Huawei Data Center Facilities Solutions

Catalogue

HUAWEI TECHNOLOGIES CO., LTD.


Power ICT in a Smart Way Modular Design, Beyond Reliability
1 Smart Modular Data Center
2 Huawei UPS Solutions
Solutions
32 UPS2000-A Series (1-3 kVA)
08 FusionModule2000 Smart Modular Data Center 34 UPS2000-A Series (6-10kVA)
10 FusionModule5000 Smart Modular Data Center 36 UPS2000-G Series (1-3kVA)
14 FusionModule800 Smart Small Data Center 38 UPS2000-G Series (6-20kVA)
16 FusionModule500 Smart Mini Data Center 40 UPS5000-E Series (25-75kVA battery integrated)
18 FusionModule1000A Prefabricated All-in-One Data Center 42 UPS5000-E Series (25-125kVA)
22 FusionModule1000A Prefabricated All-in-One Data Center 44 UPS5000-E Series (50-800kVA)
26 FusionModule1000B Prefabricated Modular Data Center 46 UPS5000-E Series (60-600kVA,60kVA Power Module)
48 UPS5000-S Series (50-800kVA)
50 UPS5000-A Series (30-120kVA)
52 UPS5000-A Series (200-800kVA)
54 FusionPower Series (UPS5000-S-1200kVA-FP)
56 Modular Precision Power Distribution Cabinet PDU8000
58 iBattery Intelligent Management Solution
Huawei Data Center Facilities Solutions Catalogue

Huawei Energy Powering the Future Digital Maintenance and Intelligent Operation
3 Huawei Smart Cooling Solutions
4 Huawei Management system

66 NetCol5000-A In-row Air Cooled Smart Cooling Product 82 iManager NetEco6000

68 NetCol5000-C030 In-row Chilled Water Smart Cooling Product


70 NetCol5000-C065 & C080 In-row Chilled Water Smart Cooling Product
72 NetCol8000-A013U In-room Air Cooled Smart Cooling Product
74 NetCol8000-A050D & A100D In-room Air Cooled Smart Cooling Product
76 NetCol8000-C In-room Chilled Water Smart Cooling Product
78 NetCol8000-E FusionCol Indirect Evaporative Cooling
1 Power ICT in a Smart Way
Huawei Data Center Facilities Solutions

04
05
Contents
Modular Data Center ���������������������������������������������������������������� 08
Prefabricated Data Center �������������������������������������������������������� 22

Indoor Modular Data Center

FusionModule2000&5000

FusionModule800
FusionModule500
FusionModule500

06
Outdoor Prefabricated Data Center

FusionModule1000B
FusionModule1000A

07
Modular Data Center
FusionModule5000 Smart Modular Data Center

Introduction
HUAWEI FusionModule5000 is a new generation smart modular data
center solution with complete integration of cabinets, power supply and
distribution systems, cooling systems, cabling systems, management
software, and other subsystems. It supports flexible deployment with
single or dual row, cold or hot aisle containment.

Application Scenarios
• Maximum IT power per module can be up to 310kW, which meet FusionModule5000 (Dual-row)
the requirements of large-scale data center for industries like ISP,
government, education, healthcare, finance, telecom, etc.
• Designed for chilled water cooling scenarios.

Features & Value


Reliable
• Single/dual power supply, Tier IV supportive, Precise monitoring of
power branch temperature prevents fire caused by loose contact and
overheat
• Water leakage monitoring keeps room away from flooding
• Ring network of monitoring system
• Warning of component expired, aging, damaged FusionModule5000 (Single-row)
• Optional aisle/cabinet-level door access keeps the data center safe

Efficient
• Closely coupled cooling to efficiently avoid partial hot spot, high-
density deployment supportive
• Hot/cold aisle containment for isolation of hot and cold air
• Local/remote monitoring, PAD or cell phone mobile O&M

Simple
• Standardized devices, modular architecture, on-demand deployment
• Busway for power distribution is optional , easy installation

08
Specifications

Item Specifications
Single-row with aisle containment (L×W×H (IT cabinets)):
L×2400×2000mm, L≤15 m
L×2300×2000mm, L≤15 m
L×2400×2200mm, L≤15 m
Dimensions
Dual-row with aisle containment (L×W×H (IT cabinets)):
L×3600×2000mm, L≤15 m
L×3400×2000mm, L≤15 m
L×3600×2200mm, L≤15 m
Cabinet number per
System Single row: 2-24; Dual row: 6-48
module
Power supply 380/400/415Vac, 50/60Hz, 3Ph+N+PE
IT power consumption per PDU inside: 310kW
module New Main Way inside: 396kW
Redundancy N+1/2N
Availability Tier II or Tier III (up to Tier IV)
Altitude 0-4000m (derating above 1000m)
Installation Installed on concrete or base support
2000mm×600/800mm×1200mm
Dimensions (H×W×D) 2000mm×600/800mm×1100mm
Cabinet 2200mm×600/800mm×1200mm
Space available 42U/47U
Protection level IP20
Cooling capacity 30/65 kW
2000mm×300mm×1200mm/
In-row chilled
Dimensions (H×W×D) 2000mm×600mm× 1200mm/
water smart
2200mm×600mm× 1200mm
cooling product
Power supply 200-240V (1Ph, 50/60Hz)
Refrigerant Water/Ethylene Glycol
Rated Voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Input MCCB Capacity 400/250A
Output MCB 16,40,63A/1P x6 routes or 16,40A/3P x2 routes
New Main Way Surge protection level-C SPD. In=20kA
Monitoring the voltage, current, power, power factor, temperature for
Monitoring function
key point, harmonic etc.
Communication Modbus
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Precision power
Rated capacity 400/250/160A
distribution
AC SPD 20kA, 8/20μs
cabinet (UPS
outside) 16A/20A/32A/40A optional, max branches up to 144 (single phase), or 48
Output
(three phase)

09
Modular Data Center
FusionModule2000 Smart Modular Data Center

Introduction
FusionModule2000 is a new generation of smart modular data center
product which had been awarded the World’s First "Uptime Tier IV
Ready" Certification. It is a module that comprises power, cooling,
rack & structure, cabling, and management. The structure of the
module can be single-row or dual-row, and supports both cold or hot
aisle containment. In addition, Huawei integrates AI technology into
the data center which significantly improves the reliability, availability,
and efficiency of the data center through iPower, iCooling, and
iManager. Dual row, Contained cold/hot aisle

Application Scenarios
•• Designed mostly for small-to-medium sized data centers
•• Suitable for enterprise HQ or large regional branch, operator,
bank secondary branch, government, education, healthcare, etc.

Features & Value


Modular design & automatic control
•• Designed for fast deployment & flexible expansion
•• eLight Module Status LED*, view operating status of each module more
clearly
•• Auto door* & smart lighting system for convenient inspection
•• System-level face recognition, more secure and reliable

i³ Smart Management System

iPower Single row, Contained cold/hot aisle


•• Whole power supply system visualized inspection, fault auto-locating
•• IT Circuit breaker terminal temp detection*, avoiding bad contract
•• iBattery* can provide battery real time inspection, proactive auto-shutdown
battery group, eliminating fire risk
•• Smart PDU* supports socket-level power inspection and remote control,
protecting IT devices
•• Output circuit breakers are hot swappable for secure online maintenance*
iCooling
•• Cooling system real time inspection & A/C key component status detection
•• 3D Visualized temp control system* eliminate existing hot spot, while IT load
& A/C interaction prevents the generation of hot spot
•• AI optimized cooling system*, saving 8-15% energy by optimum operating
status of A/C
•• Pioneering refrigerant volume detecting system, avoids decline of cooling
capacity
•• Wet film humidifier*, saving 95% humidifying power
iManager
•• 3D data center visualized management*, significantly increase O&M
efficiency
•• U-space level asset manager*, optimize DC facility usage automatically, "0"
manual asset managing needed
•• SPC (Space/Power/Cooling) management*, optimizing resource utilization of
data center

*: Optional Configuration

10
Specifications

Item Specifications
Single row (with aisle containment) (L×W×H):
L×2400×2410mm
L×2300×2410mm
L×2400×2610mm
Dimension
Dual row (with aisle containment) (L×W×H):
L×3600×2410mm
L×3400×2410mm
L×3600×2610mm
Cabinets per module Single row≤24 cabinets; dual row: ≤48 cabinets
Micro Module
Power supply 380/400/415Vac, 50/60Hz, 3Ph+N+PE
125kW (with integrated UPS)/ 145kW (with integrated PDC)/ 198kW (with
Max IT load per module
New main way)/ 235kW (with precision PDC)
Ultra low temperature condition: -40ºC to 45ºC(Need low-temp kit)
Operation condition T1 condition: -20ºC to 45ºC
T3 condition: -5ºC to 55ºC(Need T3 outdoor unit)
Cable routing Routed in/out through the top of cabinets
Installation Installing on concrete floor or raised floor
2000mm×600/800mm×1200mm
Dimensions (H×W×D) 2000mm×600mm×1100mm
Cabinet 2200mm×600/800mm×1200mm
Space available 42U/47U
Protection level IP20
Cooling capacity 25kW/46kW
2000mm×300mm×1100mm
Air-cooled In-row Dimensions (H×W×D)
2000mm×600mm×1200mm
air conditioner
Power supply 380V AC~415V AC 50/60Hz, 3Ph+N+PE
Refrigerant R410A
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Input 250/400A MCCB (single input); 250A/400A ATS (dual input)
Input power factor Full load > 0.99, Half load > 0.98
Integrated UPS Output power factor 1.0
(UPS inside) Rated capacity 25~125kVA
Output IT: 40A/1P×24×2; A/C: 40A or 63A/3P×8; lighting: 10A/1P×3
Efficiency ≥ 96%
AC SPD 5kA, 8/20μs
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE

Integrated power Input IT: 160/250A MCCB; A/C: 160/250A MCCB (single/dual input)
distribution cabinet Rated input current IT: 160A/250A, Air conditioner: 160A/250A
(UPS outside) Output IT: 40A/1P×24×2; A/C: 40A or 63A/3P×8; lighting: 10A/1P×3
AC SPD 20kA, 8/20μs

Precision power Input voltage 380/400/415Vac,50/60Hz,3Ph+N+PE


distribution cabinet Input 160/250/400A MCCB (single/dual input)
(UPS outside) Output 40A/1P, max 144 routes
Input voltage 380/400/415Vac,50/60Hz,3Ph+N+PE
Smart busway Input 250/400A MCCB (single input)
(UPS outside) 40/63A 1P (6 branches in one Power Distribution Unit, can be expanded
Output
with the length of cabinet)

11
Recommended Configurations——UPS Inside

Single-row Dual-row

IT IT IT IT IT IT IT IT IT IT IT IT IT

Air

Air

Air
R8-32kW R24-112kW
(aisle) (aisle)
Integrated

Integrated
Battery

Battery

Battery

Air
IT IT IT IT IT IT IT IT
Air

Air

Air

IT IT IT IT IT IT IT IT IT IT IT
Air

R8 single row module typical layout R24 dual row module typical layout

IT Load
Power Supply Redundancy AC Configuration Battery
(kW)

20 25kW×2

40 25kW×3

60 25kW×4 In-row (Battery


Integrated UPS N+1/2N cabinet)/Outside
80 46kW×3 Installation

100 46kW×4

125 46kW×5

12
Recommended Configurations——UPS Outside Installation Outside

Single-row Dual-row

Air conditioner

Air conditioner

Air conditioner
IT IT IT IT IT IT IT IT IT IT IT IT

R8-32kW R24-140kW
(aisle) (aisle)

Air conditioner
Air conditioner
Integrated PDC
Integrated PDC

Air conditioner

Air conditioner

Air conditioner

IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT

R8 single row module typical layout R24 dual row module typical layout

IT Load
IT Power Supply AC Power Supply Redundancy AC Configuration
(kW)

20 25kW×2

40 25kW×3

60 Integrated PDC/ 25kW×4


Integrated PDC/Precision PDC/Smart
Power Distribution
80 Busway 25kW×5
Box
120 N+1/2N 46kW×4

145
46kW×5
160
Power Distribution
200 Precision PDC 46kW×6
Box
235 46kW×7

13
Modular Data Center
FusionModule800 Smart Small Data Center

Introduction Electrical cable tray(Optional)

Data cable tray(optional)


FusionModule800 Smart Small Data Center is a new-generation data Spring to open Camera(optional)
center solution. It is integrated with PDU, UPS, monitoring , cooling and the door(rear)
Spring to open
the door(front)
rack system in a comprehensive rack in order to save space. IT racks Indicator light

can be deployed flexibly on both sides. A single module can support PDU
Glass door
maximum12 racks and 25kW IT load (T3: IT Load≤21kW), the maximum
UPS Touch
power density for each rack is 7kW/ R(T3:≤6kW). Cold and hot aisle Transformer
screen

(optional))
containment to saving Energy and reduce noise. Monitoring module
Aisle

Application Scenarios Air conditioners

• Finance, Education, Health Care, Public Security, SMEs, Retailing &


Merchandising, Edge DC, etc.
• Indoor modular data center
FusionModule800 Architecture

Features & Value


Simple
• Integrated cooling ,PDU,UPS and monitoring system in one rack,
footprint saving.
• All components are prefabricated in factories. only need to be
combined onsite, hardware are installed in 4 hours, 2 days business
on line.
• The local PAD supports facial recognition , easy login without
password.
• Support online maintenance through hot swap switches, local PAD
indicates the PUE through intelligent power distribution(only for BC6
FusionModule800 Application
and BC7).

Efficient
• Rack-mounted air conditioner saves at least one rack footprint.
600 to 7400mm
• Cold and hot aisle containment, saving energy and reducing noise.
• Improve the efficiency of cooling system through DC variable
frequency compressor, wet film humidification ,cold and hot aisle Hot aisle
ATS
containment. PDU
1100mm

Network IT IT ATS IT IT IT IT IT Battery Battery


UPS
• Real-time monitoring of mobile apps, centralized monitoring of cabinet cabinet cabinet
Monitoring
IT cabinet cabinet cabinet cabinet cabinet cabinet cabinet
multiple sits. cabinet (A/C:#3
A/C
#4)

Reliable
250mm

• Dehumidifying at min. 10% IT load avoids condensation risk. Cold aisle


• Automatic shutdown to prevent fire caused by battery overheating.
• Open rack doors automatically in case of cooling failure and the Maximum configuration:IT load 17~25KW(T1/LT),14kW~21kW(T3)
temperature exceeds the limit.
• When detect the fire alarm automatically open the rear door to let the
fire extinguishing gas enters.

14
Specifications
System features Centralized management for multiple DCs
Power system 380/400/415Vac, 50Hz, 3Ph+N+PE
Aisle containment Cold and hot aisle containment
System protection level IP20
T1*:-20℃~+45℃;
Ambient temperature T3*:-10℃~+55℃;
LT*:-40℃~+45℃;
Maximum cabinet quantity
12 LTE
for a module
Quantity of IT cabinets 0~10
25kW (T1* & LT*)
Maximum IT load
21kW (T3*) TCP/IP
7kW (T1* & LT*)
Max power density /Rack
6kW (T3*)
Mobile operation
IT cabinet weight Static load 1500kg, Dynamic load 1000kg
Total Dimensions
2000×(600-7400)×1350 Module1
(H×W×D mm) Management for
Cooling system single module ……
Power system 220/230/240Vac, 50Hz, 1Ph+N+PE
Cooling capacity 12.5kWa APP (local) Module 2 Module N
Operating temperature of T1*:-20℃~+45℃;
T3*:-10℃~+55℃;
the outdoor unit LT*:-40℃~+45℃;
Configuration N, N+1 WiFi
ECC800 data acquisition
Cooling mode Direct expansion air-cooled
Installation Rack- mounted
Air volume 2600m³/h
Air supply mode Front supply, rear return Battery UPS Cooling Temperature Water Door status Video
Power Supply and Distribution System and humidity sensor sensor
SPD CLASSII/C, In 20kA, Imax 40kA, 8/20us
Input power Single or dual inputs 7 Basic Configurations for T1/T3/LT
UPS capacity 10kVA 20kVA ≤8.5KW(T1/LT) 8.5KW~17kW(T1/LT)
UPS configuration N, N+1 IT load
≤7KW(T3) 7KW~14kW(T3)
UPS output power factor 0.9
Basic configuration BC1* BC2 BC3* BC4*
UPS rated input voltage 380/400/415Vac, 50/60HZ, 3Ph+N+PE
UPS input voltage range 138~485Vac, 40~70Hz, 3Ph+N+PE Aisle type Single row, cold & hot aisle containment
220/230/240Vac 380/400/415Vac UPS(KVA) 10+0 10+10 20+0 20+20
UPS rated output voltage
50/60Hz, 1Ph+N+PE 50/60Hz, 3Ph+N+PE
Smart cooling 1+0 1+1 2+0 2+0
UPS efficiency 94.5% 95%
Power input Single input is default (ATS optional)
Battery backup mode Battery pack, battery cabinet, battery rack
Backup time 15min/30min IT output 4 12 12 12
No-Intelligent rPDU: IEC or GB,on site Intelligent Power
NO NO NO NO
rPDU (Optional) installation distribution
Intelligent rPDU:IEC,on site installation
ATS (Optional) On site installation 17~25KW(T1/LT) ≤8.5KW(T1/LT) 8.5~17kW(T1/LT)
Maintenance bypass Standard IT load
14kW~21kW(T3) ≤7KW(T3) 7~14kW(T3)
Intelligent battery
Optional
monitoring system Basic configuration BC5* BC6* BC7*
Monitoring system
Aisle type Single row, cold&hot sealed
Mobile phone APP, SMS alarm, Web access,
Monitoring system
centralized management for multi-DCs UPS(KVA) 20*2+0 10+10 20+20
10 inched Pad Standard Smart cooling 3+0 1+1 2+0
Water sensor Optional
Power input Single input is default (ATS optional)
Camera Optional
Smoke sensor Standard IT output 20 12 12
Intelligent door lock Standard Intelligent Power
NO Yes Yes
Facial recognition Standard distribution
Temperature and humidity
Standard
sensor Note:
Local app on the mobile phone,SMS alarm 1, Basic configuration 1, 3,4,5,7 are only applicable to TierI DC.
2, The cooling capacity 12.5kW is obtained when the indoor dry bulb temperature is
Mobile O&M NetEco remote app on the mobile 37.8℃, and outdoor dry bulb temperature is 35℃,relative humidity 20%.
phone(optional) 3, ATS is optional and can be installed on site
4, T1:-20℃~ +45℃,LT:-40℃~ +45℃;T3:-10℃~ +55℃
5, BC1 cooling without heating and humidification, the others are all have one
cooling with heating and humidification
6, BC6 & BC7 are intelligient power distribution.
7, The Converged cabinet part number don't include cooling out door unit.three
type of outdoor unites are freely configured with the converged cabinet.

15
Smart Mini Data Center Solution
FusionModule500

Introduction
一体化架构 Integrated architecture
FusionModule500 smart mini data center solution integrate UPS, PDU,
monitoring, battery pack in a cabinet. All parts are prefabricated, pre- Monitoring
监控模块
installed, pre-tested. On-site installation is simple to achieve rapid
deployment. The remote monitoring function with web interface can
PDU
realize remote operation. At the same PDU
time, FusionModule500 can be
equipped with Huawei NetEco management system, achieving centralized
UPS UPS
monitoring and unified management.

电池包(可选) Battery pack


(Optional)
Feature
Simple
•• All-in-one design, preassembly, two-hours installation
•• Battery remote discharge, mobile phone APP, SMS alarm, remote web
platform control, Network centralized monitoring, realizing unattended
operation

Efficient
•• Rack DC, saving at least 50% space
Integrated cabinet
Reliable
•• Civil smart cooling product intelligent start, no risk of overheat
•• Battery overheating intelligent shutdown to prevent the fire

Application scenarios
•• Bank sites, education, enterprise branches, retail merchandising and
carrier business halls, etc.
Integrated cabinet+network cabinet
•• No need special data center room
or Integrated cabinet+battery cabinet
Netco management
Display screen
system

Integrated cabinet+network
Site 1 Site 2 Site n cabinet+battery cabinet

16
Specifications

Item Description 42U 24U


Power type 220/230/240Vac, 50/60Hz, 1Ph+N+PE
Temperature 0-40OC
Overall parameter
Humidity 5-95%
Altitude 0-4000m (1000 meters or more to reduce capacity)
Certificate Certificate CE, ROHS, REACH
Cabinet dimensions
600×2000×1100 600×1200×850
W×H×D (mm)
IT cabinet / IT cabinet+battery cabinet,
Cabinet system
IT cabinet+network cabinet,
Cabinet combination IT cabinet, IT cabinet+battery cabinet
IT cabinet+network cabinet+battery
cabinet
36U (no battery pack) 17U (no battery pack)
User space ICT space
24U (4 battery pack) 11U (2 battery pack)
System input Input switch capacity 32A (3kVA); 63A (6kVA,10kVA) 32A (3kVA); 63A (6kVA)
System 4×40A/1P+1×16A/1P (6kVA/10kVA) 4×40A/1P+1×16A/1P (6kVA/10kVA)
Input switch
output 2×16A/1P+3×10A/1P (3kVA) 2×16A/1P+3×10A/1P (3kVA)
Capacity 3kVA, 6kVA, 10kVA 3kVA
Configuration Single UPS
UPS
Power factor 0.9
Efficiency 94% (3kVA/6kVA), 94.5% (10kVA)
Vertical (6kVA/10kVAUPS)
Power Installation Horizontal
Horizontal (3kVAUPS)
system rPDU
Type IEC/GB
Configuration IEC: 20×C13+2×C19 IEC: 8×C13
Capacity 7AH, 9AH
Battery pack
Quantity 0-4 0-2
Power
Backup type Battery pack, Battery cabinet
backup
Battery
Backup time 15min-4H
cabinet
Monitoring ECC800e
Home A/C restart function Optional
SMS Optional
Remote mobile APP Optional
Liquid sensor Standard configuration
Monitoring system Tem&Hum sensor Standard configuration
Door magnetic switch Standard configuration
Smoke sensor Standard configuration
9.6-inch display (wifi module) Optional
Web monitoring Standard configuration
Camera Optional
Management system NetEco6000 Optional
Cooling system Heat radiation Natural heat dissipation
Package dimensions
734×2200×1268 734×1400×1068
W×H×D (mm)
Dimensions/weight
Integrated cabinet weight 144kg (no battery pack) 100kg (no battery pack)
Battery pack weight 61kg (7Ah), 69kg (9Ah)

17
Prefabricated Data Center
FusionModule1000A Prefabricated All-in-One Data Center

Introduction
Huawei FusionModule1000A is an advanced outdoor and prefabricated
all-in-one data center facility solution. The solution provides reliable, stable
and green environment for IT equipment. The solution can be applied to
multiple industries and scenarios and meet data center’s requirements on
energy saving and fast deployment.

Applicable Industry and Scenario


FusionModule1000A 40ft
Enterprise: small data center

Government: data center of smart city and safe city

Education: data center of university and science institute

Energy: data center of mining and exploration field

Finance: backup data center

Transportation: power supply for room of airport/railway station/port

Telecom carrier: small IDC, DR DC,edge DC

Features & Value


Simple
• Enclosure, power, cooling, firefighting , DCIM system ,server and switch
are 100% prefabricated.All faciliites and preinstalled and pretested
before delivery
• Produtized solution minimizes the engineering work and the on-site
installation of a plug& play data ceter only takes one day.
• Moveable design makes relocation easy and deployment flexibly.

Efficient
• High-efficiency modular UPS, smart in-row cooling, aisle containment,
enclosure of low heat transfer coefficient, industry-leading PUE
• Huawei NetEco system centralize the management of multiple sites. 3D
visualized managment, power&cooling monitoring enable smart O&M
• Efficient O&M anywhere& anytime with PAD and mobile APP

Reliable FusionModule1000A Site


• The world's first all-in-one product with Uptime TIER-III Ready
Certification
• Durable enclosure with 25-year servive life, IP55 protection (IP65
optional) and GR-63-CORE Zone3 anti-seismic 120min fire-resistance
when with customized fire-proof panel,EN 1627~EN 1630 Class 3
anti-theft(optional)
• 3D temperature map eliminate the risk caused by hot spots..Automatic
refrigerant detetion provides early-alarm on cooling running.

18
Layout

Layout
Integrated UPS Integrated UPS

IT cabinets Entrance IT cabinets Entrance room


room

Battery Battery
Cooling indoor units Cabinet Cooling indoor units Cabinet
Cooling Cooling
outdoor units Fire gas cylinder outdoor units Fire gas cylinder

FusionModule1000A-40ft-IT-2N FusionModule1000A-40ft-IT-N+X

Plan View

FusionModule1000A-40ft-IT-2N

① Cooling outdoor units ② Cold aisle ③ IT cabinet ④ Battery


cabinet

FusionModule1000A-40ft-IT-N+X

① Cooling outdoor units ② Cold aisle ③ IT cabinet ④ Hot aisle

⑤ Cooling indoor units ⑥ Battery cabinet ⑦ Integrated UPS ⑧ Entrance

19
Managment System

Notes: VCN, VESDA, hydrogen controller and three-in-


one reader are optional.

Local Display

Mobile Phone APP

Homepage Real-time Alarm Power Cooling Resource

20
Specifications
FusionModule1000A FusionModule1000A FusionModule1000A FusionModule1000A
System Sub-item System Sub-item
40ft-IT-N+X-380V ⑦ 40ft-IT-2N-380V ⑦ 40ft-IT-N+X-380V ⑦ 40ft-IT-2N-380V ⑦

Total IT load ≤ 54kW⑧ Automatic fire detection &


Auto fire protection
suppression system c/w emergency
system
Power density per release function
≤ 9kW
rack Fire protection Automatic monitoring and detection,
Alarm
support sound and light alarm
3Ph+N+PE,
Input mode Standard HFC-227ea optional
380V /400V/415V AC,50Hz/60Hz Gas
NOVEC1230

Integrated Integrated IC card reader as default


Module access
optional three-in-one access control
modular UPS modular UPS
UPS model (with integrated (with integrated Rack access Customization ⑥
ATS and 25kVA MCCB and 25kVA Real-time monitoring of temperature
Monitoring
module) module) and humidity control, fire control,
management
access control and cooling system
UPS capacity 75kVA Monitoring
Local display PAD
Power Number of UPS
3+1 redundancy 3 Remote O&M App
power module

BAT backup time ① 7.5min 10min E-mail Optional


SNMP short
1) Power density of 6kW/rack:basic Optional
message
type,full-height rPDU
A route:IEC320 20×C13+2×C19 DCIM NetEco
B route:IEC320 20×C13+2×C19
Basic rPDU
2) Power density of 9kW/rack:basic
type,half-height rPDU
Management Server Pre-installed
A route:(IEC320 9×C13+3×C19)x2
B route:(IEC320 9×C13+3×C19)x2 Lan switch Pre-installed
External size
Smart rPDU Optional 2896×2438×12192
(H×W×D)mm
Level-3, maximum 40kA 8/20us Enclosure Long aisle of 650/750mm;
Surge protection②
Level-2, maximum 60kA 8/20us Aisle width cold aisle of 1150mm;
hot aisle can be extended to 610mm;
Rack capacity ③ 8×42U IT rack 7×42U IT rack
Dustproof and
IP55 (optional IP65)
2×9kW/ 4×9kW/ waterproof
Rack distribution Rack+6×6kW/ rack+3×6kW/ GR-63-CORE Zone3(Equivalent to
Rack Protection Anti-seismic
Rack rack Mercalli Intensity 9)

600*1100*2000 mm Anti-theft EN 1627~EN 1630 Class 3(optional)


Size (H×W×D)
600*1200*2000mm
Operating humidity
5%~95%
Technology Air-cooled in-row (RH)
Operating
Environment Operating temp.④ -20oC~+55oC -40oC~+55oC
Sensible cooling
25kW/unit (3+1 redundancy)
capacity Altitude ⑤ ≤ 4000m
Coolant R410A

Fan type EC fan


① ③: The BAT backup time and rack capacity vary in configuration. Details refer to the
Product Overview.
Compressor DC variable-frequency
Cooling ②: Surge protection level vary in configuration. Details refer to the Product Overview.
A/C group control Support ④⑧: Low-temperature air-conditioner is required for -40oC to -20oC.When the temperature
is over 45°C,the IT load will be derated as follows: when 45oC< T ≤ 50oC, the derating
Temp. range 18~27oC coffiecient is 0.89;when 50oC < T ≤ 55oC,the derating coefficient is 0.58.
⑤: Power derating is required when the altitude is over 1000m.Details refer to the Product
Humidity range 20%~80% Overview
⑥: Customerized access control will cause changes to U space and monitoring solution.
Hot/cold aisle Hot aisle containment ⑦ N+X and 2N refers to redundancy level of power system. N+X refers to UPS module
redundancy. 2N refers to UPS unit redundancy.
Humidification Wet-film humidifier

21
Prefabricated Data Center
FusionModule1000A Prefabricated All-in-One Data Center

Introduction
Huawei FusionModule1000A is an advanced outdoor and prefabricated
all-in-one data center facility solution. The solution provides reliable, stable
and green environment for IT equipment. The solution can be applied to
multiple industries and scenarios and meet data center’s requirements on
energy saving and fast deployment.

Applicable Industry and Scenario


Enterprise: small data center
FusionModule1000A 40ft
Government: data center of smart city and safe city

Education: data center of university and science institute

Energy: data center of mining and exploration field

Finance: backup data center

Transportation: power supply room of airport/railway station/port

Telecom carrier: small IDC,DR DC,edge DC

Features & Value


Simple
• Enclosure, power, cooling, firefighting DCIM system,server and switch are
100% prefabricated.All faciliites and preinstalled pretested before delivery
• Produtized solution minimizes the engineering work and the on-site
installation of a plug& play data ceter only takes one day.
• Moveable design makes relocation easy and deployment flexibly.

Efficient
• High-efficiency modular UPS, smart in-row cooling, aisle containment,
enclosure of low heat transfer coefficient, industry-leading PUE
• Huawei NetEco system centralize the management of multiple sites.
• Efficient O&M anywhere& anytime with PAD and mobile APP

Reliable
• Durable enclosure with 25-year servive life
• IP55 protection (IP65 optional) and GR-63-CORE Zone3 anti-seismic
120min fire-resistance when covered with customized fire-proof panel,EN
1627~EN 1630 Class 3 anti-theft(optional)

FusionModule1000A Site

22
Layout

FusionModule1000A-40ft-IT-2N

Layout

IT cabinets Integrated UPS


Entrance
Room

Air conditioner Battery Fire gas


Air Conditioner indoor units cylinder
outdoor units Cabinet

Plan View

① A/C outdoor unit ② Cold aisle ③ IT cabinet ④ Battery cabinet

⑤ Hot aisle ⑥ A/C indoor units ⑦ Integrated UPS ⑧ Entrance room

23
Managment System

Notes: VCN, VESDA, hydrogen controller and three-in-


one reader are optional.

Local Display

Mobile Phone APP

Homepage Real-time Alarm Power Cooling Resource

24
Specifications
FusionModule1000A FusionModule1000A
System Sub-item System Sub-item
40ft-IT-2N-208V⑦ 40ft-IT-2N-208V⑦

Total IT load ≤ 42kW IC card reader as default


Module access
optional three-in-one access control
Power density per
≤ 6kW Rack access Customization ⑥
rack
Real-time monitoring of
3Ph+N+PE,
Input mode Monitoring temperature and humidity control,
208V /220V /230V AC, 60Hz
management fire control, access control and
cooling system
Integrated modular UPS( with
UPS model
integrated MCCB) Monitoring In-module display PAD

UPS capacity 60kVA Remote O&M App


Power
Number of UPS Smart U space
3 Optional
power module manager

BAT backup time ① 10min Cabinet


Temperature Optional
Basic type,full-height rPDU
sensor
Basic rPDU A route:IEC320 20×C13+2×C19
B route:IEC320 20×C13+2×C19
DCIM NetEco
Smart rPDU Optional
Management Server Pre-installed

Surge protection Level-2, maximum 60kA 8/20us
Lan switch Pre-installed

Rack capacity 7×42U IT rack
External size
2896×2438×12192
(H×W×D)mm
Rack distribution 7×6kW/rack
Rack
Enclosure Long aisle of 650/750mm;
Size (H×W×D) 600×1100×2000 cold aisle of 1150mm;
mm 600×1200×2000 Aisle width
hot aisle can be extended to
610mm;
Technology Air-cooled in-row
Dustproof and
IP55 (optional IP65)
Sensible cooling waterproof
21kW/unit(3+1 redundancy)
capacity
Protection Anti-seismic GR-63-CORE Zone3
Coolant R410A
Meet requirements of EN 1627~EN
Anti-theft
1630 Class 3
Fan type EC fan

Compressor DC variable-frequency
Cooling
Group control Support

Temp. range 18~27oC


① ③: The BAT backup time and rack capacity vary in configuration. Details refer to the
Humidity range 20%~80% Product Overview.
②: Surge protection level vary in configuration. Details refer to the Product Overview
Hot/cold aisle Hot aisle containment ④: Low-temperature air-conditioner is required for -40℃ to -20℃.
⑤: Power derating is required when the altitude is over 1000m.Details refer to the
Humidification Electrode humidifier Product Overview
⑥: Customerized access control will cause changes to U space and monitoring solution.
Automatic fire detection & ⑦ 2N refers to redundancy level of power system.
Auto fire protection
suppression system c/w
system
emergency release function

Automatic monitoring and


Fire protection
Alarm detection,
support sound and light alarm

Standard HFC-227ea, optional


Gas
NOVEC1230

25
Prefabricated Data Center
FusionModule1000B Prefabricated Modular Data Center

Overview
FusionModule1000B is a modular designed, prefabricated data
center. It comprises enclosure structure, power supply, cooling,
firefighting, lighting,and management systems. As an outdoor solution,
FusionModule1000B has outstanding environment adaptability and anti-
disaster ability. It is ideal solution to replace brick and mortar data center.

Application Scenarios
Prefabricated Modular Data Center
ICT Room Colo&Hosting

Regular Building-like
Appearance Appearance

Core network room/ Medium Cloud DC ,Colo&Hosting


ICT room/EDC/IDC DC and Hyper ISP DC

Features & Value


FusionModule1000B Air-cooled solution
Simple
•• 50%+ quicker TTM with prefabricated delivery
•• On-demand deployment with modular design
•• Easy scale-up with multiple floor stacking

Efficient
•• 2-year earlier ROI than that of traditional DC
•• PUE drop from 1.65 to 1.51 with iCooling(Middle East)
•• O&M efficiency increased from150 to 210 racks/person with
iManager

Reliable
•• Maximum 40-year long service life
FusionModule1000B Chilled-water solution
•• Mercalli scale-9 earthquake-proof and 120min fire-resistance
•• High protection level: IP55, IP65 (optional)

26
Specifications

System Specification

12192mm x 2438mm x 3600mm


12192mm x 3495mm x 3600mm
Multiple enclosure size
Enclosure
available(DXWXH)
12192mm x 2438mm x 4150mm
12192mm x 3495mm x 4150mm

Input power 380/400/415Vac,50/60Hz,3Ph+N+PE

Power equipment IT: Huawei UPS5000-E;CT:Huawei TP48 series


Power
Typical power density Air-cooled:3kW-10.5kW Chilled-water:3kW-20kW

Battery management Hauwei iBattery(optional)

Huawei Huawei
Huawei NetCol5000A
NetCol5000C NetCol8000C
Cooling mode In-row air-cooled PAC
In-row chilled- In-room chilled-
Cooling
water PAC water PAC

Aisle containment Cold/hot aisle containment

Fire Extinguishing Agent Standard: FM200; Optional: Novec1230

VESDA Standard in equipment, power and battery module


Fire Extinguishing
Hydrogen Detection and Discharge
Standard in power and battery module
System

Heat insulation 100mm thick rockwool sandwich panel

Standard IC card access, customizable multifunction (fingerprint,


Module access
password and IC card) access
Security Control
Rack access Customized IC card access

Video Surveillance HUAWEI HR IP Camera, connected to HUAWEI NetEco

Rack IT equipment module support installation of all types of IT rack

CT equipment module support installation of third-party CT rack

Temperature -40ºC-+52ºC*
Working
Relative humidity 10%-100%
Environment
Altitude ≦ 3000m

Protection
Water&dust proof IP55( optional IP65)

GR-63-CORE-zone3 (equivalent to mercailli intensity 9)


Earthquake proof
GR-63-CORE-zone4 (equivalent to mercailli intensity 11)(optional)

Fire resistance 120min(customized coating required )

IT scenario 2N or N+X

Availability CT & ICT scenario 2N

Comply both UPTIME TIER and TIA942 requirement.


Standard compliance
Support Uptime Tier II ,III and IV certification

*Under condition of +45ºC ~ +52ºC, the high temperature air conditioner is required. Under condition of -40ºC ~ -15ºC,the low temperature air
conditioner is required. Application in above mentioned high-temperature and low temperature environment will cause change to specifications 27
some parameters will change.
2 Modular Design, Beyond Reliability
Huawei UPS Solutions

28
29
Contents
UPS2000-A Series (1-3kVA)������������������������������������������������� 32
UPS2000-A Series (6-10kVA)���������������������������������������������� 34
UPS2000-G Series (1-3kVA)������������������������������������������������ 36
UPS2000-G Series (6-20kVA)���������������������������������������������� 38
UPS5000-E Series (25-75kVA Battery Integrated) ...............40
UPS5000-E Series (25-125kVA)������������������������������������������� 42
UPS5000-E Series (50-800kVA)������������������������������������������� 44
UPS5000-E Series (60-600kVA,60kVA Power Module) �������� 46
UPS5000-S Series (50-800kVA)������������������������������������������� 48
UPS5000-A Series (30-120kVA)������������������������������������������ 50
UPS5000-A Series (200-800kVA)���������������������������������������� 52
UPS Li-ion Battery Solution������������������������������������������������ 54
FusionPower Series (UPS5000-S-1200kVA-FP) �������������������� 58
Modular Precision Power Distribution Cabinet PDU8000����� 60
iBattery Intelligent Management Solution�������������������������� 62

UPS2000-G Series
(1-20kVA)
UPS2000-A Series
(1-10kVA)

30
UPS5000-S Series
(50-800kVA)

UPS5000-E Series
(25-800kVA)

31
UPS2000-A Series
(1-3kVA)

Introduction
UPS2000-A series with a capacity ranging from 1kVA to 3kVA is an online
double conversion power system that delivers continuous, high-quality
AC Power. It’s really a perfect power protection solution for small power
scenarios.

Scenarios
•• Small and medium enterprises, large enterprise branch offices, bank
branches and other small data centers
•• Networks, communications systems, automatic control systems and UPS2000-A-1K/2K/3K
other precision equipment
•• Family, office

Features
Reliable
•• Wide input voltage range to minimize battery use
•• Online double conversion power system provides continuous, high-
quality AC Power

Efficient
•• Efficiency up to 90%, reduce energy consumption, green and energy-
saving
•• Ultra small volume, compared to the traditional UPS system to save
space

Simple
•• LCD screen supports real-time monitoring and convenient operation
•• Built-in battery, easy to use
•• Enables quick and easy configuration of the UPS
•• NetEco network manager, supporting centralized management to all
the UPSs

32
Specifications

Rated capacity (kVA/kW) 1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW


Input: Output 1-in: 1-out
Input Wiring L+N+PE

Rated Voltage 220/230/240VAC


Mains
Input Voltage Range 110-300VAC
Input
Input Frequency Range 40-70Hz

Input Power Factor 0.99

Input Rated Voltage 220/230/240VAC


Bypass
Input Voltage Range 174-264VAC
Input
Input Frequency Range 47-53Hz / 57-63Hz

Standard 24VDC 48VDC 72VDC


Battery Voltage
Long Backup 36VDC 72VDC 96VDC
Battery
Standard >5 minutes @ 80% load
Backup Time
Long Backup Depending on the capacity of external batteries

Output Wiring L+N+PE

Output Connections 4 X IEC C13 6 X IEC C13 6 X IEC C13 + 1 X IEC C19

Rated Voltage 220/230/240VAC ±1%

Output Frequency Tracking the bypass input (Normal mode); 50/60Hz ± 0.05%
Output
Output Power Factor 0.8

Waveform Sinewave, THDv< 3%

System Efficiency 88% 89% 90%

Overload Capacity ≤110% overload for 10 minutes; ≤130% overload for 1 minute;≤150% overload for 3 seconds

Operating Temperature 0 to 40°C

Storage Temperature –40 to +70°C (battery: –20 to +40°C)


Environ-
Relative Humidity 0%–95% RH (no condensation)
ment
Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Audible Noise <50dB

Standard 282 x 145 x 220 397 x 145 x 220 421 x 190 x 318
D x W x H (mm)
Long Backup 282 x 145 x 220 397 x 145 x 220 397 x 145 x 220

Standard 9.9 17.3 26.7


Others Weight (kg)
Long Backup 4.8 7.6 8.2

Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communications USB&RS232 (optional RS485/Dry contact/SNMP)

33
UPS2000-A Series
(6-10kVA)

Introduction
UPS2000-A series (6-10kVA) is a tower-mounted, online double
conversion power system that delivers continuous, high-quality AC
Power. up to 96% efficiency at online mode for 6/10kVA models helps
save 50% energy cost. It’s really a perfect power protection solution for
small power scenarios.

Scenarios
•• Small and medium enterprises, large enterprise branch offices, bank
branches and other small data centers
•• Networks, communications systems, automatic control systems and UPS2000-A-6K/10K
other precision equipment
•• Family, office

Features

Reliable
•• Wide input voltage range to minimize battery use
•• Key component failure pre-alarm including fans, batteries to remind
customers to maintain before failure occurs
•• Coating design & key device pin special protection enhance reliability

Efficient
•• High efficiency of up to 96% at online mode for 6/10kVA reduces
power loss of UPS and smart cooling product and saves customers
more than 50% over less efficient models
•• The output power factor is 0.9, high load capacity

Simple
•• LCD screen supports real-time monitoring and convenient operation
•• Built-in battery design provides you integrated solution and makes it
especially applicable for space-scarce use
•• 6kVA/10kVA Professional Edition supports 4 machines in parallel
operation, built in maintenance bypass, easy to use
•• The NetEco 1000U management system monitors UPSs in real time
and allows users easy management, and operation
•• Multiple remote monitoring: supports SMS, E-mail, etc
•• NetEco network manager, supporting centralized management to all
the UPSs

34
Specifications

6kVA/5.4kW 10kVA/9kW
Rated capacity (kVA/kW)
(Standard Version) (Standard Version)

Model UPS2000-A-6KTTL-S UPS2000-A-10KTTL-S


Input: Output 1 phase input, 1 phase output
Input Wiring L+N+PE
Rated Input Voltage 220/230/240V AC
Input Voltage Range 80-280V AC
Mains Input Frequency Range 50/60Hz ± 5Hz
Input power factor ≥ 0.99
Total Harmonic
Total Harmonic Distortion of current <3% at rated load
Distortion

Bypass Input rated voltage 220/230/240V AC


Input Input frequency range 50/60Hz ± 5Hz

Battery Standard 192V DC 192V DC


voltage Long backup 192-240V DC 192-240V DC
Battery
Backup Standard > 5 minutes at 80% rated load > 4 minutes at 80% rated load
time Long backup Depending on the capacity of external batteries
Output wiring L+N+PE
Rated voltage 220/230/240V AC ±1%
Output Output frequency Tracking the bypass input (Normal mode); 50/60Hz ± 0.05% (Battery Mode)
Output power factor 0.9
Waveform Sine wave, THDv ≤ 2%
Maintenance Bypass No Built-in Maintenance Bypass
Expandability ----
System
Efficiency 96%
Overload capacity ≤125% overload for 5 minutes; ≤150% overload for 1 minute
Operating Temperature 0°C to 40°C

Enviro- Relative Humidity 0%–95% RH (no condensation)


nment Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3
Audible Noise <50dB
Height×Width×Depth (mm) 580 x 250 x 605
Standard 60kg 67kg
Weight
Others Long backup 20kg 21kg
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.
Communications USB (optional RS485/Dry contact/SNMP)

35
UPS2000-G Series
(1-3kVA)

Introduction
UPS2000-G series with a capacity ranging from 1kVA to 3kVA is an online
double conversion power system that delivers continuous, high-quality
AC Power. It’s really a perfect power protection solution for small power
scenarios. It’s support tower and rack installation.

Scenarios
UPS2000-G-1K/2K/3K
•• Small and medium-sized enterprises, large enterprise branch offices,
bank branches and other small data centers
•• Networks, communications systems, automatic control systems and
other precision equipment

Features
Reliable
•• Wide input voltage range to minimize battery use
•• Online double conversion power system provides continuous, high-
quality AC Power

Efficient
•• Efficiency up to 90%, reduce energy consumption, green and energy-
saving
•• Ultra small volume, compared to the traditional UPS system to save
space

Simple
•• LCD screen supports real-time monitoring and convenient operation
•• Built-in battery, easy to use
•• Enables quick and easy configuration of the UPS
•• NetEco network manager, supporting centralized management to all
the UPSs

36
Specifications

Rated capacity (kVA/kW) 1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW


Input: Output 1-in: 1-out
Input Wiring L+N+PE

Rated Voltage 200/208/220/230/240VAC


Mains
Input Voltage Range 110-300VAC
Input
Input Frequency Range 40-70Hz

Input Power Factor 0.99

Bypass Input Rated Voltage 200/208/220/230/240VAC


Input Input Frequency Range 50/60±3Hz

Standard 24VDC 48VDC 72VDC


Battery Battery Voltage
Long Backup 36VDC 72VDC 96VDC

Output Wiring L+N+PE

Output Connections 4 X IEC C13 6 X IEC C13 6 X IEC C13 + 1 X IEC C19

Rated Voltage 200/208/220/230/240VAC ±1%

Output Output Frequency Tracking the bypass input (Normal mode); 50/60Hz ± 0.05%

Output Power Factor 0.8

Waveform Sinewave, THDv< 3%

System Efficiency 88% 89% 90%

Operating Temperature 0 to 40°C

Storage Temperature –40 to +70°C (battery: –20 to +40°C)


Environ-
Relative Humidity 0%–95% RH (no condensation)
ment
Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Audible Noise <50dB

Standard 88 × 438 × 310 88 × 438 × 410 88 × 438 × 630


D x W x H (mm)
Long Backup 88 × 438 × 310 88 × 438 × 410 88 × 438 × 410

Standard 11.1 18.8 28.9


Others Weight (kg)
Long Backup 6.0 8.7 9.3

Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communications USB&RS232(optional RS485/Dry contact/SNMP)

37
UPS2000-G Series
(6-20kVA)

Introduction
UPS2000-G series with a capacity ranging from 6kVA to 20kVA is an online
double conversion power system that delivers continuous, high-quality
AC power. It is rack/tower convertible and 95% high efficiency helps it get
ECA energy saving certification from United Kingdom government and the
world’s first batch of "Energy Star" certification. It’s really a perfect power
protection solution for small power scenarios.

UPS2000-G-6K/10K
Scenarios
•• Small and medium-sized enterprises, large enterprise branch offices,
bank branches and other small data centers
•• Networks, communications systems, automatic control systems and
other precision equipment

Features
Reliable
•• 5kA lightning protection design, reducing lightning-related failure rate
•• Key component failure pre-alarm including fans, batteries, bus UPS2000-G-15K/20K
capacitors to remind customers to maintain before failure occurs
•• Ultra-wide voltage input range to extend battery service life by
effectively reducing times of switchover to battery mode

Efficient
•• High efficiency at online mode to reduce power loss of UPS and air
conditioner: up to 95% for 15/20kVA, 94.5% for 10kVA, 94% for 6kVA

Simple
•• Rack/tower convertible, suitable for different installation scenarios
•• High expandability design: up to four units can be connected in parallel
to achieve higher capacity or reliability
•• NetEco network manager, supporting centralized management to all
the UPSs

38
Specifications

Rated Capacity(kVA/kW) 6/5.4 10/9 15/13.5 20/18


1-in: 1-out or
Input: Output 1-in: 1-out 1-in: 1-out, 3-in: 1-out or 3-in: 3-out
3-in: 1-out
Input Wiring L+N+PE L+N+PE /3Ph+N+PE

Rated Voltage L-N: 220/230/240V AC


Mains
Input Input Voltage Range L-N: 80-280V AC

Input Frequency Range 40-70Hz

Input Power Factor 0.99

Bypass Rated Voltage L-N: 220/230/240V AC


Input Frequency 50/60 ± 6Hz

Standard 240V DC -
Rated
Battery 384-480V DC, 32-40 section adjustable,
Voltage Long Backup 192-240V DC
default 40

Output Wiring L+N+PE L+N+PE /3Ph+N+PE

Output Sockets 2 × C13 (10A) -

Rated Voltage 220/230/240V AC ±1% L-N: 220/230/240V AC ±1%

Output Rated Frequency Tracking the bypass input (Normal mode); 50/60 Hz±0.05% (Battery mode)

Output Power Factor 0.9

Waveform Sine wave, THDv<2%

Efficiency 94% 94.5% 95%

Operating Temperature 0-40ºC

Storage Temperature -40 to 70ºC


Enviro-
Relative Humidity 0%-95% (No condensing)
nment
Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Audible Noise <55dB <58dB

H × W × D (mm) 86 × 430 × 615 130 × 430 × 757

Weight 14kg 16kg 32kg


Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc

Communications USB(optional RS485/Dry contact/SNMP)

39
UPS5000-E Series
(25-75kVA Battery Integrated)

Introduction
UPS5000-E Battery Integrated Solution features the double-conversion
online and modular design with pre-integrated battery module, fast on-site
deployment & installation, intelligent management, unattended operation
and simple O&M, thus providing customers with reliable, efficient and
Power Module: 25kVA/2U
simple modular UPSs.

Scenarios
•• Small-to-medium sized data centers
•• Telecom and Internet switch computer rooms of small-to-medium sized
enterprises
•• Area network and communication equipment rooms
•• Computer rooms of branch offices of industries like finance, etc

Features
Reliable
•• Wide input voltage range from 138Vac to 485Vac to suit for worst grid
and minimize battery use Integrated Cabinet
•• Dual-controller design to eliminate the single point of failure 25kVA-75kVA
•• Redundant auxiliary power supply and fans
•• Intelligent Battery Management: monitoring battery's temperature,
early warning for failure, battery powered high reliability.

Efficient
•• High efficiency of system up to 96%
•• Intelligent hibernation technology to keep UPS operating at high
efficiency
•• All in one design, saving the area of 50%

Simple
•• Modularized power, bypass, control and battery modules, fast
installation and maintenance
•• 7-inch colored LCD showing real-time operation status in various
languages
•• Various communication interfaces including dry contacts, RS485, Modular Battery Cabinet
Modbus etc.
•• NetEco network manager, supporting centralized management to all
the UPSs

40
Specifications

Model UPS5000-E-(25-75kVA)-BF

Capacity (kVA/kW) 25kVA/kW 50kVA/kW 75kVA/kW

Rated Voltage 380/400/415Vac

Voltage Range 138 to 485Vac

Input Wiring 3Ph+N+PE


Mains Frequency Range 40 to 70 Hz

Total Harmonic
Input <3% (100% linear load)
Distortion

Input Power Factor 0.99

Rated Voltage 380/400/415Vac

Bypass Frequency Range 50/60Hz (adjustable, 0.5 to 6Hz, ±2Hz by default)

Input Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac

Output Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode)

Output Power Factor 1

Output Waveform Sine wave; THDv<1% (linear load)

Output Wiring 3Ph+N+PE

System Efficiency Up to 96%

Overload Capacity ≤110% overload for 60min; ≤125% overload for 10min; ≤150% overload for 1min

Operation Temperature 0 to 40 ºC

Storage Temperature -40 to 70 ºC

Environment Relative Humidity 0% to 95% (No condensing)

Maximum Operation Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Noise <65dB

System Expandability 4

Integrated Cabinet Power Backup Standard configuration 2 to 4 groups of battery (8 to 16 battery modules)

Battery Cabinet (optional) Power Optional battery cabinet, 1 to 8 groups of battery (4 to 32 battery modules) per
Backup cabinet, max. 4 cabinets in parallels

Support battery or empty battery for battery module, battery typical configuration:
Others Battery Module
10×12V 9Ah

Height×Width×Depth (mm) 2000 × 600 × 1100

Weight (full configuration) 890kg 910kg 930kg

Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communication Interface/Protocol Dry contacts, RS485, FE; Support SNMP, Modbus.

Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV
requirements stated in TIA942.
41
UPS5000-E Series
(25-125kVA)

Introduction
Based on the online double conversion technology, UPS5000-E series
(25-125kVA) can provide reliable, pure and uninterrupted power for
critical ICT equipment. The modularized architecture helps improve the
availability and reduce the engineering cost significantly.

Scenarios
25kVA Power Module @ 2U
•• Small & medium data center, large enterprise regional datacenter
•• Central offices, dispatch center, control center, etc.

Features
Reliable
•• 138-485Vac ultra-wide input voltage range, suitable for the worst
power grid
•• Redundant design for modules, elimination of the single point of failure
•• iPower pre-warnings for key components in case of power supply
interruption

Efficient
•• High efficiency up to 96% at most frequently-used load rate, reducing
power consumption of UPS and cooling efficiency
•• Intelligent hibernation technology ensures efficient UPS operation

Simple
•• Hot swappable power module, bypass module and control module,
simple maintenance and expansion in 5 minutes
•• iPower real time monitoring system for UPS, PDU and batteries, UPS5000-E-125K-FM
elimination of manual routing inspection

42
Specifications

Model UPS5000-E-125K-FM
Rated Capacity (kVA/kW) 25kVA/kW 50kVA/kW 75kVA/kW 100kVA/kW 125kVA/kW
Number of Power Modules 1 2 3 4 5
Input Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac

Voltage Range 138-485Vac


Mains
Input Input Frequency 40-70Hz

Total Harmonic
THDi<3% for linear load
Distortion

Input Power Factor 0.99

Input Wiring 3Ph+N+PE


Bypass
Rated Voltage 380/400/415Vac
Input
Input Frequency 50/60 ± 6Hz

Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 32 batteries in default)

Output Wiring 3Ph+N+PE

Voltage 380/400/415Vac±1%

Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode)

Waveform Sine wave (THDv<1% for linear load)


Output
Output Power Factor 1

Overload Capacity Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute

Efficiency Up to 96%

Expandability 4

Operating Temperature 0-40ºC

Enviro- Storage Temperature -40 to 70ºC


nment Relative Humidity 0%-95% (No condensing)

Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Height×Width×Depth
2000 × 600 × 850
(mm)

Weight 250kg 270kg 290kg 310kg 330kg


Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol
Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV
requirements stated in TIA942.

43
UPS5000-E Series
(50-800kVA)

Introduction
UPS5000-E Series (50-800kVA) is an advanced modular UPS based on
Huawei's extensive experience in digital technology and power electronics.
Benefiting from high performance DSP and high speed communication
technology, the UPS5000-E system achieves leading expandability and
availability. Its high efficiency, high availability match the requirements of
cloud data center perfectly.

Scenarios
UPS5000-E-200/300K
•• Data centers in headquarter or disaster recovery data centers
•• Internet data centers
•• Large cloud computing data centers

Features
Reliable
•• 138-485Vac ultra-wide input voltage range, suitable for the worst
power grid
•• Redundant design for modules, elimination of the single point of failure
•• iPower pre-warnings for key components in case of power supply
interruption

Efficient
•• High efficiency up to 95%-96% at most frequently-used load rate UPS5000-E-400/500K
•• Intelligent hibernation technology ensures efficient UPS operation
•• Single UPS capacity up to 800kVA, 50% footprint saving, more IT rack
space

Simple
•• Hot swappable power module, bypass module and control module,
simple maintenance and expansion in 5 minutes
•• iPower real time monitoring system for UPS, PDU and batteries,
elimination of manual routing inspection

44
Specifications

UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E-


Model
200K 300K 400K 500K 600K 800K

Rated Capacity (kVA/kW) 50-200 50-300 50-400 50-500 50-600 50-800


Number of Power Modules 1-4 1-6 1-8 1-10 1-12 1-16
Input Wiring 3Ph+PE (Neutral wire: optional*)
Rated Voltage 380/400/415Vac
Voltage Range 138-485Vac (305-485Vac for 100% load; 138-305Vac for 40%-100% load)
Mains Frequency Range 40-70Hz
Input
Total Harmonic
THDi<3% for 100% linear load
Distortion
Input Power
0.99
Factor

Bypass Rated Voltage 380/400/415Vac


Input Input Frequency 50/60±6Hz
Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 40 batteries in default)
Output Wiring 3Ph+N+PE
Voltage 380/400/415Vac±1%
Output Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode)
Waveform Sine wave (THDv<1% for linear load)
Overload Capacity Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute
Output Power
1
Factor
System
Efficiency Up to 96%
Expandability 8
Operating
0-40ºC
Temperature
Storage
-40 to 70ºC
Temperature
Enviro-
nment Relative Humidity 0%-95% (No condensing)
Operating
0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3
Altitude
Audible Noise 66-75dB
Height × Width × 2000 × 2000 ×
2000 × 600 × 850 2000 × 1200 × 850
Depth (mm) 1400 × 850 2400 × 850

Weight 285-390kg 275-450kg 465-710kg 515-830kg 705-1090kg 1075-1540kg


Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.
Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol
* Without neutral wire, it's TN-C system.
Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV 45
requirements stated in TIA942.
UPS5000-E Series
(60-600kVA,60kVA Power Module)-SMS/FMS

Introduction
UPS5000-E series (60-600kVA, 60kVA Power Module)-SMS/FMS is a high
performance modular UPS comprising of 3U 60kVA power modules. It
has leading performance in the industry and delivers reliability, efficiency,
simplicity and intelligence to the customer. These features meet the power
supply needs of large data centers in the cloud computing era.

Scenarios
•• Data centers in headquarter or disaster recovery data centers 400kVA/500kVA-SMS/FMS
•• Internet data centers
•• Large cloud computing datacenters
•• Large IT device and manufacture device
•• Public safety system and E-government system

Features
Reliable
•• 138-485Vac ultra-wide input voltage range, suitable for the worst
power grid
•• Redundant design for modules, elimination of the single point of failure
•• iPower pre-warnings for key components in case of power supply
interruption

Efficient 600kVA-SMS/FMS
•• High efficiency up to 96% at most frequently-used load rate
•• Intelligent hibernation technology ensures efficient UPS operation
•• Single power module capacity up to 60kVA/54kW. Single UPS capacity
up to 600kVA/540kW, 50% footprint saving, more IT rack space

Simple
•• Hot swappable power module, bypass module and control module,
simple maintenance and expansion in 5 minutes
•• iPower real time monitoring system for UPS, PDU and batteries,
elimination of manual routing inspection

46
Specifications

UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E- UPS5000-E-


Model
400K-SMS 400K-FMS 500K-SMS 500K-FMS 600K-SMS 600K-FMS

Rated Capacity (kVA) 400 400 500 500 600 600


Number of Power Modules 1-7 1-7 1-9 1-9 1-10 1-10
Input Wiring 3Ph+N+PE
Rated Voltage 380/400/415Vac
Input Voltage 0-30OC: 324-485Vac for 100% load; 138-324Vac for 35%-100% load
Mains Range 30-40OC:343-485Vac for 100% load; 138-343Vac for 35%-100% load
Input
Input Frequency
40-70Hz
Range
Input Power
0.99
Factor

Bypass Rated Voltage 380/400/415Vac


Input Input Frequency 50/60±6Hz
Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 40 batteries by default)
Output Wiring 3Ph+N+PE
Voltage 380/400/415Vac±1%
Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode)

Output Waveform Sine wave (THDv<1% for linear load)


105%<Load≤110%, 60min; 0-30OC, 110%<Load≤125%, 10min; 30-40OC, 110%<Load≤125%,
Overload Capacity
3min; 125%<Load≤150%, 30s; Load>150%:200ms
Output Power
0.9
Factor
Efficiency Up to 96%
System
Expandability ≤8
Operating
0-40ºC
Temperature
Storage
-40 to 70ºC
Temperature
Enviro-
nment Relative Humidity 0%-95% (No condensing)
Operating
0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3
Altitude
Audible Noise 62dB @50%Load 63dB @50%Load
Height × Width
2000×1200×850 2000×1200×850
× Depth (mm)
Weight at
Others rated capacity 640 680 780 800 975 1025
(kg)
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc
Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol
Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV
requirements stated in TIA942.

47
UPS5000-S Series
(50-800kVA)

Introduction
UPS5000-S Series (50-800kVA) is an advanced modular UPS based
on Huawei's extensive experience in digital technology and power
electronics. Benefiting from high performance DSP and high speed
communication technology, the UPS5000-S system achieves leading
expandability and availability. Its high efficiency, high availability
match the requirements of cloud data center perfectly.

UPS5000-S-200/300kVA UPS5000-S-400/500kVA
Scenarios
•• Data centers in headquarter or disaster recovery data centers
•• Internet data centers
•• Large cloud computing data centers

Features
UPS5000-S-600kVA UPS5000-S-800kVA
Reliable
•• 138-485Vac ultra-wide input voltage range, suitable for the worst
power grid
•• Redundant design for modules, elimination of the single point of
failure
•• iPower pre-warnings for key components in case of power supply
interruption

Efficient
•• High module efficiency up to 97.5% and system efficiency up to
96%-97% at most frequently-used load rate
•• Intelligent hibernation technology ensures efficient UPS operation
•• Single cabinet power capacity up to 600kVA, 50% footprint
saving, more IT rack space

Simple
•• Hot swappable power module, bypass module and control
module, simple maintenance and expansion in 5 minutes
•• iPower real time monitoring system for UPS, PDU and batteries,
elimination of manual routing inspection

48
Specifications

UPS5000-S- UPS5000-S- UPS5000-S- UPS5000-S- UPS5000-S- UPS5000-S-


Model
200K 300K 400K 500K 600K 800K

Rated Capacity (kVA/kW) 50-200 50-300 50-400 50-500 50-600 50-800

Number of Power Modules 1-4 1-6 1-8 1-10 1-12 1-16


Input Wiring 3Ph+PE
Rated Voltage 380/400/415Vac
Voltage Range 138-485Vac (305-485Vac for 100% load; 138-305Vac for 40%-100% load)
Mains Frequency Range 40-70Hz
Input
Total Harmonic
THDi<3% for 100% linear load
Distortion
Input Power
0.99
Factor
Input Wiring 3Ph+N+PE
Bypass
Rated Voltage 380/400/415Vac
Input
Input Frequency 50/60±6Hz
Battery Rated Voltage 384-600Vdc (The number of batteries can be selected from 32 to 50; 40 batteries in default)
Output Wiring 3Ph+N+PE
Voltage 380/400/415Vac±1%
Output Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.1% (Battery mode)
Waveform Sine wave (THDv<1% for linear load)
Overload Capacity Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute
Output Power
1
Factor
System
Efficiency Up to 97.1%
Expandability 8
Operating
0-40ºC
Temperature
Storage
-40 to 70ºC
Temperature
Enviro-
nment Relative Humidity 0%-95% (No condensing)
Operating
0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3
Altitude
Audible Noise 66-75dB
Height×Width× 2000 × 2000 ×
2000 × 600 × 850 2000 × 1200 × 850
Depth(mm) 1400 × 850 2400 × 850
Weight 225-354kg 251-416kg 462-693kg 648-945kg 709-1072kg 1061-1556kg
Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.
Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol
Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV
requirements stated in TIA942.

49
UPS5000-A Series
(30-120kVA)

Introduction
The UPS5000-A (30-120kVA) is an online, double-conversion, and tower/
rack convertible UPS that Huawei has launched. It uses the digital signal
processing (DSP) technology to output pure and stable sine wave with
a voltage of 380/400/415 Vac. With comprehensive reliability assurance
measures and other leading technologies, the UPS5000-A (30-120kVA)
can provide reliable, economical, intelligent, and convenient solutions to
medium power scenarios.

Scenarios UPS5000-A-30/40K

•• Small and medium-sized data centers


•• Telecom and Internet switch rooms
•• Equipment rooms of branch offices in sectors such as finance
•• Infrastructures, such as control equipment rooms, wireless systems, etc.

Features
Reliable
•• Wide input voltage range to minimize battery use: 485-305 Vac for
100% load; 305-138 Vac for 100%-40% load (derating linearly)
•• High output power factor of up to 1, 30% more load driven than
traditional UPS

Efficient
•• High efficiency at online mode of up to 95.7%, reducing power
consumption of UPS and cooling equipment effectively

Simple
UPS5000-A-60/80/120K
•• Rack/tower convertible, suitable for different installation scenarios
•• Flexible battery configuration: 30-44 batteries per string allow customers
to get the faulty battery out instead of replacing it

50
Specifications

Rated Capacity (kVA/kW) 30kVA/30kW 40kVA/40kW 60kVA/54kW 80kVA/80kW 120kVA/108kW


Input Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac

Voltage Range 138-485Vac


Mains
Input Frequency Range 40-70Hz

Total Harmonic
THDi<3% for 100% linear load
Distortion

Input Power Factor 0.99

Input Wiring 3Ph+N+PE


Bypass
Rated Voltage 380/400/415Vac
Input
Input Frequency 50/60±6Hz

Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 32 batteries in default)

Output Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac±1%

Output Frequency Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode)

Waveform Sine wave (THDv<1% for 100% linear load)

Overload Capacity 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute

Output Power Factor 0.9(60/120kVA);1 (30/40/80kVA)

System Efficiency Up to 95.7%

Expandability Up to 8 units connected in parallel

Operating Temperature 0-40ºC

Storage Temperature -40 to 70ºC


Enviro-
Relative Humidity 0%-95% (No condensing)
nment
Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Audible Noise 58-64dB

Height×Width×Depth (mm) 500 × 264 × 800 1020 × 440 × 850

Weight 70kg 200kg 240kg


Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communications Dry contacts, RS485, SNMP

51
UPS5000-A Series
(200-800kVA)

Introduction
Huawei UPS5000-A (200-800kVA) is an online double conversion UPS
which can output pure sine wave with rated voltage of 380/400/415 Vac.
UPS5000-A has a high efficiency of up to 96% and high power density of
up to 300kVA per cabinet; all-digital control allows precise output at any
input and load condition. It’s suitable to ensure continuous power supply
to critical loads in large datacenters.

Scenarios
•• Large data centers, server rooms, security systems of finance, telecom
and other large enterprises UPS5000-A-200/300K
•• Data center of government or public institutions
•• Precision instruments

Features
Reliable
•• Wide input voltage range to minimize battery use: 485-305 V for 100%
load; 305-138 Vac for 100%-40% load (derating linearly)
•• Better load adaptability: high output power factor up to 1 and no
derating for capacitive or inductive devices with a PF>0.5

Efficient
•• High efficiency of up to 96%, reducing power consumption effectively
•• High power density of up to 300kVA per rack, 50% footprint saving
compared with traditional UPS
UPS5000-A-400/500K
Simple
•• Flexible battery configuration: 30-44 batteries per string allow customers
to get the faulty battery out instead of replacing it

52
Specifications

Rated Capacity 200kVA/200kW 300kVA/300kW 400kVA/400kW 500kVA/500kW 600kVA/600kW 800kVA/800kW


Input Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac

Voltage Range 138-485Vac


Mains
Input Frequency Range 40-70Hz

Total Harmonic
THDi<3% for 100% linear load
Distortion

Input Power Factor 0.99

Input Wiring 3Ph+N+PE


Bypass
Rated Voltage 380/400/415Vac
Input
Input Frequency 50/60±6Hz

Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 40 batteries in default)

Output Wiring 3Ph+N+PE

Rated Voltage 380/400/415 Vac±1%

Output Frequency Tracking the bypass input (Normal mode); 50/60 Hz±0.05% (Battery mode)

Waveform Sine wave (THDv<1% for 100% linear load)

Overload Capacity 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute

Output Power Factor 1

System Efficiency 96%

Expandability Up to 8 units connected in parallel

Operating Temperature 0-40ºC

Storage Temperature -40 to 70ºC


Enviro-
Relative Humidity 0%-95% (No condensing)
nment
Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Audible Noise 66-75dB

Height×Width×Depth 2000 × 1400 2000 × 2400 ×


2000 × 600 × 850 2000 × 1200 × 850
(mm) × 850 850

Weight 370kg 450kg 710kg 850kg 1100kg 1610kg


Others
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol

Notice:
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIERIII or TIER IV
requirements stated in TIA942.

53
UPS Li-ion Battery Solution
SmartLi

Introduction
SmartLi is a battery energy storage system developed by Huawei for
UPS, which has the features of safety and reliability, long lifespan, space
saving and easy maintenance. LFP is the safest cell of Li-ion battery. The
unique active current balance control technology supports the mix use
of new and old batteries, which reduces Capex. Three-level BMS system
realizes intelligent battery management with Huawei UPS and Network
management system, which reduces Opex.

Scenarios
•• Long lifespan, cycle lifetime is 3000 times
•• LFP cell ensures safety and reliability SmartLi
•• Three-level BMS ensures reliability
•• Active current balance control, full use of battery

Specifications

Item 200kVA/200kW
Product Model SmartLi-512V-80AH

Battery Cell Material LiFePO4

Nominal Voltage 512Vdc

Nominal Charging Voltage 544Vdc

Max. Charging / Discharging


80A / 400A continuous, @35ºC
Current Limited

Basic Cycle Life 3000 cycles @ 80% DOD, 35ºC


Parameters
Nominal Capacity 40.96kWh @ 0.2C, 35ºC (charging to 544Vdc, discharging to 408Vdc)

Weight Approx. 750kg

Dimension (W*D*H) 600mm*850mm*2000mm

Self Discharge @ 25ºC Less than 5% in 90 days storage

Communication Interface RS485; Dry contacts

Protection Over temperature, over current, short circuit, over charge/discharge, etc.

Certification UL1642, UN38.3, IEC62619, IEC62040

54
Specifications

Item 800kVA/800kW
Storage Temperature 0ºC ~ 45ºC

Transportation Temperature -40ºC to 60ºC


Environment
Operating Temperature 0ºC ~ 40ºC

Relative Humidity 5% - 95%

Max. Operating Altitude 4000 m

Specifications

Cell Module Cabinet


Configuration 1S1P 20S1P 160S2P

Nominal Capacity 128Wh 2.56kWh 40.96kWh

Nominal Voltage 3.2Vdc 64Vdc 512Vdc

Operation Voltage Range 2.5-3.6Vdc 51-68Vdc 408-544Vdc

Dimension(W*D*H: mm) 148*26.5*132 200.5*592*155.5 600*850*2000

Weight 1.1kg Approx. 30kg Approx. 750kg

Back-up Time(in minutes)

UPS Power 1 Cabinet 1 Cabinets 3 Cabinets 4 Cabinets 5 Cabinets


100kW 21 42 63 84 105

200kW - 20.5 31.5 42 52.5

300kW - 12.5 20.5 27.5 35

400kW - - 15 20.5 25.5

500kW - - 11 16.5 20.5

600kW - - - 13 17

55
FusionPower Series
(UPS5000-S-1200kVA-FP)

Introduction
UPS5000-S-1200kVA-FP which belongs to FusionPower series solution is
an advanced power supply solution integrate modular UPS, input PDU and
output PDU. The system adopts UPS5000-S which achieves high efficiency,
the module efficiency is up to 97.5% and system efficiency is up to 97%.
This integrated solution can save more space for customers and its high
efficiency, high availability match the requirements of data center perfectly.

Scenarios
•• Data centers in headquarter or disaster recovery data centers
•• Internet data centers Power Module: 55kVA/3U & 97.5%
•• Large cloud computing data centers

Features
Reliable
•• 138-485Vac ultra-wide input voltage range, suitable for the worst
power grid
•• Redundant design for modules, elimination of the single point of failure
•• iPower pre-warnings for key components in case of power supply
interruption

Efficient
•• High module efficiency is up to 97.5% and system efficiency is up to
96.5%-97% at most frequently-used load rate
UPS5000-S-1200kVA-FP
•• Integrated power solution saves 40% footprint
•• Installation labor hours reduced by 60%

Simple
•• Hot swappable power module, bypass module and control
module,simple maintenance and expansion in 5 minutes
•• iPower real time monitoring system for UPS, PDU and batteries,
elimination of manual routing inspection

56
Specifications

Model UPS5000-S-1200kVA-FP
Input Wiring 3Ph+N+PE

Rated Voltage 380/400/415Vac

Voltage Range 138-485Vac


Mains
Input Frequency Range 40-70Hz

Total Harmonic
THDi<3% for 100% linear load
Distortion

Input Power Factor 0.99

Input Wiring 3Ph+N+PE


Bypass
Rated Voltage 380/400/415Vac
Input
Input Frequency 50/60±6Hz

Battery Rated Voltage 360-528Vdc (The number of batteries can be selected from 30 to 44; 40 batteries in default)

Output Wiring 3Ph+N+PE

Rated Voltage 380/400/415 Vac±1%

Output Frequency Tracking the bypass input (Normal mode); 50/60 Hz±0.05% (Battery mode)

Waveform Sine wave (THDv<1% for 100% linear load)

Overload Capacity 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minute

Output Power Factor 1


System
Efficiency Up to 97%

Operating Temperature 0-40ºC

Enviro- Storage Temperature -40 to 70ºC


nment Relative Humidity 0%-95% (No condensing)

Operating Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3

Height×Width×Depth
2200*2800*1000
(mm)

Others Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.

Communication
Dry contacts, RS485, FE; Support SNMP, Modbus.
Interface/Protocol

57
Modular Precision Power Distribution
Cabinet PDU8000

Introduction
The Precision Power Distribution Cabinet provides power distribution,
electrical parameters measurement and risk pre-alarm functions to match
the reliable operation of data center.

Scenarios
•• Large data centers
•• Disaster recovery data center
•• Enterprise date centers

Features
Reliable
•• A full range of type tests, environmental tests and 9 intensity seismic
tests to ensure high reliability
•• Intelligent risk management, 24 hours key node temperature real-time
detection
•• Modular design, standardized production, fully automated testing to
ensure product reliability

Simple
•• The monitoring module and the output switch can be hot-swappable,
which is easy to expand and maintain
•• 7 inch LCD color touch screen, visual intelligent detection, simple
management

58
Specifications

Items Precision PDC (Standard)


Parameter

Rated Voltage 208/380/400/415

Rated current (A) 160/250/400/630(optional)

Rated frequency (Hz) 50/60

Total Harmonic
THDi<3% for 100% linear load
Distortion

Input switch MCCB

Bus architecture Dual buses or single bus(optional)

Outputs Max. 144 1-pole MCBs or 48 3-pole MCBs (optional)

Rated current of
10/16/20/32/40/63 (optional)
outputs(A)

Ingress Protection IP20

Surge protection level-C SPD (In=20kA)

Cabling route from the top

Maintenance Front operation and rear maintenance

Monitoring Function

Monitoring the voltage, current, power, power factor, harmonic etc. of the main circuit Monitoring the current,
Monitoring Function
load ratio, active power, switch status etc. of the branch circuit

Communication Modbus , SNMP

Environment

Operating Temperature –5ºC to +40ºC

Storage Temperature -40 to 70ºC

Relative Humidity 5%–95% (No condensation )

Altitude 2000 m, derated when the altitude exceeds 2000 m

Others
Dimensions (WxDxH)
600×1100×2000,600×1200×2000,600×1200×2200
(mm)

Installation Floor-mounted

Weight < 380 kg

Certification CCC, CE, TLC

59
iBattery Intelligent Management Solution

Product Introduction
iBattery is an intelligent battery management system based on wireless transmission. It can perform real-time detection of core
parameters including voltage, current, temperature and internal resistance. Besides, through the linkage with Huawei UPS system,
it can, by effectively identifying the SOH, provide automatic shutdown of battery group in an emergency so as to keep stable and
reliable operation of the backup power system.

Application Scenario
Operation with Huawei UPS or NetEco, applicable to:
•• 12V valve regulated lead acid battery
•• 2V valve regulated lead acid battery

Typical Networking Diagram

Features & Values


Real-time detection, manual routing detection Real-time calculation of SOH, automatic
eliminated identification of weak cells

Linkage with UPS, automatic shutdown


Wireless connection, easy deployment
in case of emergent fault

60
iBox Technical Specifications

Type iBox

iBat Access No. 300

Current Detection Precision 1%

Current Detection Input No. 8

iBOX SOC, SOH Detection Precision ±10%

DI/DO Interface 1 DI,1 DO

Power Supply 12V or 48V or POE


•• Support 4 pieces in parallel
•• Single iBox supports 300 iBats access Southbound Communication Protocol Zigbee

•• Support automatic identification of weak cells Northbound Communication Protocol SNMP, modbus TCP, modbus RTU
•• Linkage with UPS, automatic shutdown in case of
Dimensions (H*W*D) 180mm×116mm×43.6mm
emergent fault (fire)
Weight <0.45kg

Operating environment -20 to 65℃

iBat Technical Specifications

Type 2V iBat 12V iBat

Single voltage measurement range 1.5V to 2.5V 9V to 15V

Single internal resistance measurement range 0.1 to 20mΩ 1.5mΩ to 100mΩ

Pole temp. measurement range -20 to 125℃

12V iBAT 2V iBAT Voltage detection precision ±0.2%

Pole temp. detection precision ±0.5ºC


•• "0" consumption, power supplied by battery
•• Accurate detection for cell voltage, temperature, Internal resistance detection precision 2%±0.01mΩ

internal resistance Communications Mode Zigbee


•• Wireless connection, high reliability, easy expansion
Normal operation power consumption <0.5W

Current at low power consumption mode <350uA 150uA

Poor connection of battery power cable Yes

Dimensions (H*W*D) 80mm×44.4mm×22.2mm

Weight <0.1kg

Operating environment -20 to 65℃

61
3 Huawei Energy Powering the Future
Huawei Smart Cooling Solutions

62
63
Contents
NetCol5000-A In-row Air Cooled Smart Cooling Product��������������������66
NetCol5000-C030 In-row Chilled Water Smart Cooling Product����������68
NetCol5000-C065 & C080 In-row Chilled Water Smart Cooling Product��70
NetCol8000-A In-room Air Cooled Smart Cooling Product������������������72
NetCol8000-A050D & A100D In-row Air Cooled Smart Cooling Product
�����������������������������������������������������������������������������������������������������������74
NetCol8000-C In-room Chilled Water Smart Cooling Product�������������76

In-row Smart Cooling Product

NetCol5000-A NetCol5000-C
(21-42kW) (30-80kW)
In-room Smart Cooling Product

NetCol8000-C
(62-253kW)
NetCol8000-A
(50/100kW)

NetCol8000-
A013U

A: Air cooled
C: Chilled water
In-row Air Cooled Cooling Product
NetCol5000-A

Introduction
NetCol5000-A is the in-row air cooled smart cooling product developed
by Huawei. It is configured with DC inverter compressor, EC fans, PTC
electric heater and electrode humidifier. Cooling capacity is 21kW, 25kW,
42kW. It is usually installed between the IT racks, closely coupled with heat
source so as to provide in-row cooling solution for medium-high density
data centers. NetCol5000-A supports piping and cabling from both top
and bottom side of the unit, and can be accessed from both front and
back side. It is an efficient, reliable and simple solution, helps to build next
generation green data center.

Application Scenarios
NetCol5000-A025 NetCol5000-A042
•• Modularized data center
•• Small and Medium sized Enterprise data center
•• Carrier base, city/district level data center
•• Financial branches

Value & Features


Efficient
•• DC inverter: inverter compressor and EC fan, 10%-100%* stepless Typical applications
capacity regulation, high efficiency at partial load
•• Group control: maximum 32 units can be group controlled, precision
management for capacity and power consumption
•• Without heating water, save 95%+ energy compared with traditional
humidifier*

Reliable
•• Dehumidification at low load: reliable dehumidification at minimum
10% load, eliminate condensation risk
•• Expansion valve shut automatically: Expansion valve will shut
automatically after unexpected power cut, eliminate liquid return
which may hit compressor
•• Refrigerant detection: AI algorithm detects the refrigerant content,
generating charging prompt when the refrigerant is insufficient

Simple DC inverter scroll EC fan


•• Intelligent display: 7” true color screen, clear and friendly operation compressor
interface, easy O&M
•• No welding maintain: compressor uses Rotalock connection, no
welding on maintenance
•• Malfunction self-diagnosis*: remove irrelevant reason intelligently,
guiding O&M engineer maintain quickly

Notice: the feature with * is just for 042H.

66
Technical Specification
NetCol5000-A Technical Specification
Unit model Unit NetCol5000-A021H NetCol5000-A025H NetCol5000-A050H
Air discharge direction – Horizontal Horizontal Horizontal

Total cooling capacity kW 21.0 25.0 46

Sensible cooling capacity kW 21.0 25.0 46

Air flow m3/h 4300 5,000 9,000

380-415/3/50,
Power supply V/Ph/Hz 208/3/60 380-415/3/50(60)
380-415/3/60

Refrigerant – R410A R410A R410A

Heating capacity kW 4 4 6

Humidifier capacity kg/h 1.5 1.5 3



Full load current A 28.0 (48.0) 20.0 (30.0) 46.0

Dimensions: W*D*H mm 300*1100*2000 300*1100*2000 600*1200*2,000

Net Weight kg 260 230 305

Notes:
1. Nominal cooling condition: Return air dry bulb temperature 37.8ºC/RH20%, outdoor temperature 35ºC
2. The data in brackets are applicable to the indoor unit with electric heater & humidifier
3. Data are subject to change without prior notice

Outdoor Condenser Technical Specification


Unit model Unit NetCol500-A026 NetCol500-A036 NetCol500-A060 NetCol500-A080 NetCol500-A120
380-415/3/50, 380-
220-240/1/50,
Power supply V/Ph/Hz 415/3/60, 440- Power supply from indoor unit
380-480v/3/50(60)
480/3/60

Fan quantity – 1 1 1 2 2

External diameter External diameter


Liquid pipe
in 5/8in, 5/8in, Thickness Diameter 5/8 in
diameter
Thickness 1.2mm 1.2mm

External diameter External diameter


Gas pipe
in 3/4in, 7/8in, Diameter 7/8 in
diameter
Thickzness 1.2mm Thickness 1.2mm

Full load current A 3.3, 2.5 2.5 Power supply from indoor unit

Dimensions: 1110×1094×1053, 1355×1094×1156, 1356×1094 2186×1094 2189×1356


mm
W*D*H 1120*1094*920 1370*1094*1160 ×1107 ×1107 ×1107

Net weight kg 91, 132 130 240 290 250

Notes: Data are subject to change without prior notice; the pipe diameter only for reference and it may be changed for the actual configuration

Outdoor Water-cooled Module Technical


Item Unit NetCol500-W055
Power supply - 220-240Vac, 50/60Hz, 1Ph+N+PE

Refrigerant Pipe in Gas pipe: 7/8; Liquid pipe: 5/8

Water Pipe - Inlet/outlet: G1-1/2 internal screw

Full load current A 0.15

Dimensions: W*D*H mm 1417*326*330

Net weight kg 60

67
In-row Chilled Water Cooling Product
NetCol5000-C030

Introduction

NetCol5000-C is a fan coil unit installed inside the data center, combined
together with chiller, chilled water pump and piping etc. to form a
complete cooling system. It is coupled with EC fan, and has the functions
of cooling & dehumidification. Normally, it is installed between the IT racks,
closely coupled with heat source so as to provide in-row cooling solution
for medium to high density DC. NetCol5000-C is an efficient, reliable and
simple cooling product, helps to build next generation green data center.

Application Scenarios
•• Carrier base, province/city level data center
•• ISP, EDC, IDC
•• Finance headquarter, disaster recovery data center
•• Smart city, safe city
NetCol5000-C
•• E-government

Value & Features


Efficient
•• High efficiency DC power module: Fans are powered by high efficiency self-
developed DC power module, efficiency is up to 94%, unit’s total rated
power input is only 1.0kW
•• High efficiency heat exchanger: CFD simulation and field synergy helps
achieve optimum heat exchange, improves heat transfer efficiency by 10%

Reliable IT Equipment 1 2 Precision AC


•• Dual condensate pumps: condensation drainage is not affected when one
pump fails Typical applications
•• Dual power sources: automatically switches to the other power source in
case of power failure
•• Multi. EC fans: Mutual backup, ensures smooth air flow

Simple
•• On-line fan maintenance: No need to switch off power.
•• Water piping: high quality imported rubber hose; threaded connection
makes installation easier and free of brazing work
•• It supports piping and cabling from both top and bottom of the unit, and
can be accessed from both front and rare
•• Leading-edge 7-inch colored touch screen features innovative one-touch 7 inch LCD true color EC fan
interface switch and provides temperature & humidity curves display of the
touch screen
last 30 days, bringing an excellent usage experience

68
Technical Specification

NetCol5000-C Technical Specification


NetCol5000-
Unit model Unit NetCol5000-C032H NetCol5000-C065H NetCol5000-C080H
C030H
Air discharge direction – Horizontal Horizontal Horizontal Horizontal

Total cooling capacity kW 30.0 32.0 65.0 80.0
Sensible cooling capacity kW 30.0 32.0 65.0 80.0
Air flow m3/h 5,100 5,000 10,000 12,000
Power supply V/Ph/Hz 220-240/1/50(60) 220-240/1/50(60) 220~240/1/50(60) 220~240/1/50(60)
Water flow l/s 1.4 1.6 3.2 3.9
Humidifier capacity kg/h 3 1.5 3 3
Full load current② A 5.5 (23) 9.5 15 17
Dimensions: W*D*H mm 300×1200×2000 300×1200×2200 600×1,200×2,000 600×1,200×2,500
Net weight② kg 166 176 200 238

Notes:
1. Cooling capacity condition: Return air dry bulb temperature 37.8ºC/RH20%, Inlet/Outlet water temperature 10ºC/15ºC
2. Nominal cooling condition: The current data in brackets are applicable to the unit with electric heater & humidifier
3. The unit with electric heater & humidifier does not support up piping for without water pump
4. Data are subject to change without prior notice

NetCol520 liquid distribute unit


Without NetCol520 (Liquid distribute unit) With NetCol520 (liquid distribute unit)
NetCol5000-C Air cooled chiller NetCol5000-C Air cooled chiller Liquid distribute unit

Valve Filter Valve Filter

Items Parameter description


Unit model NetCol520-12T (Upper water pipe) / NetCol520-12B (bottom water pipe)
Dimensions 1200*600*1800mm (W*D*H)
Unit weight 300kg
Water flow 43.2 m3/h

69
In-row Chilled Water Cooling Product
NetCol5000-C065 & C080

Introduction

NetCol5000-C is the in-row chilled water cooling product developed by


Huawei. Generally, it has a complete cooling system by combining chillers,
chilled water pumps and pipes, etc. It is usually deployed near the IT rack
and provides the cooling solution for middle-high power density DC.
NetCol5000-C helps to build the next generation of green DC.

Application Scenarios
•• Carrier base, province/city level data center
•• ISP, EDC, IDC
•• Finance headquarter, disaster recovery data center NetCol5000-C065H
•• Smart city, safe city
•• E-government

Value & Features


Efficient
•• ECFan: high efficiency variable frequency EC fan, save 30% energy
compared with AC fan
•• Wet-film humidifier: save over 95% energy in comparison with
electrode humidifier Application Scenario
Reliable
•• Dual power supply: the power supply can switch over automatically
when main power cut off
•• On-line maintenance: the fan can be maintained on-line, the unit can
still work when one fan breaks down
•• Reliable drainage: standardly configure water pump, support upper &
lower drainage, reduce the leakage risk of DC

Simple
7" Touch Screen ECFan
•• Digital management: 7“ colortouch screen, key parameters displayed
and uploaded to the management system such as cooling capacity, air
volume
•• Malfunction self-diagnosis: eliminate irrelevant failure reason
intelligently and save pending and maintenance time
•• Guide debugging: intelligent guide debugging, automatical logic
running, avoiding manual maloperation

70
Technical Specification

NetCol5000-C (600mm) Technical Specification


Unit Model Unit NetCol5000-C065 NetCol5000-C080

AirSupply - Horizontal Horizontal

Total Cooling Capacity1 kW 65.0 80.0

Sensible Cooling Capacity kW 65.0 80.0

Air Volume m3/h 10,000 12,000

Fan Quantity / 10 12

Power Supply V/Ph/Hz 220-240/1/50(60) 220-240/1/50(60)

Water Flow l/s 3.2 3.9

Water Pressure Drop kPa 100 100

Humidification (Optional) kg/h 3 3

Full Load Current A 15 17

Dimension: W ×D ×H mm 600 ×1,200 ×2,000 600×1,200×2,500

Net Weight kg 240 300

Notice:
Cooling capacity condition: return air DB temperature 37ºC/RH24%, inlet/outletwatertemperature10ºC/15ºC

71
In-room Air Cooled Cooling Product
NetCol8000-A

Introduction

NetCol8000-A013U is composed of indoor and outdoor unit. Indoor unit


is configured with scroll compressor, large surface evaporator, EC fan, wet-
film humidifier and electric heater. The cooling capacity is 13kW, and it is
commonly deployed around the equipment room. NetCol8000-A013U
is an efficient, reliable and simple solution, which helps to build next
generation green data center.

Application Scenarios
•• Data center power distribution room NetCol8000-A013U
•• Small computer room
•• Communication room

Value & Features


Efficient

•• Full DC variable frequency design, cooling capacity stepless regulation,


high efficiency at partial load
•• Wet-film humidifier, save energy 95%+ compared with electrode
humidifier

Reliable

•• 6kV surge protection level, greatly reduces the risk of lighting strike
Condenser Appearance
•• Works stably at extremely ambient temperature, with less cooling
capacity derating

Simple

•• The unit is delivered with refrigerant for 30m long pipes, fast install
on-site
•• The connectors of indoor and outdoor unit adopt welding-free design,
easy to install and maintain

72
Technical Specification

Indoor Unit Technical Specification


NetCol8000- NetCol8000- NetCol8000- NetCol8000- NetCol8000-
Unit Model Unit
A013U A045D/U A060D/U A090D/U A120D/U
AirDischarge Direction - Upflow D: Downflow; U: Upflow

Total Cooling Capacity1 kW 13.0 45 60 90 120

Sensible Cooling
kW 11.7 45 60 90 120
Capacity

AirVolume m3/h 3600 11250 11250 22500 25000

PowerSupply Voltage V/Ph/Hz 380-415/3/50(60) 380/400/415/3Ph/50/60Hz

Heating Capacity
kW 4.0 6 6 12 12
(Optional)

HumidifierCapacity
kg/h 3.0 6 6 10 10
(Optional)

Dimension:W×D×H mm 800×664×1886 900*900*2000 1100*1000*2000 1800*1000*2000 2200*1000*2000


2
NetWeight kg 141(153) 355 600 643 850

1. Nominal cooling condition: Return air dry bulb temperature 24ºC/RH50%, outdoor temperature 35ºC.
2. The data in bracket is suitable for the unit with heater and humidifier.

Outdoor Condenser Technical Specification


Model Unit NetCol500-A022 NetCol500-A060 NetCol500-A080 NetCol500-A090 NetCol500-A120

3/8 in (outer
Power Supply V/Ph/Hz 220-240/1/50(60) Power supply from indoor unit
diameter)

FanQuantity - 2 1 2 2 2

Liquid Pipe Diameter in 3/8 5/8 5/8 5/8 5/8

Gas Pipe Diameter in 3/4 7/8 7/8 7/8 7/8

FullLoad Current A 30 2.5 4.5 5.0 5.0

Dimension: W×D×H mm 903×320×1325 1356×1094×1107 2186×1094×1107 2710×1270×1148 2189×1356×1107

Net Weight kg 117 130 240 290 250

Notice: The pipe diameter is only for reference and it may be changed based on the actual configuration. If the pipe length is longer than 60m, please contact Huawei
system engineer.

73
In-room Air Cooled Cooling Product
NetCol8000-A050D & A100D

Introduction
NetCol8000-A is composed of indoor and outdoor unit. Indoor unit is
configured with scroll compressor, large surface evaporator, EC fan, electric
humidifier and electric heater. Cooling capacity is 50kW and 100kW. And
the fan can be sunk under the floor to further improve air supply efficiency.
NetCol8000-A is an efficient, reliable and simple solution, which helps to
build next generation green data center.

Application Scenarios
•• Small and Medium sized Enterprise data center
•• Carrier base, city/district level data center NetCol8000-A Appearance
•• Financial branches

Value & Features


Efficient
•• Unique energy-saving algorithm: For single unit, partialload EER is
increased by 26%; For multi units, avoidscompetitive operation, over
30% energy saving
•• Group control:Avoids conflict within a multi-unit system,dynamically
Typical Application
distributes cooling capacity and providesmajor control system backup

Reliable
•• Redundant design: If one circuit is faulty, the operationof the other
circuit is not affected
•• Multiple system protections: Compressor failure andabnormal pressure
protection, insufficient airflow,temperature / humidity out of limit alarm
•• Refrigerant leakage and anti-freeze protection: Whenrefrigerant is
leaked, unit switches off automatically,avoids freezing on evaporator

Simple
•• Modular design: No brazing work for unit disassembly,reduces the
Modular Design
requirement on dimensions of elevator anddoors
•• 100% front access, supports side by side installation,smallest maintenance
space in the industry
•• The control system has self-diagnosis and precautionfunctions, and it
can provide pre-maintenance tips

74
Technical Specification

NetCol8000-A Technical Specification

Unit Model Unit NetCol8000-A050D NetCol8000-A100D

Air Discharge Direction – Down Flow Down Flow

Total Cooling Capacity kW 50.0 100.0

Sensible Cooling Capacity kW 46.8 93.5

Air Volume m3/h 14,000 28,000

Power Supply V/Ph/Hz 380-415/3/50 380-415/3/50

Refrigerant – R410A R410A

Heating Capacity kW 6 12

Humidifier Capacity kg/h 7 10

FullLoad Current A 38.0 76.0

Dimension: W×D×H mm 1140×890×1980 2280×890×1980

Net Weight kg 415 830

Notice: Nominal cooling condition: Return air dry bulb temperature 24ºC/RH50%, condensing temperature 45ºC

Out Door Condenser Technical Specification

Unit Model Unit NetCol500-A072 NetCol500-A088

Power Supply V/Ph/Hz 380-415/3/50

Fan Quantity - 2

Liquid pipe diameter in. OuterDiameter: 5/8

Gas pipe diameter in. Outer Diameter: 7/8

Full Load Current A 4.5 6.25

Dimension:W×D×H mm 2200×1094×1100 2410×1270×1265

NetWeight kg 185 200

75
In-room Chilled Water Cooling Product
NetCol8000-C

Introduction
NetCol8000-C 2.0 is the in-room chilled water smart cooling product
developed by Huawei. Generally, it has a complete cooling system
by combining chillers, chilled water pumps and pipes, etc. Its cooling
capacity covers from 62kW to 253kW. The efficient, reliable and simple.
NetCol8000-C helps to build next generation of green data center.

Application Scenarios
NetCol8000-C
•• Carrier base, province/city level data center
•• ISP, EDC, IDC
•• Finance headquarter, disaster recovery data center
•• Smart city, safe city
•• E-government

Value & Features

Efficient
•• Pressure difference control: save 10%+ energy compared with
1. Smart cooling product 2. IT equipment
ordinary EC fan with supply and return air control
Typical applications
•• Fresh air free cooling: adjust fresh air ratio intelligently, save 30%+
energy comparison with traditional chilled water system

Reliable
•• Modular design: no effect on the operation of the other modules
even if there is one faulty module
•• Dual power sources: dual auto-switch power supply with
independent dual 6kV surge protection and power detection
•• On-line maintenance: hot swappable for control module and
auxiliary power module

Simple
Hot swapped module
•• Digital management: 7“ color touch screen, cooling capacity, air
flow and power consumption could be displayed
•• Malfunction self-diagnosis: eliminate irrelevant failure reason
intelligently and save pending and maintenance time 7h+
•• De-engineering: prefabricate components including air damper, = +
dynamic balance valve, save installation man-hour max. 10h/unit

Discerptible modular design

76
Technical Specification
NetCol8000-C Technical Specification
Unit Model Unit NetCol8000-C070D NetCol8000-C130D NetCol8000-C190D
Air Direction - Downflow
Total cooling
kW 63.2 126.4 189.6
capacity①
Sensible cooling
kW 51.4 102.8 154.2
capacity
Air flow m3/h 13,500 27,000 40,500
Power supply V/Ph/Hz 380-415/3/50, 380-415/3/60
Water flow l/s 3.02 6.03 8.86
Water pressure drop kPa 62.4 85.4 92.7

Full load current A 4.7 (15.2) 8.9 (29.9) 13.1 (34.1)
Dimensions:W*D*H mm 900*1000*2000 1800*1000*2000 2700*1000*2000
Net weight kg 340 635 930

Unit model Unit NetCol8000-C070U NetCol8000-C130U NetCol8000-C190U


Air direction _ Upflow
Total cooling
kW 61.9 123.8 185.7
capacity①
Sensible cooling
kW 50.3 100.6 150.9
capacity
Air flow m3/h 13,200 26,400 39,600
Power supply V/Ph/Hz 380-415/3/50, 380-415/3/60
Water flow l/s 2.95 5.91 8.86
Water pressure drop kPa 60.5 82.6 92.7
Heating capacity kW 6 12 12
Humidifier capacity kg/h 5 8 12

Full load current A 4.7 (15.2) 8.9 (29.9) 13.1 (34.1)
Dimensions:W*D*H mm 900*1000*2000 1800*1000*2000 2700*1000*2000
Net weight kg 330 615 900

Notes:
1. Cooling capacity condition: Return air DB temperature 24℃/RH50%, inlet/outlet water temperature 7℃/12℃, ESP: 20Pa

77
FusionCol Indirect Evaporative Cooling
NetCol8000-E

Introduction
FusionCol is an indirect evaporative cooling product launched by
Huawei.Indirect evaporative cooling technology can extend the free
cooling time significantly, reduce the energy consumption of whole
data center. Built in DX supplemental cooling system can support
continuous cooling. All components include container body structure
are prefabricated in the factory. Box transportation support rapid
installation. Efficient, reliable and simple solution helps customer to
build a green data center.
External

Application Scenarios
•• ISP, IDC, EDC

Value & Features

Efficient
• “Fusion-iCooling” extend free cooling time, maximize the use of natural
cold sources
• Intelligent recommendation of water-saving & power-saving mode
• Match IT load changes in real time, control air supply accurately
• High efficiency heat exchanger, pPUE≤0.07*
• High efficiency EC fan, 30%-100% stepless adjustment

Reliable
• Redundant design of components and there is no single failure Internal
• Support dual power input and continuous cooling
• Modular system design , faulted module isolation

Simple
• Container body design, factory pre-installation and pre-test, support
fast delivery
• Supports automatic fault diagnosis and easy O&M

*Cooling Model:
• Location: London
• IT load:12MW
• Load ratio:50%

78
Technical Specification

Type NetCol8000-E220
Power format 380-415V/3PH/50/60Hz
Total capacity /Sensible capacity 220/220kW
Air Flow 55,000m³/h
Type Direct Expansion Cooling
Supplemental cooling (kW)
Capacity 22-110kW
Supply Temp/Relative Humidity 25℃/50%
Temperature & Humidity
Return Temp/Relative Humidity 38℃/25%
Indoor G4
Filter(EN779)
Outdoor G2

Dimension FsusionCol Without Air duct 6058x2438x3600mm


(LxWxH) Air duct (optional) 5810x2020x800mm
Weight Static weight/Operating weight 5,750/6,300kg
Altitude 0-4000m; no derate<1000m
Communication FE, RS485
Certification CE/ Eurovent/ RoHS/ REACH/ WEEE
Net weight kg 600

(Note: Cooling capacity: Indoor return air temp.38 °C (dry bulb), air supply temp 25°C (dry temp)

79
Data Center Infrastructure Management System
on
em
Data Center Infrastructure Management
System
iManager NetEco6000
Introduction

The NetEco6000 solution is the next-generation data center infrastructure


management system developed by Huawei using intelligent technology.
The NetEco6000 solution provides easy access to data center information
and controls, with optimization analyses that maximize the efficiency of
data center infrastructure.

System Concepts
Digital Maintenance
•• Smart devices combined with intelligent software dramatically improve
O&M efficiency.

Intelligent Operation
•• Supporting U-position capacity management and tenant resource
analysis, NetEco6000 simplifies use of data center resources.

AI Energy Analysis
•• Optimization of data center energy use based on AI technology reduces
annual energy costs.

Security Protection
•• NetEco6000’s security protection frame helps prevent network and data
security issues.

Benefits

Digital Maintenance Intelligent Operation

10 years' labor cost 10 years' rental revenue

2,000,000 873,000 Rack space 3,300,000


USD USD usage USD
(120 racks/ (275 racks/ increase 10-
(1500 racks)
person) person) 20%

NetEco
6000

Data Center Infrastructure Management System

Prefabricated Modular Indoor Modular Large Data Ceneer


Data Center Data Center Power Cooling Environment

82
Product Features

Digital Maintenance
Feature Description Advantage Details
•The overview UI pages show data center
Provides O&M
O&M The O&M UI can be KPIs on a multi-screen grid.
overview of data
Overview customized. •Various dashboards focus on KPIs such as
center
alarms, energy efficiency, and capacity.
Several views support efficient O&M:Device
Topology of power
Provides real-teim monitoring view
Real-Time distribution and
monitoring of data •Topologies of the power distribution and
Monitor refrigeration system show
center facility refrigeration systems
the operating status.
•Layout planning of data halls
•Providing the 3D view of data center,
micro-module
Provides a 3D view of Integrated web 3D view in
3D View •NetEco6000 generates the 3D view
the data center the monitor system
automatically based on the layout of the
data center.
•Supports browsing, inquiry, masking,
redefinition, and threshold setting for each
Views povide ways alarm.
Supports alarm masking
Alarm to deal with device •Sends alarm remote notifications via SMS
with multiple rules.
alarms and email.
•Provides expert experience library that
records alarm-handling suggestions.
•Integration with Huawei IVS video system
supports browsing of real-time video.
•Provides access control for data hall,
Provides video
Security Supports access control for micro-module, and rack, using fingerprints,
surveillance and
Management each rack. passwords, and IC cards.
access control
•Generates alarms for unauthorized access,
and supports opening and closing of doors
remotely.
•Provides views of variables such as current
Monitor network security
Supports access via alarms, device real-time parameters, PUE,
Mobile Access policies to help prevent
mobile device and energy consumption.
intrusions.
•Compatible with Android 4.2.2 and above.
•Supports three layers of temperature
Identifies hot spots
Temperature The number of layers can nephogram.
through temperature
nephogram be customized •Identifies top five hot spots and cold spots
field monitoring
automatically.
•The content and inspection “routes” for
daily inspections can be customized.
Computer room Fills inspection form with
•Daily inspection tasks and data can be
Daily Inspection paperless daily report real-time monitoring data
accessed using mobile device.
via mobile device automatically
•Automatically generates daily inspection
reports.
•Creates risk tickets for the abnormal items
Tracks data center Enables closed-loop risk
Risk Management in daily inspection reports.
risks management.
•Handles closed-loop tracking of risk tickets.
•Creates, dispatches and tracks the alarm
Work orders track
Creates alarm tickets tickets.
Work Order daily operations and
directly from alarm pages •Supports remote notification via email and
maintenance work
SMS.
83
Product Features

Intelligent Operation
Feature Description Advantage Specification
•Supports capacity usage statistics, including rack
Provides capacity Manages the power
space, load-bearing, power capacity, power ports,
Capacity Analysis overview of data and network port of
cooling capacity, and network ports.
center each device.
•Provides KPI dashboard and capacity reports.
•Supports the design of rack-mounted device install
and un-install plans, including U-position, rPDU
•Supports search
socket, and network port.
for recommended
•Supports recommended installation location
installation location.
search.
•Provides U-position
Device Installation Manages IT device •Supports automatic generation of work orders
auto-discovery
Planning install and uninstall recording the installation date, location, equipment
collectors.
model, equipment installation, etc.
•Generates change
•Integrates with ITSM to exchange data
ticket for device
requirements.
installation.
•Automatically identifies changes of rack-mounted
devices using U-position auto-discovery collectors.
•Supports inventory management of IT and facility
devices, including records of activities such as device
install, transfer, uninstall, and maintenance.
•Provides IT device
Manages inventory •Records attributes of assets such as device model,
Inventory library.
information of IT and department, maintenance information, and user-
Management •Manages devices in
facility devices defined attributes.
storage area.
•Provides IT device library showing the device
models of the top manufacturers in the most recent
3 years.
•Supports allocation and pre-allocation of rack and
Tenant Resource Allocates racks to Simplifies rack
U-position resources.
Allocation specific users resource allocation
•Provides statistics of space resource allocations.
•Tracks statistics and trends of data center resource
•Analyzes tenant occupancy rates.
Operation analysis groups. •Identifies tenants whose power consumption
Tenant Resource
based on tenant •Identifies abnormal exceeds the contract limits.
Analysis
resources tenants and most •Identifies valuable tenants whose resources are
valuable tenants. almost exhausted or whose contract will soon
expire.
•Supports PUE analysis of data center, data hall and
Provides PUE of each
PUE analysis of data micro-module.
PUE Analysis data hall and micro-
center •Generates an alarm when the PUE exceeds a
module.
threshold.
•Supports energy consumption monitoring and
statistics of each data hall.
Real-time monitoring Supports energy
Power Consumption •Supports energy consumption monitoring and
of device energy monitoring of each
Monitor statistics of each rack and server.
consumption rack and server.
•Calculates electricity costs based on the energy
price.

84
Product Features

AI Energy Analysis
Feature Description Advantage Details
•cPUE analysis based on the energy
Identifies any abnormal chain identifies any abnormal points
Provides cPUE analysis
Energy Chain Analysis points of energy of energy efficiency.
based on the energy chain.
efficiency •Analyzes UPS energy efficiency to
determine UPS module sleep mode.
Adjusts the CRAC operation to reduce
Energy optimization for Optimizes cooling algorithm its energy consumption by 8%,
iCooling (air-cooled)
air-cooled systems based on AI. accounting for factors such as IT load
and temperature field.
•Adjusts the chiller system operation
Energy optimization for Optimizes cooling algorithm to reduce data center energy
iCooling (water-cooled)
water-cooled systems based on AI. consumption by 8%.
•Compatible with TOPN BMS system.

Product Features

Product Modules
Feature Description Features

O&M overview, real-time monitor, alarm management,


Basic Functions Core program
security management

3D View 3D View
Energy Efficiency Management PUE analysis, power consumption monitor
Cooling Optimization iCooling (air-cooled), iCooling (water-cooled)
Inventory Management Inventory Management
Capacity analysis, device installation planning, rack
Capacity Management
Optional Functions allocation
Tenant Management Tenant resource analysis, tenant resource allocation
Paperless Inspection Daily inspection, risk management
Work Order Work Order
Temperature Nephogram Temperature Nephogram
Mobile App Mobile Access
Northbound Interface SNMP, Web Service, and FTP
System Interfaces
Southbound Interface Third-party system integration, Third-party device monitoring

85
Copyright © Huawei Technologies Co., Ltd. 2018. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademark Notice

, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners.

General Disclaimer HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
The information in this document may contain predictive statements including,
Bantian Longgang
without limitation, statements regarding the future financial and operating results,
Shenzhen 518129, P.R. China
future product portfolio, new technology, etc. There are a number of factors
Tel: +86-755-28780808
that could cause actual results and developments to differ materially from those
Version No.: M3-040174-20170225-E-3.0
expressed or implied in the predictive statements. Therefore, such information
is provided for reference purpose only and constitutes neither an offer nor an
acceptance. Huawei may change the information at any time without notice. www.huawei.com