Structural Drawing-Himel Vaiya-01-03-2020
Structural Drawing-Himel Vaiya-01-03-2020
6"
SLAB SLAB
6"
6"
10"
7b) STIRRUP END DETAIL
6) COLUMN DETAIL 7) BEAM DETAIL
4"
135° 1.5" (i) (ii)
6a) MINIMUM MAIN BAR SPACING OF COLUMN 7a) SPACER BARS min 6"
CLEAR DISTANCE BETWEEN LONGITUDINAL BARS SHALL NOT BE LESS THAN
TO SUPPORT SECOND LAYER BARS IN BEAMS/SLABS, USE (IN BETWEEN BAR)
1"
I)1.5 TIMES BAR DIAMETER 25∅ SPACER BARS @ 30" C/C WHERE REQUIRED. min 6" min 6"
II)1.5 TIMES THE SIZE OF COURSE AGGREGATE NOR
STIRRUP IN BEAM
III)1.5"
6b) TIE ARRANGEMENTS IN COLUMN
10"
10"
7c) ROOF BEAM & COLUMN JUNCTION DETAIL WITH STIRRUP SPACING PLACEMENT
S
6"
S SLAB SLAB
10"
MIDDLE STIRRUP SPACING
Smallest of the following
2" 10mmØ@ S min"c/c. 1) S = Avfy/50bw. 1.5" (ii) (ii)
2) S = d/2.
SPACING (S) > 6" S S S
3) S = 24".
d
h
L/4 L/4
Main Reinforcement
d
SLOPE 1:6 (MAINTAIN BY TIE)
Ø10@4"c/c. Ø10@8"c/c.
2h
Joint of stirrups/ties center half of column length in each Bottom Splice
alternately at the main L
floor. If bars of different sizes are
bars on adjacent spliced then db should be of larger bar.
corners of the column
L/4
Lb
n1
FLOOR LEVEL 7d) LAP LOCATION :
i) FOR BEAM BOTTOM BAR, LAP NOT TO BE PROVIDED AT MIDDLE THIRD ZONE OF THE SPAN.
La OPENING
ii) FOR BEAM TOP BAR, LAP MAY BE PROVIDED AT MIDDLE THIRD ZONE OF THE SPAN.
c La. Lb ≤ 24"
6d-i) MAIN BAR SLOPE, TIE SPACING iii) NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE PLACE. IF MORE THAN 50% OF THE BARS
ARE SPLICED AT ONE PLACE, SPLICE LENGTH SHOULD BE INCREASED BY 30%.
iv) LAP SPLICES ARE TO BE CONFINED BY HOOPS WITH MAXIMUM SPACING OR PITCH OF d/4 OR 4" WHERE d a
IS THE EFFECTIVE DEPTH OF THE BEAM.
Offset Less than 3" v) FIRST STIRRUP SHOULD BE PLACED 2" FROM COLUMN FACE & REMAINING STIRRUP SHOULD BE SHOWN
FLOOR LEVEL AS PER DRAWING.
FLOOR LEVEL L1
Ø10@4"c/c.
So shall be least value of 7e) BEAM - SLAB DETAIL . 7f) PLAN OF COLUMN & BEAM JOINT
Ld=Development Length a) 8db (smallest longitudinal bar) REINFORCEMENT PATTERN: L1
Ø10@4"c/c. Ø10@8"c/c.
Offset Greater than 3" b) 24db (tie bar) Hook Must be provided. SLAB.
FLOOR LEVEL L/2 c) 1/2 (smallest dimension of
column)
Ld
n1,n2: THE NUMBER OF BARS WHICH ARE CUT OFF FOR OPENING
2"
d) 4" At least 6" extended.
BEAM COLUMN TIE a THE NUMBER OF EXTRA BARS ≥ n1/2 (TOP AND BOTTOM BARS)
L/4
FIRST TIE 2" FROM SUPPORT
So
COLUMN VERTICAL REINFORCEMENT b THE NUMBER OF EXTRA BARS ≥ n2/2 (TOP AND BOTTOM BARS)
2"
FLOOR LEVEL FLOOR LEVEL c THE NUMBER OF EXTRA BARS = 2-D12 (TOP AND BOTTOM BARS)
BEAM STIRRUP
6d-ii) COLUMN OFFSET 6d-iii) CONFINEMENT REQUIREMENTS OF COLUMN MAIN BEAM REINFORCEMENT
S-02
9) OTHER DETAILS 10. HOOK , ANCHORAGE & DEVLOPMENT LENGTH:
9a) OPENING IN R.C.C. WALLS AND SLAB 9f) TRANSVERSE REINFORCEMENT REQUIREMENTS FOR JOINTS
CONFINED BY STRUCTURAL MEMBERS
NOT LESS THAN TWO NO.16 BARS SHALL BE PROVIDED AROUND ALL DOOR AND 10a) HOOKS OF REBAR:
WINDOW OPENINGS IN R.C.C. WALLS. THE BAR SHALL BE EXTENDED BEYOND THE FOR ALL REBAR: PROVIDE 90° STANDARD HOOKS
CORNERS OF THE OPENINGS TO A DISTANCE EQUAL TO THE DEVELOPMENT (L-BENT) IF NOT SHOWN IN THE DRAWINGS.
LENGTH(D) BUT NOT LESS THAN 600mm.
10b) DEVELOPMENT LENGTH:
R.C.C. Slab (typical) Ldh=16db ALL BEAM AND SLAB RE-BARS SHOULD BE EXTENDED
R.C.C. Wall (typical) Ldh
INTO THE SUPPORT UPTO DEVELOPMENT LENGTH.
12db
D
D
h
4db ≥= 2.5" 6d REQUIREMENTS FOR
JOINTS NOT CONFINED BY DUCT BEAM.
Ø12 @ 200c/c 4-12mmØ
16" Cross tie STRUCTURAL MEMBERS PLAN
TRANSVERSE REINFORCEMENT
°
6db ≥= 3"
135
≥= MEMBERS
3" PLAN OF DUCT
12"
9g) ADDITIONAL BAR, FASTENING BAR IN BEAM (UNLESS SHOWN OTHERWISE IN THE DRAWING(S))
9d) SPECIAL REINFORCEMENT AT EXTERIOR CORNERS
OF BEAM SUPPORTED TWO -WAY SLAB DEPTH (D) " D ≤ 24" 24"≤ D ≤36" 36"≤ D ≤ 48" D≥ 48"
L/5 ADDITIONAL BAR NOT NECESSARY 2-D10 4-D12 n-D12
Beam 9e) BUNDLE BAR ≤ 12"
L/5
Bottom Bar
D
Top Bar SECTION
Splice bar
Beam B
BARS IN A BUNDLE MUST TERMINATE WITH AT LEAST
40 BAR DIA STAGGER EXCEPT WHERE THE BUNDLE FASTENING Ø8 mm @ 24"
L=LONGER CLEAR SPAN SPACING TERMINATED. FOR 3 BUNDLE BARS SPLICE LENGTH
AS POSITIVE REINFORCEMENT INCREMENT FACTOR IS 1.2 AND FOR 4 BARS IS 1.3
S-03
10e) RECOMMENDED END HOOKS 12. SECTION REINFORCEMENT DETAIL OF PARAPET WALL:
6" SEE DETAIL:Z 6"
BAR FORM AND BEND ANGLE BEND USED
6"
3"
6"
STIRRUPS
TIE/ r FASTENING
135° r = 1.25db 6 to 12
STIRRUPS BAR DIAGONAL
b m 8mm Ø @6"C/C 8mm Ø @ 6"C/C
6d 75m HOOP
3'-6"
≥ 8mm Ø @6"C/C
db
PRIMARY BEND-UP FOR
90° r = 2.5db 6 to 32
12db
REINF. EMBEDMENT
r
12" 12"
db BEND BAR 4" THICK L.C.C
SLAB 45° r = 5db 8 to 20 MAIN SLAB
IN SLAB
1 Extra 8mm
r
SECTION: 01
PART LONGITUDINAL SECTION OF PARAPET WALL
DETAIL: Z
8mmØ@6"C/C 8mmØ@8"C/C
6" 4-10mmØ 4-10mmØ
3"
11. SCHEDULE OF LINTEL
6"
3"
6"
3"
WIDTH OF LINTEL CLEAR SPAN 6"
3"
SIZE & REBAR
PLAN OF Z VERTICAL SECTION OF PLAN Z
4-10mmØ
5" UP to 6'-0"
6"
5" 6'-1" to 9'-0" 8mm Ø @ 6" c/c ii) ALL FALSE SLAB THICKNESS ARE 3" UNLESS INDICATED.
iii) ALL FALSE SLAB AND LINTEL BOTTOM (WITHOUT LIFT CORE LINTEL)
5" 7'-1" ABOVE FROM FLOOR LEVEL OR AS PAR INSTRUCTION OF
ARCHITECTURAL DRAWING.
4-10mmØ
iv) ALL OUT SIDE MEASUREMENT OF FALSE SLAB MUST BE RE-CHECKED
6"
6'-
81
5"
2"
5' -
12" 15" 12"
12"
12"
12"
4 4
C1 C2 C1
13'-2"
13'-2"
C2 C2 C2
12" 15" 12"
15"
15"
12"
3 3
41'-6"
41'-6"
14'-4"
14'-4"
12" C2 C3 18" C2 15"
12"
12"
15"
2 2
13'-0"
13'-0"
C2 C1 12"
12" C1 15"
12"
12"
12"
1 1
21'-0" 16'-0"
15'-3 2
9 "
38'-0"
2
15'- 1
1 "
A B C
S-05
A B C
38'-0"
21'-0" 16'-0"
6"
6"
4 4
6"
6"
6"
6" 6" 6"
C1 C2 C1
13'-2"
13'-2"
C2 C2 C2
6" 9" 6"
9"
9"
3 6" 3
6"
6"
6"
6" 6" 6"
41'-6"
41'-6"
14'-4"
14'-4"
6" C2 C3 9" C2 9"
6"
6"
6"
2 2
6"
6"
9"
13'-0"
C2 C1 6"
6" C1 9"
6"
6"
6"
1 1
6"
6"
6"
21'-0" 16'-0"
38'-0"
A B C
S-06
A B C
38'-0"
21'-0" 16'-0"
4 4
F1 F3 F1
13'-2"
13'-2"
F2 F4 F2
3 3
41'-6"
41'-6"
14'-4"
14'-4"
F2 F4 F2
2 2
13'-0"
13'-0"
F3 F1
F1
1 1
21'-0" 16'-0"
38'-0"
A B C
S-07
A B C
38'-0"
21'-0" 16'-0"
9'-0"
6'-0" 6'-0"
6'-0"
6'-0"
7'-0"
4 4
F1 F3 F1
13'-2"
13'-2"
6'-0" 9'-0" 6'-0"
F2 F4 F2
8'-0"
8'-0"
9'-0"
3 3
41'-6"
41'-6"
14'-4"
14'-4"
9'-0"
6'-0" 6'-0"
F2 F4 F2
9'-0"
8'-0"
8'-0"
2 2
13'-0"
13'-0"
9'-0"
6'-0" 6'-0"
F3 F1
F1
6'-0"
7'-0"
6'-0"
1 1
21'-0" 16'-0"
38'-0"
A B C
S-08
A B C
38'-0"
21'-0" 16'-0"
4'-712" 4'-41 2"
3'-0" 3'-0" 3'-0"
3'-6"
3'-0"
3'-0"
4 4
3'-0"
3'-0"
3'-6"
F1 F3 F1
13'-2"
13'-2"
4'-712" 4'-41 2"
3'-0" 3'-0" 3'-0" 3'-0"
4'-112"
4'-112"
4'-6"
F2 F4 F2
3 3
3'-101 2"
3'-101 2"
4'-6"
41'-6"
41'-6"
14'-4"
14'-4"
4'-712" 4'-41 2"
3'-112" 2'-1012"
3'-0" 3'-0"
3'-1012"
4'-6"
4'-0"
F2 F4 F2
2 2
4'-112"
4'-0"
4'-6"
13'-0"
13'-0"
F3
3'-0"
3'-0"
F1 F1
1 1
3'-0"
3'-0"
3'-6"
21'-0" 16'-0"
38'-0"
A B C
S-09
SCHEDULE OF INDIVIDUAL FOOTING AND REINFORCEMENT
TYPE LENGTH BREADTH THICKNESS REINFORCEMENT
L B D T1 T2 RL RS
F1 6'-0'' 6'-0'' 12'' 12'' 0'' 16mm @ 6" c/c 16mm @ 6" c/c
F2 8'-0'' 7'-0'' 15'' 12'' 3'' 16mm @ 6" c/c 16mm @ 6" c/c
F3 9'-0'' 7'-0'' 16'' 13'' 3'' 16mm @ 5" c/c 16mm @ 5" c/c
F4 9'-0'' 9'-0'' 18'' 15'' 3'' 16mm @ 5" c/c 16mm @ 5" c/c
PL
E.G.L.
3" 10mm Ø @5" c/c
( UP TO PL)
3" RS 3"
FOOTING DEPTH=8'-0"
D
RL
D RS
B D
2'-0"3"3" T1 T2
18"
D
RL
2 FEET SAND KHOA COMPACTION
3"
L L
PLAN OF FOOTING NOTE: THE FOUNDATION DETAILS SHOULD
BE AS SHOWN IN THIS FIGURE. Qa=2.5ksf
S-10
SCHEDULE OF COLUMN SIZE AND REINFORCEMENT
BELOW GROUND LEVEL GROUND TO TOP
COLUMN
ID NOS.OF COLUMN NOS.OF COLUMN
REINFORCEMENT SIZE REINFORCEMENT SIZE
15" 12"
C1 8-16mmØ 8-16mmØ
15"
12"
12X12 15X15 12X12
18" 15"
C2 10-16mmØ 10-16mmØ
12X15 15X18 12X15
15"
12"
21" 18"
C3 12-16mmØ 12-16mmØ
12X18 15X21 12X18
15"
12"
LEGEND
16mmØ
20mmØ
25mmØ
S-11