: should be discussed, defined and
documented.
Prism testing is recommended for each
5,000 square feet of wall. During 7. Submittals:
construction, three prisms constitute a
test, however, five are recommended. Verify that the required project submittals
Test the first one at seven days, the next have been approved or are in the
three at 28 days and hold the final process of being approved.
sample for testing in case of a problem.
8. Cleaning and Water Repellents:
If prism tests are conducted, grout and
mortar tests are usually not required. The procedures to be used to clean and
apply water repellents should be
4. Inspection: discussed. It is important that the mason
contractor verify the cleaning method
ACI 530-02/ASCE 5-02/TMS 402-02 with the unit manufacturer. If water
Building Code Requirements for repellent is to be applied, the method and
Masonry Structures. materials to be used should also be
verified with the brick manufacturer.
Proper water repellents do not seal the and often others, all come together at the
wall. Masonry must breathe. Painting sealant joints. The selected sealant and
contractors often are not experienced installation procedures should be
with applying water repellents to checked for compatibility with adjacent
masonry, and assuring understanding of materials.
proper methods is important.
12. Compliance Testing
9. Construction Sequence and
Schedule: Most Structural Brick Veneer projects
require compliance testing. When the
The successful installation of a Structural brick supplier is not experienced with the
Brick Veneer project requires co- system, testing of prisms in accordance
ordination of many trades (see previous with national standards should be
discussion). Ask the general contractor completed before construction begins.
questions to ensure that the construction Testing during construction is also
sequence and responsibilities have been generally required. During the pre-
defined. Discuss the schedule for construction conference, the compliance
inspection and testing. Discuss co- testing required should be communicated
ordination issues. One usually missed to all involved.
item is the coordination with the window
and door supplier. The design of the 5.4 Submittal Review
connections should be discussed.
Items submitted for review include the
10. Window Attachment: following:
The additive Grout Aid should be added The structural engineer should make site
to the grout as recommended by the visits to check on the progress and
manufacturer. quality of the work. This part of the
engineer’s scope of services is called
For batch-provided grout, the proportions construction observation. It is defined in
are normally described by weight. The AIA C141 Section 2.6.3 as:
weight proportions should be converted
to volume proportions for comparison “The consultant shall visit the site at
with ASTM C 476. intervals appropriate to the stage of
construction for This Part of the Project,
3. Unit certifications: or as otherwise agreed with the Architect
in writing, to become generally familiar
The unit manufacture should provide with the progress and quality of the Work
certificates that the masonry units comply completed for This Part of the Project
with the requirements specified. and to determine in general if the Work is
being performed in a manner indicating
4. Reinforcement shop drawings: that the Work, when completed, will be in
accordance with the Contract
These should be scheduled to provide Documents. However, the consultant
sufficient time for review and resubmittal shall not be required to make exhaustive
prior to construction. Experience has or continuous on-site inspections to
shown that rejection of the first set of check the quality or quantity of the Work
drawings is likely. for This Part of the Project. On the basis
of such on-site observations as a
5. Connector shop drawings: consultant, the consultant shall keep the
Architect informed of the progress of the
Shop drawings showing the detailing of Work for This Part of the Project and
reinforcement, connectors and embedd- shall endeavor to guard the Owner
ed items need to be submitted with against defects and deficiencies in such
sufficient time for review. work. (More extensive site representation
may be agreed to as an Additional
Service, as described in Paragraph 3.2).”
Experience has shown that the field- When prism (units) are tested prior to
testing of masonry is highly variable. construction and conform to the
The source of the variability can be the requirements, but do not conform to the
materials, the methods used to prepare requirements when tested during
the samples, the testing of the samples construction, the problem is probably in
and the interpretation of the results. the manufacturing of the prisms or there
Before rejecting a wall because of non- was a change in the testing procedures
conforming field-testing, the engineer or materials. The units should be tested
should carefully assess the possible (or re-tested). If the units still do not
causes of the field test non- comply, the code allows prism testing to
conformance and possibly remove and verify strength. Construct prism tests to
test samples from the actual wall. verify the strength.
Sometimes the brick tests prior to The field sampling and testing for mortar
construction are not performed and the compression strength is highly variable.
units are tested during construction and The following figure is a frequency
do not conform. In this case, a new distribution of field mortar compression
analysis may be required to verify tests taken from actual projects in
strength. One option is to use Strength California, Oregon and Washington.
Design provisions based on UBC Section There are a total of 205 mortar tests. The
2108. These methods are less sensitive coefficient of variation is 36%.
to low compression strength. But, the
engineer should be careful about excess
deflections and other serviceability
16
28 day strength = 441 + 1.31 * 7 day strength ( psi )
14 8000
12
10
6000
8
4
4000
2
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 2000
COMPRESSION STRESS
0
0 2000 4000 6000 8000 10000
28 DAY TEST (PSI)
40
2000 PSI SPECIFIED
30
testing.
FREQUENCY
25
20
10
fairly consistent from sample to sample. 0 1000 2000 3000 4000 5000
COMPRESSION STRESS
6000 7000 8000 9000
ed:
4000
Prisms fail to reach the 1. The testing lab has incorrectly 1. Instruct the lab to retest being
design strength. tested the prism, usually by not careful to follow the ASTM C 1314.
placing the prism correctly in the
machine or using a loading platen
that is too thin. Or the specimens
may have been damaged during
transportation. 2. Request that the contractor have a
lab retest the brick. If still too low,
2. The bricks are below the specified change the brick or redesign.
strength.
3. Check mortar proportions. Retest
3. The mortar is under specified the prisms.
strength.
4. Lab reported gross area stress 4. Have the lab correct the report.
instead of net area stress.
5. Re-test.
5. Lab stopped testing with first noise.
Welded bars are ASTM A 706 bars were not used. Inspect bars. A "W" symbol indicates
breaking off. type A 706. Use the correct bars.
Contractor is not Sometimes the responsibility for Write a letter to your client. Explain the
protecting his materials protecting the work is left with the consequences. Send a copy to the brick
or work. general contractor. He is saving manufacturer.
money. Sometimes the
responsibility is not well defined.
Cracks in the mortar 1. Shrinkage of the mortar joint. 1. Suggest the contractor decrease the
joints. cement content of the mortar and
increase the lime.
4. Too rapid drying. 4. Pre-wet the units. Wet the wall during
curing. Add lime to the mortar.
Shop drawings are not The requirement was missed or Write a letter to your client explaining the
prepared. "value engineered away". requirement. If the project is underway,
require an engineer familiar with the
design be on site full time.
The grout strength is This is normal. Explain that the prism does not fail in
specified at a minimum accordance with the weak link theory.
of 2000 psi, how can I
get a prism of 4000
psi.
The contractor wants The code restricts the grout lift to 6' The problem is blow-outs of mortar joints
to high-lift grout with even though the grout pour might and the ability to reconsolidate. In hollow
lifts larger than 6' be higher. clay, these problems are unlikely. Have
the contractor demonstrate the
procedure to you and the inspector.
The contractor doesn't Code requires clean-outs for high- In most Structural Brick Veneers the
want clean-outs. You lift, in order to remove the mortar shear stresses are low. It is usually
want high-lift grouting. droppings. possible to waive the clean-out
requirement.
The dowels out of the Improper placement of the dowels. Cut the unit cross webs to allow the
concrete foundation However, it is often very difficult to dowel to pass or drill in new dowels.
or ledger interfere get them in the right place. This Verify that all the dowels are required to
with the unit cross situation should not occur in a meet strength requirements. Do not,
webs. They miss the Structural Brick Veneer. allow the dowels to be bent.
cells.
The brick masonry is 1. A great deal of force is required 1. Find the reason for the cracking. It is
cracked, with cracks for this condition to exist. The likely that something needs to be
extending through the cause is likely a problem. corrected. Likely candidates include
units. frozen grout, foundation movement, or
thermal movement from adjacent
structure.
2. The bricks may have been 2. Verify the integrity of the units before
manufactured with the cracks. use. A quick check is to bang the bricks
together, If a ringing sound results
instead of a thud, then the bricks are
sound.
Corrosion of the joint 1. Too strong an acid cleaning 1. Pre-wet the wall and use industry
reinforcement. without pre-wetting the wall. cleaners as recommended by the
manufacturer of the units.
6.1 Air
6.2 Water
6.3 Structural