The document contains a table with 24 rows listing signal types, descriptions, and paths for various measurements and relay statuses related to an electrical substation incomer panel. The measurements include current, voltage, power, and other readings. The relay statuses indicate breaker position, protection operations, and relay health. The signals involve both analog measurements and digital inputs and outputs related to the incomer breaker, transformer, and protective relays.
The document contains a table with 24 rows listing signal types, descriptions, and paths for various measurements and relay statuses related to an electrical substation incomer panel. The measurements include current, voltage, power, and other readings. The relay statuses indicate breaker position, protection operations, and relay health. The signals involve both analog measurements and digital inputs and outputs related to the incomer breaker, transformer, and protective relays.
The document contains a table with 24 rows listing signal types, descriptions, and paths for various measurements and relay statuses related to an electrical substation incomer panel. The measurements include current, voltage, power, and other readings. The relay statuses indicate breaker position, protection operations, and relay health. The signals involve both analog measurements and digital inputs and outputs related to the incomer breaker, transformer, and protective relays.
Sr No PANEL TYPE TECHNICAL KEY Feeder Type Signal Description Signal Type LN\PATH
1 SS62PC01P01R1 Incomer R phase current Measurement‐AI Measurements.PriRmsMMXU1.A.phsA.cVal.mag
2 SS62PC01P15R1 Incomer Y phase current Measurement‐AI Measurements.PriRmsMMXU1.A.phsB.cVal.mag 3 SS62MC11P10R1 Incomer B phase current Measurement‐AI Measurements.PriFRmsMMXU1.A.phsC.cVal.mag 4 SS62MC11P13R1 Incomer R‐Y line voltage Measurement‐AI Measurements.PriRmsMMXU1.PhV.phsA.cVal.mag 5 Incomer Y‐B line voltage Measurement‐AI Measurements.PriRmsMMXU1.PhV.phsB.cVal.mag 6 Incomer B‐R line voltage Measurement‐AI Measurements.PriRmsMMXU1.PhV.phsC.cVal.mag 7 Incomer KW‐Real Power Measurement‐AI Measurements.PriFouMMXU1.TotW.mag 8 Incomer KVAR ‐ Reactive Power Measurement‐AI Measurements.PriFouMMXU1.TotVAr.mag 9 Incomer PF‐ Power Factor Measurement‐AI Measurements.PriFouMMXU1.TotPF.mag 10 PCC/MCC Incomer Transformer in TROUBLE Measurement‐AI PLC PART 14 Incomer I.C‐1 BREAKER ON Relay‐DI System.OptGGIO1.Ind6.stVal 15 Incomer I.C‐1 BREAKER OFF Relay‐DI System.OptGGIO1.Ind7.stVal 16 Incomer I.C‐1 BREAKER IN SERVICE Relay‐DI System.OptGGIO1.Ind8.stVal 18 Incomer (Relay‐86) Trip Operated Relay‐DI System.RlyGGIO1.Ind3.stVal 19 Incomer Line PT MCB On Relay‐DI System.OptGGIO1.Ind10.stVal 20 Incomer Trip From ECS Relay‐DO 21 Incomer Close Inhibit From ECS Relay‐DO 22 Incomer Trip on Under Voltage PROTECTION Protection.VtpPhsPTUV1.Op.general 23 Incomer RELAY 95 Relay‐DO System.RlyGGIO1.Ind13.stVal 24 Incomer NUMERICAL RELAY UNHEALTH RELAY‐DI System.LPHD1.PhyHealth.stVal