TRENCH WIDTH TRENCH WIDTH

UNDISTURBED SOIL

VARIABLE, DEPENDING

3" CLR.
6" MIN.

6" MIN.
UPON PIPE SIZE
AND SOIL CONDITION

15# ROOFING
FELT PAPER
6" MIN.

PIPE

6" MIN.
PIPE

3" CLR.
O.D. AROUND PIPE
O.D.
UNDISTURBED SOIL

#4 BARS (TYP.) 3" CLR.






TRENCH WIDTH

CONCRETE ENCASEMENT
2' JOINT
(VARIES) EACH SIDE
6" MIN.

MIN. DETERMINED
BY PIPE SIZE

MIN.
6"
90°

BEDDING


 



NOTES:
1. CONCRETE ENCASEMENT SHALL BE USED WHEN COVER IS LESS THAN 3 FEET.

2. ENCASEMENT TO BE PLACED AGAINST UNDISTURBED NATURAL GROUND OR FILL COMPACTED TO 90% RELATIVE
COMPACTION, UNLESS OTHERWISE SPECIFIED.

3. #4 STEEL REINFORCING BARS SHALL BE USED AS SPECIFIED.


4. TYPE OF CONCRETE ENCASEMENT TO BE USED WILL BE SHOWN ON PLANS TO MEET FIELD CONDITIONS.

5. WHERE SLOPE TRENCHES ARE USED, WALLS WILL NOT BEGIN TO SLOPE CLOSER THAN 12 INCHES FROM THE TOP
OF THE PIPE.

6. ENCASEMENT CONCRETE TO BE 450-C-2500, USE 560-C-3250 WITH REINFORCEMENT.

7. BACKFILL SHALL COMMENCE WHEN THE CONCRETE STRENGTH IS 75% OF THE SPECIFIED STRENGTH .

APPROVED: STANDARD PLAN N0.


CITY OF
/S/ SIMI VALLEY
STANDARD CONCRETE
DIRECTOR OF PUBLIC WORKS SV 40-60
Aug 28,2006 DEPARTMENT OF PUBLIC WORKS ENCASEMENT TYPE A, B, &C
DATE SHEET 1 OF 1