OVERCURRENT PROTECTION PART 2 QUIZ

©Stephen Brooks BEng CEng MIET


OVERCURRENT PROTECTION PART 2
Identify the common curves shown…
1000

100

Operating Time ( Secs )


10

__ _____________________

1.0 __ ______________________
__ ______________________

__ ______________________
0.1
1 10 100
Current ( multiples of Is )
OVERCURRENT PROTECTION PART 2
Identify the following relay types from their ANSI numbering..

67 50
OVERCURRENT PROTECTION PART 2
If the relay is set to 1.2 for the current pickup in the forward direction, will
the circuit breaker trip for the fault shown?

11,000V
A
1600 2000
11,000V / 230V 1200

800

400
800A
0
P1 S1

800/5 67
P2 S2
OVERCURRENT PROTECTION PART 2
Fill in the missing blanks

__________________

MTA
V
_______

_______
Zero Torque Line
OVERCURRENT PROTECTION PART 2
ANSWER : Identify the common curves shown…
1000

100

Operating Time ( Secs )


10

SI STANDARD INVERSE ( SI )

1.0 DT DEFINITE TIME ( DT )


VI VERY INVERSE ( VI )

EI EXTREMELY INVERSE ( EI )
0.1
1 10 100
Current ( multiples of Is )
OVERCURRENT PROTECTION PART 2
ANSWER : Identify the following relay types from their ANSI numbering..

67 50

Directional overcurrent Instantaneous overcurrent


OVERCURRENT PROTECTION PART 2
ANSWER : If the relay is set to 1.2 for the current pickup in the forward
direction, will the circuit breaker trip for the fault shown?

11,000V
A
1600 2000
11,000V / 230V 1200

800

400
800A
REVERSE P1 S1
0

800/5 67
P2 S2
The current is in the reverse direction so
the relay will NOT trip the circuit breaker
OVERCURRENT PROTECTION PART 2
ANSWER : Fill in the missing blanks
I

Maximum Torque Line

MTA
V
Operate

Restrain
Zero Torque Line