OVERCURRENT PROTECTION PART 2
Identify the following relay types from their ANSI numbering..
67 50
OVERCURRENT PROTECTION PART 2
If the relay is set to 1.2 for the current pickup in the forward direction, will
the circuit breaker trip for the fault shown?
11,000V
A
1600 2000
11,000V / 230V 1200
800
400
800A
0
P1 S1
800/5 67
P2 S2
OVERCURRENT PROTECTION PART 2
Fill in the missing blanks
__________________
MTA
V
_______
_______
Zero Torque Line
OVERCURRENT PROTECTION PART 2
ANSWER : Identify the common curves shown…
1000
100
SI STANDARD INVERSE ( SI )
EI EXTREMELY INVERSE ( EI )
0.1
1 10 100
Current ( multiples of Is )
OVERCURRENT PROTECTION PART 2
ANSWER : Identify the following relay types from their ANSI numbering..
67 50
11,000V
A
1600 2000
11,000V / 230V 1200
800
400
800A
REVERSE P1 S1
0
800/5 67
P2 S2
The current is in the reverse direction so
the relay will NOT trip the circuit breaker
OVERCURRENT PROTECTION PART 2
ANSWER : Fill in the missing blanks
I
MTA
V
Operate
Restrain
Zero Torque Line