REQUISITION No.

Project No. Coding REV.NO.


TECHNICAL REQUISITION
COVER SHEET - APPROVAL Unit Project Number Area Code/IA Doc. Type Sequence No.

& AUTHORISATION 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 2 of 4)

1.0 SPECIAL REQUIREMENTS FOR STORAGE, HANDLING, PACKAGING, PRESERVATION & DELIVERY (TO BE LISTED BELOW)

As per Manufacturers Standard/ P.O.

2.0 SPECIAL LEGISLATION / STATUTORY APPROVALS (AS APPLICABLE TO BE LISTED BELOW)

IBR

3.0 ORDER OF PRECEDENCE

3.1 Data Sheets


3.2 Specifications
REQUISITION No.
Project No. Coding REV.NO.
TECHNICAL REQUISITION
DESCRIPTION OF GOODS Unit Project Number Area Code/IA Doc. Type Sequence No.

OR SERVICES 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 3 of 4)

This Requisition is issued for the procurement of the materials or services specified herein. If you have any queries
regarding the TECHNICAL content of the Requisition they should be directed in writing to Jacobs, for the attention of
...............………………………
REQ. NO. OF OR UNITS EQUIPT. OR DESCRIPTION OF GOODS OR SERVICES REV
ITEM QUANTITY MARK NO.
CODE NO./DESCRIPTION/CAT NO.
NO.
AS PER DESIGN, MANUFACTURE, TEST AND SUPPLY OF VORTEX FLOW METER,
1 16 Nos.
DATASHEET WHICH SHALL COMPLY WITH JACOBS DATA SHEET / SPECIFICATIONS.

NOTE

VENDOR DATA REQUIREMENTS


All documents, drawings, schedules, calculations and certificates as described & quantified on the SUPPLIER DOCUMENT REQUIREMENTS form
shall be submitted by the supplier. All documents must be submitted with the Jacobs Requisition reference clearly identified

INSPECTION/ TESTING REQUIREMENTS


Jacobs, acting for and on behalf of the Client, WILL / WILL NOT carry out inspection of the equipment in accordance with the approved Vendor Quality
Plan.
REQUISITION No.
Project No. Coding REV.NO.
TECHNICAL REQUISITION
LIST OF ATTACHMENTS Unit Project Number Area Code/IA Doc. Type Sequence No.

4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 4 of 4)

THE DOCUMENTS LISTED FORM A CONSTITUENT PART OF THE REQUISITION AND MUST NOT BE DEVIATED
FROM UNLESS WRITTEN PERMISSION IS GIVEN BY JACOBS
LINE DOCUMENT NUMBER REV NO. DATE TITLE CHANGED
No. THIS REV.

1 44PS5400-00/JJ.04A/0026 0 09.02.2017 DATASHEET – VORTEX FLOW METER

Specifications

2 IND SS J203 0 08.08.2011 STANDARD SPECIFICATION FOR VORTEX FLOW METER


(5 Pages)

4 ANNEXURE – 1 QA/QC REQUIREMENT

5 ANNEXURE – 2 VENDOR QUALITY PLAN (FORMAT)

6 ANNEXURE – 3 - - CONFIRMATION OF COMPLIANCE WITH REQUISITION


(FORMAT)

7 ANNEXURE – 4 TEMPORARY PROTECTION DURING TRANSPORT

8 ANNEXURE – 5 0 09.02.2017 SUPPLIER DOCUMENT REQUIREMENTS (7 Pages)

9 ANNEXURE – 6 INSPECTION AND TEST

10 ANNEXURE – 7 - INFORMATION/ DOCUMENTS REQUIRED ALONGWITH


11.03.2015
TECHNICAL OFFER (1 Page)

11 ANNEXURE – 8 - - CONCESSION REQUEST (CR) (2 Pages)

12 ANNEXURE – 9 - - NON CONFIRMITY NOTICE (NCN) (1 Page)

13 ………… - FORMAT NO. 2 (EXCEPTION & DEVIATIONS) & 10 (SPARES


- FOR 2 YEARS NORMAL ORGANISATION) (2 Pages)

Standards

14 44PS5400-000-JN-02B-0008 A 06.03.2013 NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS

Procurement

15 Instructions to the Bidder

16 Terms and Conditions.

17 General Conditions of Purchase

18 Appendix i : certificate of conformance to technical


specifications

19 Appendix ii : commercial details

20 Price schedule
M/S. RSPL LIMITED

RSPL CHEMICAL COMPLEX

JAMNAGAR, GUJARAT

DATASHEETS FOR VORTEX FLOW METER

DOCUMENT NO: 44PS5400-000/J.04A/0026

PAGE 1 OF 19

Rev Issue Date Pages Rev Description Prepared Checked Approved


No.
By By By
A 11-Mar-2015 27 Issued for Enquiry NM YDK MDM
0 09-Feb-2017 19 Issued for Purchase KVK HSC MDM
DESIGN DATA SHEET INDEX Rev.
VORTEX FLOW METER JE Doc No.: 44PS5400-000/J.04A/0026 0
Project No: 44PS5400 Sheet 2 of 19
Client: M/S. RSPL LIMITED Item No: ALL
Location: JAMNAGAR, GUJARAT Requisition No: 44PS5400-000-JJ-11A-0026
Plant: RSPL CHEMICAL COMPLEX

SHEET DESCRIPTION REVISION REMARK

1 COVER SHEET 0
2 DESIGN DATASHEET INDEX 0
3 GENERAL NOTES 0
4 01-FIT-0201 0
5 01-FIT-0802 0
6 03-FIT-0102 0
7 03-FIT-2303 0
8 04-FIT-1101 0
9 04-FIT-1201 0
10 04-FIT-1301 0
11 04-FIT-1401 0
12 05-FIT-1401 0
13 12-FIT-0103 0
14 12-FIT-0301 0
15 12-FIT-0302 0
16 12-FIT-0303 0
17 13-FIT-0301 0
18 13-FIT-0302 0
19 25-FIT-0101 0

Rev./Date A Date 0 2 Date 3 Date 4 Date


Description FOR ENQUIRY FOR PURCHASE
Made by NM 11.03.15 KVK 09.02.17
Checked by YDK 11.03.15 HSC 09.02.17
Approved by MDM 11.03.15 MDM 09.02.17
DATA SHEET Project Name : RSPL Chemical Complex

VORTEX FLOWMETER Project No. : 44PS5400


TAG NUMBER Doc. No. : 44PS5400-00/JJ.04A/0026
Sheet No. 3 OF 19

GENERAL NOTES

1 . TRANSMITTER SHALL BE PROVIDED WITH STAINLESS STEEL TAG NUMBER PLATE / LABEL WITH THE FULL ALPHANUMERIC TAG
NUMBER HARD STAMPED, OR DEEP ENGRAVED, PERMANENTLY ATTACHED.

2 . BRASS, COPPER, ALUMINIUM OR ITS ALLOY SHALL NOT BE USED FOR CONSTRUCTION OF THE METER / TRANSMITTER.

3 . 2 NOS. 1/2" NPT ELECTRICAL ENTRY IS REQUIRED .UNUSED ENTRY SHALL BE PLUGGED WITH SS PLUG .

4 . TRANSMITTERS SHALL HAVE ELECTRICAL ISOLATION BETWEEN INPUT AND OUTPUT SIGNALS.

5 VENDOR SHALL PROVIDE THE FULL DEVICE DESCRIPTION (DD) AND COMMON FILE FORMAT (PLUS ANY EDDL OR DTM FILES) FOR
EACH DEVICE TYPE / REVISION TO ENSURE FULL COMPATIBILITY WITH THE HOST SYSTEM.

6 OVERALL ACCURACY SHALL INCLUDE COMBINED EFFECTS OF LINEARITY, HYSTERESIS AND REPEATABILITY.

7 VENDOR TO PROVIDE FLOW MULTIPLICATION FACTOR FOR THE METERS WHERE FLOW RANGE WILL NOT FIT IN DISPLAY (4 1/2 DIGIT).

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-15
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 4 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 01-FE-0201 01-FIT-0201 0
2 SERVICE Compressor Air to Salt Dissolver 01G001A/B/C
3 P & ID NO. 44PS5400-001-JP-01D-0002
GENERAL

4 LINE / EQUIPMENT NO. 01-CAD-001-100-A6A-0


5 LINE SIZE (mm) & RATING 100 Class 150
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS STD
10 FLUID Compressor Air
11 FLUID STATE Air
12 FLOW RATE MIN / OP. / MAX (Nm3/hr) 324.6 1623 1947.6
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 45 -


14 PRESSURE MIN / OP. / MAX (bar g) - 5.7 -
15 DESIGN TEMPERATURE (°C) 70
16 DESIGN PRESSURE (bar g) 11
17 SPECIFIC GRAVITY 7.89 Kg/m3
18 VISCOSITY (cP) 0.021
19 % SOLIDS NA
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.9994
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 80 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 80 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF030SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (Nm3/hr) 0 - 2350
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (Nm3/hr) 311.78
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Not Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B8, A194 GR.8M

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 5 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 01-FE-0802 01-FIT-0802
2 SERVICE Contaminated Condensate to brine sludge tank 01V007
3 P & ID NO. 44PS5400-001-JP-01D-0008
GENERAL

4 LINE / EQUIPMENT NO. 04-CC-055-80-A4S-0


5 LINE SIZE (mm) & RATING 80 Class 150
6 PIPE LINE MATERIAL FRP Derakene 411
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS PIPE ID: 80 mm, PIPE OD: 98.8 mm
10 FLUID Contaminated Condensate
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX (m /hr) 1.002 5.01 7.515
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 51 -


14 PRESSURE MIN / OP. / MAX (bar g) - 2.762 -
15 DESIGN TEMPERATURE (°C) 100
16 DESIGN PRESSURE (bar g) 9
17 SPECIFIC GRAVITY 0.988
18 VISCOSITY (cP) 0.55
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 40 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 40 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF015SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0-9
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 1.59
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Not Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B8, A194 GR.8M

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 6 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 03-FE-0102 03-FIT-0102
2 SERVICE RO Water to lime mill 03B002A
3 P & ID NO. 44PS5400-003-JP-01D-0001
GENERAL

4 LINE / EQUIPMENT NO. 03-PW-001-100-A3S-0


5 LINE SIZE (mm) & RATING 100 Class 150
6 PIPE LINE MATERIAL FRP Isopthalic
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS PIPE ID: 100 mm, PIPE OD: 108.8 mm
10 FLUID RO water
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX (m /hr) 8.828 44.14 52.96
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 35 -


14 PRESSURE MIN / OP. / MAX (bar g) - 1.2 -
15 DESIGN TEMPERATURE (°C) 60
16 DESIGN PRESSURE (bar g) 7.2
17 SPECIFIC GRAVITY 0.994
18 VISCOSITY (cP) 0.72
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 80 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 80 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF030SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0 - 65
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 5.7
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Not Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B8, A194 GR.8M

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 7 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 03-FE-2303 03-FIT-2303
2 SERVICE Steam-Medium pressure to Flash tank Ejector 03K002A/B/C
3 P & ID NO. 44PS5400-003-JP-01D-0023
GENERAL

4 LINE / EQUIPMENT NO. 03-OS1-001-150-D2A-1


5 LINE SIZE (mm) & RATING 150 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS XS
10 FLUID Steam-Medium pressure (Overheated Steam)
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 1348.8 6744 8092.8
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 250 270


14 PRESSURE MIN / OP. / MAX (bar g) - 31 -
15 DESIGN TEMPERATURE (°C) 385
16 DESIGN PRESSURE (bar g) 37 / FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.0179
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.87
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 100 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 100 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF040SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 9700
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 1133.72
52 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
53 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
54 ATEX N/A
55 SIL N/A
CERT.

56 PMI Required
57 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK YDK
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 8 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 04-FE-1101 04-FIT-1101
2 SERVICE Steam-Medium pressure to bottom gas compressor turbine 04CK001
3 P & ID NO. 44PS5400-004-JP-01D-0011
GENERAL

4 LINE / EQUIPMENT NO. 04-OS3-002-200-D2A-1


5 LINE SIZE (mm) & RATING 200 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS XS
10 FLUID Steam-Medium pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 6286 15715 19643.75
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 350 -


14 PRESSURE MIN / OP. / MAX (bar g) - 31 -
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37 / FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.022
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.941
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 150 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 150 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF060SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0- 23600
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 1774
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK YDK
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 9 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 04-FE-1201 04-FIT-1201
2 SERVICE Steam-Medium pressure to middle gas compressor turbine 04CK002
3 P & ID NO. 44PS5400-004-JP-01D-0012
GENERAL

4 LINE / EQUIPMENT NO. 04-OS3-003-200-D2A-1


5 LINE SIZE (mm) & RATING 200 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr. B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS XS
10 FLUID Steam-Medium pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 7332 18330 22912.5
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 350 -


14 PRESSURE MIN / OP. / MAX (bar g) - 31 -
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37 / FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.021
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.941
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 150 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 150 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF060SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 27500
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 1774
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 10 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 04-FE-1301 04-FIT-1301
2 SERVICE Steam-Medium pressure to cleaning gas compressor turbine 04CK003
3 P & ID NO. 44PS5400-004-JP-01D-0013
GENERAL

4 LINE / EQUIPMENT NO. 04-OS3-004-200-D2A-1


5 LINE SIZE (mm) & RATING 200 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS XS
10 FLUID Steam-Medium pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 5600 14000 17500
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 350 -


14 PRESSURE MIN / OP. / MAX (bar g) - 31 -
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37 / FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.021
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.941
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 150 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 150 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF060SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 21000
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 1774
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 11 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 04-FE-1401 04-FIT-1401
2 SERVICE Steam-Medium pressure to gas CO2 gas compressor turbine 04CK004
3 P & ID NO. 44PS5400-004-JP-01D-0014
GENERAL

4 LINE / EQUIPMENT NO. 04-OS3-005-200-D2A-1


5 LINE SIZE (mm) & RATING 200 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS XS
10 FLUID Steam-Medium pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 7332 18330 22912.5
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 350 -


14 PRESSURE MIN / OP. / MAX (bar g) - 31 -
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37 / FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.021
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21 COMPRESSIBILITY 0.941
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 150 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 150 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF060SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 27500
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 1774
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 12 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 05-FE-1401 05-FIT-1401
2 SERVICE RO water to soda solution preparation tank 05V009
3 P & ID NO. 44PS5400-005-JP-01D-0014
GENERAL

4 LINE / EQUIPMENT NO. 05-PW-005-25-A3S-0


5 LINE SIZE (mm) & RATING 25 Class 150
6 PIPE LINE MATERIAL FRP Isopathalic
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS PIPE ID: 25 mm, PIPE OD: 33.8 mm
10 FLUID Process Water
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX ( m /hr) 0.582 1.94 2.13
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 35 -


14 PRESSURE MIN / OP. / MAX (bar g) - 0.75 -
15 DESIGN TEMPERATURE (°C) 60
16 DESIGN PRESSURE (bar g) 7.2
17 SPECIFIC GRAVITY 0.994
18 VISCOSITY (cP) 0.72
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 15 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 15 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF005SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0-3
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 0.43
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Not Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B8, A194 GR.8M

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 13 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 12-FE-0103 12-FIT-0103
2 SERVICE Condensate Medium Pressure to Deareater 12C001A
3 P & ID NO. 44PS5400-012-JP-01D-0001
GENERAL

4 LINE / EQUIPMENT NO. 12-PC2-001-250-A2A-1


5 LINE SIZE (mm) & RATING 250 Class 150
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH 20
10 FLUID Condensate Medium Pressure
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX (m /hr) 50.49 168.3 218.79
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 95 -


14 PRESSURE MIN / OP. / MAX (bar g) - 1.5 -
15 DESIGN TEMPERATURE (°C) 190
16 DESIGN PRESSURE (bar g) 14/FV
17 SPECIFIC GRAVITY 0.962
18 VISCOSITY (cP) 0.3
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 150 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 150 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF060SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0 - 270
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 15.73
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 14 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 12-FE-0301 12-FIT-0301
2 SERVICE Boiler Feed Water from 12C001C
3 P & ID NO. 44PS5400-012-JP-01D-0003
GENERAL

4 LINE / EQUIPMENT NO. 12-BFW-003-250-A2A-1


5 LINE SIZE (mm) & RATING 250 Class 150
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH 20
10 FLUID Boiler Feed Water
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX (m /hr) 52.5 175 210
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 120 -


14 PRESSURE MIN / OP. / MAX (bar g) - 0.98 -
15 DESIGN TEMPERATURE (°C) 220
16 DESIGN PRESSURE (bar g) 5
17 SPECIFIC GRAVITY 0.943
18 VISCOSITY (cP) 0.232
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 200 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 200 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF080SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0 - 250
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 25.63
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 15 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 12-FE-0302 12-FIT-0302
2 SERVICE Boiler Feed Water from 12C001B
3 P & ID NO. 44PS5400-012-JP-01D-0003
GENERAL

4 LINE / EQUIPMENT NO. 12-BFW-002-250-A2A-1


5 LINE SIZE (mm) & RATING 250 Class 150
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH 20
10 FLUID Boiler Feed Water
11 FLUID STATE Liquid
3
12 FLOW RATE MIN / OP. / MAX (m /hr) 52.5 175 210
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 120 -


14 PRESSURE MIN / OP. / MAX (bar g) - 0.98 -
15 DESIGN TEMPERATURE (°C) 220
16 DESIGN PRESSURE (bar g) 5
17 SPECIFIC GRAVITY 0.943
18 VISCOSITY (cP) 0.232
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 200 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 200 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF080SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0 - 250
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 25.63
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 16 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 12-FE-0303 12-FIT-0303
2 SERVICE Boiler Feed Water from 12C001A
3 P & ID NO. 44PS5400-012-JP-01D-0003
GENERAL

4 LINE / EQUIPMENT NO. 12-BFW-001-250-A2A-1


5 LINE SIZE (mm) & RATING 250 Class 150
6 PIPE LINE MATERIAL ASTM A106 Gr.B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH 20
10 FLUID Boiler Feed Water
11 FLUID STATE Liquid
12 FLOW RATE MIN / OP. / MAX ( m3/hr) 52.5 175 210
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 120 -


14 PRESSURE MIN / OP. / MAX (bar g) - 0.98 -
15 DESIGN TEMPERATURE (°C) 220
16 DESIGN PRESSURE (bar g) 5
17 SPECIFIC GRAVITY 0.943
18 VISCOSITY (cP) 0.232
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 200 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 200 mm Flanged , ANSI 150 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF080SA1N6D1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (m3/hr) 0 - 250
41 ACCURACY ± 0.65% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET N/A
50 LOW FLOW CUT-OFF (m3/hr) 25.63
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required.
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 17 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 13-FE-0301 13-FIT-0301
2 SERVICE Medium Pressure Steam to Spray Attemperator 13A005
3 P & ID NO. 44PS5400-013-JP-01D-0001
GENERAL

4 LINE / EQUIPMENT NO. 13-OS3-025-250-D2A-1


5 LINE SIZE (mm) & RATING 250 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr. B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH XS
10 FLUID Steam Medium Pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 4400 44000 50600
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 393 -


14 PRESSURE MIN / OP. / MAX (bar g) - 32.5 -
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37/FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.024
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.2
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 200 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 200 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF080SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 60720
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 3358
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 18 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 13-FE-0302 13-FIT-0302
2 SERVICE Medium Pressure Steam to Spray Attemperator 13005B
3 P & ID NO. 44PS5400-013-JP-01D-0003
GENERAL

4 LINE / EQUIPMENT NO. 13-OS3-042-150-D2A-1


5 LINE SIZE (mm) & RATING 150 Class 600
6 PIPE LINE MATERIAL ASTM A106 Gr. B
7 HAZARDOUS AREA CLASSIFICATION Safe Area
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH XS
10 FLUID Steam Medium Pressure
11 FLUID STATE Vapors
12 FLOW RATE MIN / OP. / MAX ( kg/hr) 1140 5700 6555
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 393 404


14 PRESSURE MIN / OP. / MAX (bar g) - 32.5
15 DESIGN TEMPERATURE (°C) 420
16 DESIGN PRESSURE (bar g) 37/FV
17 SPECIFIC GRAVITY 0.62
18 VISCOSITY (cP) 0.0162
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.15
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 80 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Extended / MultiVariable Output With Integral Temperature Sensor
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 80 mm Flanged , ANSI 600 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF030SA6E6D1MTAM5R33Q4Q8Q70Q76
37 TYPE SMART Transmitter
38 MOUNTING Remote
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE (kg/hr) 0 - 7866
41 ACCURACY ± 1% of rated flow
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Downscale (Configurable)
49 MOUNTING BRACKET Required ( SS316,suitable for 2'' Pipe)
50 LOW FLOW CUT-OFF (kg/hr) 441.36
51 SENSOR TO TRANSMITTER CABLE 10 m Refer Note-3
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX N/A
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required. Refer Note-4
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Cable shall be armoured type , vendor to provide SS cable gland for both ends.
4 Inspection certificate weld examination (flanged) per ISO 10474 3.1B and EN 10204 3.1 is required

NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
DATA SHEET Project Name : RSPL Chemical Complex
VORTEX FLOWMETER Project No. : 44PS5400
Doc. No. : 44PS5400-000/JJ.04A/0026
Sheet No. 19 Of 19
REV.
1 TAG NO. (FLOW ELEMENT / TRANSMITTER) 25-FE-0101 25-FIT-0101
2 SERVICE NH3 Storage Tank 25V001A/B to NH3 Absorbers
3 P & ID NO. 44PS5400-025-JP-01D-0001
GENERAL

4 LINE / EQUIPMENT NO. 25-AL-002-50-B4A-5


5 LINE SIZE (mm) & RATING 50 Class 300
6 PIPE LINE MATERIAL LTCS (ASTM A 333 Gr.6)
7 HAZARDOUS AREA CLASSIFICATION Zone-2, IIB,T1
8 MANUFACTURER EMERSON ROSEMOUNT
9 PIPE SCH / THICKNESS SCH STD
10 FLUID Ammonia
11 FLUID STATE Liquid Ammonia (Ammonia Gas-NOTE 3)
12 FLOW RATE MIN / OP. / MAX m3/hr 1 1.5 2
PROCESS DATA

13 TEMPERATURE MIN / OP. / MAX (°C) - 37 -


14 PRESSURE MIN / OP. / MAX (bar g) - 35 -
15 DESIGN TEMPERATURE (°C) -35/55
16 DESIGN PRESSURE (bar g) 24
17 DENSITY (Liquid/ Gas) kg/m3 593.41
18 VISCOSITY (cP) 0.124
19 % SOLIDS
20 ALLOWABLE PRESSURE DROP (bar) 0.25
21
22 MODEL NO. ROSEMOUNT 8800D
23 TYPE Vortex shedder type
24 METER SIZE 25 mm
25 BODY MATERIAL SS316/SS316L
FLOW ELEMENT

26 SHEDDER MATERIAL SS316/SS316L


27 SENSOR TYPE Standard
28 SENSOR MATERIAL SS316/SS316L
29 END CONNECTION SIZE / TYPE & RATING 25 mm Flanged , ANSI 300 # RF
30 FLANGE MATERIAL SS316/SS316L
31
32
33
34
35
36 MODEL NO. 8800DF010SA3N6D1I1M5Q4Q8Q76
37 TYPE SMART Transmitter
38 MOUNTING Integral
39 POWER SUPPLY 24 VDC, Two wire
40 CALIBRATION RANGE L-m3/hr(G-kg/hr) 0-3(0-260)
41 ACCURACY (Liquid/ Gas) ± 0.65% of rated flow for GasLiquid , ± 1 % of rated flow for Gas
TRANSMITTER

42 CONDUIT CONNECTION 1/2'' NPT (F) - 2 Nos.


43 OUTPUT SIGNAL 4-20 mA, HART
44 DIGITAL COMMUNICATION HART
45 INTEGRAL DISPLAY LCD INDICATOR
46 ENCLOSURE WEATHER PROTECTION IP 66
47 ENCLOSURE MATERIAL 316 SST Housing
48 FAILURE MODE Upscale (Configurable)
49 MOUNTING BRACKET N/A
3
50 LOW FLOW CUT-OFF L-m /hr(G-kg/hr) L-0.94(G-61.58)
51 SENSOR TO TRANSMITTER CABLE N/A
52 STRAIGHT RUN REQUIREMENT Upstream 10D- Downstram 5D (Typical)
53 ATEX ATEX Intrinsic Safety
54 SIL N/A
CERT.

55 PMI Required
56 MATERIAL CERTIFICATE Required
57 IBR CERTIFICATE Not Required
58 OTHER CERT: (CCOE / CE / CALIBRATION) Calibration certificate required (Liquid and Gas)
1 N/A : Not applicable
NOTES

2 Bolt / Nut material shall be A193 GR.B7, A194 GR.2H


3 Flowmeter shall be designed for vapour fluid state also, following are the process parameters.
Flow (Min/ Oper./Max)= 69.55/ 139.1/ 208.6 kg/h and density 8.1 kg/m3 all other process condition remain same.
L-Liquid, G-Gas
NO. A 0
REV. Issued for Enquiry Issued for Purchase
DATE 11-Mar-15 9-Feb-17
PREP. NM KVK
CHECK YDK HSC
APPR. MDM MDM
Page 1 of 5

STANDARD SPECIFICATION

VORTEX FLOWMETER

DOCUMENT NO : IND SS J203

Rev. No. Issue Date Pages Rev. Description Prepared Checked Approved

By By By

0 8 August 2011 5 Issued for Use RV PV KA

IND SS J203_VFM
DATE: 8 August 2011 STANDARD SPECIFICATION: IND SS J203
PAGE: 2 OF 5 VORTEX FLOWMETER
REVISION NO: 0

TABLE OF CONTENTS

1.0 PURPOSE

2.0 SCOPE

3.0 TECHNICAL REQUIREMENTS

3.1 General
3.2 Type of Meter & Selection Criteria
3.3 Installation Requirements
3.4 Nameplate & Tagging
3.5 Quality Assurance & Certification
3.6 Deviations

4.0 RELATED DOCUMENTATION

5.0 ATTACHMENTS

IND SS J203_VFM
DATE: 8 August 2011 STANDARD SPECIFICATION: IND SS J203
PAGE: 3 OF 5 VORTEX FLOWMETER
REVISION NO: 0

1.0 PURPOSE

The purpose of this Specification is to define the Requirements of Design, Manufacture and
Testing of Vortex Flow meters.

2.0 SCOPE

The scope of work is design, manufacture, testing and supply of Vortex Flow meters as per
this standard specification and the design data sheets. The inspection requirements shall be
as per the Inspection Plan and vendor documents deliverables shall be as per Vendor
Document Requirements.

3.0 TECHNICAL REQUIREMENTS

3.1 GENERAL

3.1.1 Vortex flow meters are used for measurement of liquid, gas or steam. Generally, Vortex flow
meters are preferred for the following reasons.

1) Where high accuracy is required


2) Where no maintenance spare is expected
3) Where process is a clean service
4) Where higher rangeability is required, i.e. 10:1

3.1.2 The calibration of the meter is unaffected by operating conditions, i.e. density, pressure,
temperature. Vortex flow meter cannot be recommended for the following services.

1) High viscous and slurry service.

2) Liquids having large concentration of solids and two phase flow or pulsating flow
service.

3.2 TYPE OF METER & SELECTION CRITERIA

3.2.1 There are three types of vortex meters available.


1) Vortex Shedding
2) Vortex Precession
3) Fluidic Oscillation

Of the above, Vortex shedding type is the most commonly used.

IND SS J203_VFM
DATE: 8 August 2011 STANDARD SPECIFICATION: IND SS J203
PAGE: 4 OF 5 VORTEX FLOWMETER
REVISION NO: 0

3.2.2 While selecting the meter the following aspects have to be checked

1) Operating conditions like pressure and temperature

2) Compatibility of the wetted material like sensor, bonding agents with the process fluid.
Ex. for Oxygen service, non-ferrous materials only should be used.

3) For the meter, the minimum flow rate is established by a Reynolds number of 10,000
fluid density and a minimum acceptable shedding frequency, whereas the maximum
flow rate is governed by the meter pressure loss and the onset of cavitation of liquids
and compressibility of gases. Hence, the flow range for any application depends
mainly on fluid viscosity, density, vapour pressure, maximum flow rate and line
pressure.

4) Low viscosity liquids do have a rangeablility as high as 40:1 with a low pressure loss.
The rangeability decreases with increase in viscosity. Hence, Vortex meter is not
suitable for high viscous liquids.

5) Line pressure should be checked so that cavitation does not occur. Manufacturer's
guidelines should be followed in this.
Typically minimum acceptable upstream pressure is > 1.3 x vapour pressure + 2.5 x
net pressure loss across the meter.

3.3 INSTALLATION REQUIREMENTS

3.3.1 Vortex shedding meters require a fully developed flow profile. Hence, the flow meter should
be installed in straight unobstructed pipe to ensure that it will perform to its full capabilities.
Also, flow meter performance varies with the type of pipe and pipe fittings used in line. Hence,
the manufacturer's guidelines should be followed with reference to the upstream and
downstream straight pipe requirements.
Also, it is recommended that when control valves are required to be mounted down stream of
the flow meter, it should be ensured that back pressure is sufficient to prevent cavitation at the
flow meter.

3.3.2 Installation position of electronics housing of the meter should be as given below for the
following mediums:

1) Steam: The electronics shall have features for compensating changes in process
temperature.

2) Gas: The recommended position for electronics housing is above the flow tube body.

IND SS J203_VFM
DATE: 8 August 2011 STANDARD SPECIFICATION: IND SS J203
PAGE: 5 OF 5 VORTEX FLOWMETER
REVISION NO: 0

3) Liquid with solid particles: The electronics housing should be above the flow tube
body. Care to be taken so that air or sediment does not accumulate in the sensor
cavity.
For clean liquid, the electronics housing can be mounted above or below the body.

3.4 NAMEPLATE & TAGGING

Each meter shall be identified with a permanent label bearing the tag number.

The following details shall be furnished in English language.

1) Manufacturer's name
2) Model number
3) Serial number

3.5 QUALITY ASSURANCE AND CERTIFICATION

3.5.1 The Seller shall maintain an effective quality system. A concise description of the vendor’s
system and its proposed application to the Scope of Work, including references, where
applicable, to a quality manual or similar authorised company document, is required with the
Quotation.

3.5.2 A List of Documents, in dossier form, shall be retained as evidence or proof that the product or
service supplied complies with specific requirements.

3.5.3 A quality plan, indicating the verification activities that will be applied in order to achieve the
required quality will be required to be submitted for approval.
This Quality Plan will include all sub-contractors used in the performance of the work.
The agreed quality plan will be the control document for the performance of the work.

3.6 DEVIATIONS

3.6.1 Deviations from specification must be stated in writing at the quotation stage.

3.6.2 In the absence of such a statement it will be assumed that the requirements of the
specification are met without exception.

4.0 RELATED DOCUMENTATION

Nil

5.0 ATTACHMENTS

Nil

IND SS J203_VFM
PROJECT NO.: 44PS5400 REQUISITION NO.: 44PS5400-000/JJ.111A/0026

TITLE: ANNEXURE 1 - QA/QC REV.NO. 0


REQUIREMENTS ISSUE DATE: 09-FEB-17
PAGE 1 OF 1

QA/QC REQUIREMENTS

Criticality Rating
1 2 3 4
1. Supplier pre-qualification prior to enquiry x x x X

2. Supplier to supply typical quality control plan with bid x x

Supplier to supply project specific Quality Plan after PO receipt (see


3. x x
Note 3)

Supplier to supply design documentation/procedures for review after


4. x
PO receipt

5. Approval of sub-suppliers required x

6. Copies of all sub-orders required x

7. Pre-inspection meeting required (see Note 2) x x

Witness functional and final testing by specialist Engineers /


8. x x
Inspector

Final inspection and issuance of inspection release note (see Note


9. x x x
1)

10. Documentation as required (see Note 4) x x x x

11. Receipt inspection at site and GRN issued x x x x

Note

1. For items of equipment with a criticality rating of 3, witness of functional and final testing and/or final
inspection and issuance of inspection release certification, will only be undertaken when it is specified
as a requirement of the Purchase Requisition.

2. Pre-inspection meeting will be held on all criticality 1 rated Purchase Orders and “as agreed” with
requisition originator on criticality 2.

3. The extent of surveillance and final inspection shall be agreed based upon the supplier Quality Plan.

4. Documentation shall be supplied as specified in the supplier document requirements.


PROJECT NO.: 44PS5400 SPEC.NO: ANNEXURE 4
REV.NO. / ISSUE DATE: 0 / 09.02.17
PAGE 1 OF 1
TITLE: TEMPORARY PROTECTION
DURING TRANSPORT

TEMPORARY PROTECTION DURING TRANSPORT

1) Prior to shipment and after completion of all shop tests and inspections, all parts
(including flange facings) shall be thoroughly flushed and/or cleaned of all foreign matter.
2) All protection shall be such that equipment may be stored in the open, unsheltered,
except for very small items which can be stored under cover, or for machinery which is
specifically ordered for indoor installation.
3) Suitable grades of protectives shall be applied to guard the equipment against corrosion
for a period of at least eighteen months for export sites (or atleast six months for home
sites) from the date of dispatch or as specified on the data sheets; the protective
application to be adequate whether the equipment remains in the packing case or is
removed on site. Such coatings shall be easily removable for cleaning at site.
4) Selected protectives shall suit the equipment and also the climatic conditions during
transit and storage (e.g. tropical, high humidity), extreme cold, rapid temperature
changes, etc.) Details of the climatic conditions will be found in the specification.
5) If the manufacturer considers that his equipment should not be stored in the packages or
crates used for transportation, this shall be stated on the advice note and the boxes shall
be painted with a bright yellow band at least 75 mm (3 inch) wide. (Applicable only where
packaging is not part of Vendor’s scope)
6) -Lubricated surfaces of valves shall be coated with the appropriate protective lubricating
grease.
-Bare metal surfaces of critical nature, like machined surfaces, shall be protected against
mechanical damage after coating with an appropriate protective material.
-Valves and / or fittings shall be firmly packed in such a way as to prevent movement in
transit by using shredded wax paper or internal fixing battens.
7) External surfaces of mechanical equipments and electrical motor shall be prepared and
finish painted as per the painting specification enclosed with this requisition. Where
possible the finish colour shall be light grey or as specified by the purchaser.
8) Gears and bearings normally oil lubricated, shall be filled with an appropriate protective
oil to match the lubrication oil. Bearings normally grease lubricated shall be packed, with
appropriate grease.
9) The method employed to prevent damage to bearings due to vibration and shocks in
transit shall be submitted for approval by purchaser/consultant.
10) The recommendation indicated above are of general nature only and supplier shall follow
recommendations of the manufacturers of any protective medium selected. These
recommendations shall not absolve the supplier from his responsibilities.
11) All the equipment shall be protected for atleast six months outdoor storage and
seaworthy packing shall be provided during transport.
12) These are minimum requirements. Vendor shall submit the detailed Protection and
preservation procedure post order based on his experience.
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 1 of 7)

The following notes should be read carefully as they explain how to interpret the attached sheets.
If you do not understand what the documentation requirements are please contact Document Control immediately.
The Supplier shall furnish the number of copies, prints or reproducible as listed below. All documents shall be
accompanied
accompanied by a covering letter (in duplicate) quoting titles of data, references, etc., addressed to
Document Control
NOTES

1. Dimensions and calculations to be metric


2. Language requirements: English
3. Preliminary drawings & documents to contain sufficient information to enable Jacobs to proceed with detail design
4. The Jacobs requisitioning Engineer shall complete the “Jacobs Req’d Date” column with his required date for the
submission of all documentation by indicating PO (Purchase Order) + a number of weeks.
5. The Supplier shall complete the “Supplier Proposed Date” column indicating his proposed submission date. At the
same time the Supplier shall advise those documents he will not be submitting because the information required is
provided for within another document. The Supplier shall also advise how many documents he will be supplying
within each category.
6. The Jacobs requisitioning Engineer shall complete the “Agreed Date” column after discussion with the supplier
indicating ACTUAL CALENDAR DATES
7. The Supplier shall issue completed Supplier Document Schedule (SDS) within two weeks of PO. The SDS
shall list the actual documents being provided. All documents shall be numbered doc. category no.-three-
digit sequential number e.g., if 3GA drawings and 2 Cross-sectional drawings are being provided, they
shall be listed B01-001, B01-002, B01-003, B03-001, B03-002 in Jacobs Document Category column of the
SDS. The Supplier will be required to submit all documentation in accordance with the agreed dates.
8. Jacobs will review the documents and return them to the Supplier within 2 weeks of submission.
9. The Supplier shall incorporate the comments and return the document within 2 weeks of receipt from Jacobs.
10. If required, as built drawings to be provided within 30 days of equipment release.
11. Final issue of Documents to be stamped ‘FINAL CERTIFIED’
12. Two hard copies and two soft copies of the handover package shall be provided.

DOCUMENTS WILL NOT BE ACCEPTED UNLESS THE FOLLOWING INFORMATION IS INCORPORATED


ADJACENT TO THE TITLE BOX:-
a. Jacobs Requisition Number d. Equipment Tag Number / Instrument
Tag Number
b. Document Category/Sequence No. (See Note 7) e. Supplier’s Shop or Job Number
c Document Revision Number

SYMBOL NOTES
P = Prints or Copies
R = Reproduceable
PO = Purchase Order
D = Delivered with equipment
T = Test / Final inspection date
S = At supplier’s works
E = Electronic Copy

0 09/02/2017 KVK HSC MDM


A 12/01/2015 NM YDK MDM
REV. NO. DATE PREPARED CHECKED APPROVED
DISTRIBUTION - the requisitioning Engineer shall ensure that each revision of this document is issued to BUYER/
EXPEDITOR and the DOCUMENT CONTROL ENGINEER / PROJECT MANAGER
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 2 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE
A01 SUPPLIER DOCUMENT SCHEDULE 2E PO PO +2Weeks PO 6P@+2
+2Weeks +2Weeks E
ARRANGEMENTS
B01 GENERAL ARRANGEMENTS 2E PO PO +2Weeks PO 6P@+2
+2Weeks +2Weeks E
B02 EXPLODED VIEW DRAWINGS
B03 CROSS SECTIONAL DRAWINGS (INC
PARTS LIST)
B04 PANEL & ANNUNCIATOR LAYOUT
DRAWINGS

ELECTRICAL
C01 ELECTRICAL SCHEMATIC DRAWINGS
C02 INTERCONNECTION DIAGRAMS
C03 TERMINAL BLOCK/ BULKHEAD DIAGRAMS
C04 INTERNAL WIRING DIAGRAMS
(PANEL/EQUIPM’T)
C05 ELECTRICAL SINGLE LINE DIAGRAMS
C06 ELECTRICAL PROTECTION DETAILS
C07 ELECTRICAL TERMINATION & HOOK-UP
DETAILS
C08 ELECTRICAL LOAD (kW RATING)
C09 MOTOR DATA SHEET
C10 VARIABLE SPEED DRIVE PROGRAMMING
INSTRUCTIONS
C11 ELECTRICAL PARTS LIST

P&ID’s & PROCESS SCHEMATICS


D01 PROCESS FLOW DIAGRAMS, HEAT &
MASS BALANCE SHEETS
D02 P & ID & LINE LISTS
D03 SYSTEM SCHEMATICS

INSTRUMENTATION
E01 INSTRUMENT EQUIPMENT OUTLINE
DIAGRAMS
E02 INSTRUMENT LAYOUT DIAGRAMS
E03 LOOP DRAWINGS
E04 INTERFACE DIAGRAMS
E05 INSTRUMENT TERMINATION & HOOK-UP 2E PO PO +2Weeks PO 6P@+2
+2Weeks +2Weeks E
DETAILS
E06 LOGIC DIAGRAMS
E07 CAUSE & EFFECT CHARTS
E08 INSTRUMENTATION WIRING
SCHEMATICS
E09 SYSTEM FUNCTIONAL DESIGN
SPECIFICATION
E10 CONTROL SYSTEMS FUNCTIONAL
DESCRIPTION
E11 RELIABILITY STUDIES & CALCULATIONS
E12 PLC I/O LIST
E13 PLC PROGRAM DISK
E14 PLC PROGRAM LISTING
E15 PNEUMATIC CIRCUIT DIAGRAM
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 3 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE

DATA SHEETS
F01 BILL OF MATERIALS
F02 CATALOGUE DATA SHEET 2E PO PO +2Weeks PO 6P@+2
+2Weeks +2Weeks E
F03 EQUIPMENT DATA SHEET
F04 EQUIPMENT LIST
F05 ELECTRICAL DATA SHEETS

F06 INSTRUMENT DATA SHEETS 2E PO PO +2Weeks PO 6P@+2


+2Weeks +2Weeks E
SCHEDULES
G01 INSTRUMENT LABEL SCHEDULE
G02 UTILITIES SCHEDULE
G03 CABLE SCHEDULE
G04 TRANSIT SCHEDULE
G05 DISTRIBUTION BOARD SCHEDULE
G06 PRODUCTION SCHEDULE
G07 BOLT SCHEDULE
G08 LUBRICATION SCHEDULE
G09 CUSTOMER TERMINAL POINT SCHEDULE
G10 SCHEDULE OF SUB-ORDERS
G11 ELECTRICAL HAZ. EQUIPMENT
SCHEDULE
G12 INSTRUMENT SCHEDULE
G13 VALVE SCHEDULE
G14 PURCHASERS INTERCONNECTION
SUMMARY
G15 PRE-COMMISSIONING CHECKLIST
G16 COMMISSIONING CHECKLIST
G17 MATERIALS OF CONSTRUCTION

DETAILS
H01 ISOMETRIC
H02 PIPE SUPPORTS
H03 VESSELS
H04 TANKS
H05 EXCHANGERS
H06 EQUIPMENT DETAILS
H07 INSULATION/ LINING DETAILS
H08 MECHANICAL SEAL DETAILS
H09 INSTRUMENT PANEL DETAILS
H10 PNEUMATIC HOOK UPS
H11 INSTRUMENT PIPING HOOK UPS

MECHANICAL
J01 NOZZLE MOVEMENTS
J02 ACCEPTABLE NOZZLE LOADS
J03 ENCLOSURE VENTILATION
REQUIREMENTS
J04 FOUNDATION LOADING DIAG.& SUPPORT
DETAILS
J05 AGITATOR LIVE LOAD DATA
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 4 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE
CALCULATIONS
K01 FOUNDATION SUPPORT CALCULATIONS
K02 STRUCTURAL STEEL CALCULATIONS
K03 BEARING LIFE CALCULATIONS
K04 UNBALANCED FORCE CALCULATION
K05 ACCELERATION EFFECT CALCULATION
K06 LATERAL CRITICAL SPEED
CALCULATIONS
K07 TORSIONAL CRITICAL SPEED
CALCULATIONS
K08 SYSTEM HEAD LOSS CALCULATION
K09 STRENGTH CALCULATIONS
K10 THERMAL CALCULATIONS
K11 STRESS ANALYSIS CALCULATIONS
K12 HYDRAULIC CALCULATIONS
K13 HEAT EMISSION CALCULATIONS
K14 GENERAL CALCULATIONS (VIBRATION)
K15 THRUST BEARING LOADS & CAPABILITY
K16 RELIABILITY CALCULATIONS
K17 LIFTING LUG CALCULATIONS
K18 FLOW ELEMENT CALCULATIONS 2E PO PO +2Weeks PO 6P@+2
+2Weeks +2Weeks E
K19 RESTRICTION ORIFICE CALCULATIONS
K20 CONTROL VALVE SIZE & NOISE
CALCULATIONS
K21 RELIEF VALVE CALCULATION
K22 THERMOWELL VIBRATION & STRESS
CALCULATION
K23 INSTRUMENT ELECTRICAL POWER
CALCULATION
K24 INSTRUMENT AIR REQUIREMENTS
CALCULATION
K25 BUS BAR SIZING CALCULATIONS
K26 BOWL STRESS CALCULATIONS

PERFORMANCE DATA
L01 GENERAL PERFORMANCE DATA
L02 NOISE LEVEL DATA
L03 CURRENT TRANSFORMER MAGNETISM
CURVES
L04 MOTOR PERFORMANCE CURVES
L05 HYDRAULIC MOTOR PERFORMANCE
CURVES
L06 ENGINE PERFORMANCE CURVES
L07 CENTRIFUGAL COMPRESSOR
PERFORMANCE CURVES
L08 CENTRIFUGAL PUMP PERFORMANCE
CURVES
L09 ROTARY PUMP CURVES
L10 COMBUSTION GAS TURBINE
PERFORMANCE CURVES
L11 FAN PERFORMANCE CURVES
L12 ELECTRICAL RELAY CHARACTERISTICS
& RATINGS
L13 SPEED/ TORQUE STARTING
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 5 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE
CHARACTERISTICS
L14 CRANK EFFORT DIAGRAMS

PROCEDURES
M01 WELD REPAIR PROCEDURES
M02 VIBRATION/ NOISE TEST PROCEDURE
M03 NDT PROCEDURE
M04 WELD PROCEDURE SPEC. &
QUALIFICATIONS
M05 PERFORMANCE TEST PROCEDURE
M06 MANUFACTURING/ FAB PROCEDURE
M07 HEAT TREATMENT PROCEDURE
M08 WELDING PLAN
M09 HYDROSTATIC & PNEUMATIC TEST
PROCEDURE
M10 SYSTEM TEST PROCEDURE
M11 INSTRUMENT TEST PROCEDURE
M12 LOAD TEST PROCEDURES (CRANES &
DAVITS)

PACKING/ STORAGE
N01 PACKING REQUIREMENTS
N02 STORAGE PROCEDURES
N03 PRESERVATION & DE-PRESERVATION
PROCEDURES
N04 SURFACE CLEANING PREP. & PAINTING
SPEC
N05 RE-PRESERVATION PROCEDURE

SPARES
P01 RECOMMENDED COMMISSIONING SPARE
PARTS LIST
P02 RECOMMENDED SPARES FOR 2 YEARS
CONTINUOUS OPERATION.
P03 SPECIAL TOOLS LIST
P04 RECOMMENDED INSURANCE SPARES

CERTIFICATION
Q01 INTERIM RELEASE/ DESPATCH DOSSIER
Q02 INST./ ELECT. APPROVAL REPORT
Q03 COMPONENT/ ASSEMBLY BALANCE
CERTIFICATE
Q04 STRIPDOWN TEST & RECORD
Q05 NACE CONFORMANCE CERTIFICATE
Q06 HYDROSTATIC/ PNEUMATIC D-2 D-2 Week D-2 Week 6P@+2
Week E
CERTIFICATE
Q07 N.D.T. OPERATOR QUALIFICATIONS
Q08
Q09 WELDERS QUALIFICATION
Q10 HEAT TREATMENT CERTIFICATES
Q11 HEAT TREATMENT CHARTS
Q12 CALIBRATION CERTIFICATES D-2 D-2 Week D-2 Week 6P@+2
Week E
Q13 HAZARDOUS AREA TEST CERTIFICATES D-2 D-2 Week D-2 Week 6P@+2
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 6 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE
Week E
Q14 FIRE TEST CERTIFICATES
Q15 C.A. ACCEPTANCE/ REJECT NOTES
Q16 INSPECTION RELEASE CERTIFICATE (BY 6P@+2
E
JACOBS)
Q17 CODE COMPLIANCE CERTIFICATE
Q18 TYPE TEST CERTIFICATE
Q19 C.A. SURVEY CERTIFICATE
Q20 LIFTING EQUIPMENT TEST CERTIFICATES
Q21 MATERIAL TEST CERTIFICATE D-2 D-2 Week D-2 Week 6P@+2
Week E
Q22 N.D.T. TEST REPORTS D-2 D-2 Week D-2 Week 6P@+2
Week E
Q23 LETTERS OF CONFORMITY D-2 D-2 Week D-2 Week 6P@+2
Week E
Q24 CONCESSION REQUESTS
Q25 NOISE TEST CERTIFICATES
Q26 VIBRATION TEST CERTIFICATES
Q27 SUPPLIER’S QUALITY PLAN 2E PO PO PO 6P@+2
+2Weeks +2Weeks +2Weeks E
Q28 NAMEPLATE DRAWINGS/ RUBBINGS
Q29 PERFORMANCE TESTING CERTIFICATE
Q30 DIMENSIONAL CONTROL REPORTS
Q31 MECHANICAL TEST REPORT
Q32 LIFTING SWL CERT. FOR WIRE ROPES &
SLINGS
Q33 CABLE & WIRING INSTALLATION TEST
RECORDS
Q34 EARTHING CONTINUITY CHECK
RECORDS
Q35 PROOF TEST REPORTS
Q36 DEFLECTION TEST REPORTS
Q37 Q.C. DATA DRAWING (WELD & N.D.T.)
Q38 MATERIAL LOCATION PLAN
Q39 FACTORY ACCEPTANCE TEST
CERTIFICATE
Q40 BEARING NOISE LEVEL REPORT
Q41 BEARING TEMPERATURE REPORT
Q42 V-BELT ELECTRICAL CONDUCTIVITY
CERTIFICATE
Q43 PED CERTIFICATES
Q44 WARRANTY CERTIFICATES
Q45 FILTER RATING CERTIFICATES
Q46 WELDING RECORDS
Q47 SURFACE FINISH CERTIFICATES
Q48 PASSIVATION CERTIFICATES
Q49 POSITIVE MATERIAL IDENTIFICATION D-2 D-2 Week D-2 Week 6P@+2
Week E

WEIGHT
R01 WEIGHING EQUIPMENT CALIBRATION
CERTIFICATE
R02 WEIGHT INFORMATION SHEET
R03 WEIGHT TEST CERTIFICATES

MANUALS
REQUISITION No.
Project No. Coding REV.
SUPPLIER DOCUMENT NO.
Unit Project Number Area Code/IA Doc. Type Sequence No.
REQUIREMENTS.
ANNEXURE 5 4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX STATUS (Enquiry/Order/ Amendment)
REQUISITION TITLE: VORTEX FLOW METER COVER SHEET (Page 7 of 7)

WITH ORDER REQUIREMENT


QUOTE FIRST ISSUE FINAL
No. No. JACOBS SUPPLIER AGREED NO. OF IN
DOC DOCUMENT DESCRIPTION OFF OFF REQ,D PROPOSED DATE SUPPLIER HAND
OVER
CAT DATE DATE DOC.
FILE
S01 INSTALLATION MANUAL INDEX
S02 COMMISSIONING MANUAL INDEX
S03 OPERATING MANUAL INDEX
S04 MAINTENANCE MANUAL INDEX
S05 INST. OP. & MNTNCE. (I.O.M.) MANUAL
INDEX
S06 CERTIFICATION MANUAL INDEX

S07 INSTALLATION MANUAL


S08 COMMISSIONING MANUAL
S09 OPERATING MANUAL
S10 MAINTENANCE MANUAL
S11 INST. OP. & MNTNCE. (I.O.M.) MANUAL D-2 D-2 Week D-2 Week 6P@+2
Week E
S12 QUALITY ASSURANCE MANUAL
S13 CERTIFICATION MANUAL
S14 TECHNICAL MANUAL

T01 AS SHIPPED DRAWINGS

Z01 FAT PLAN


Z02 SAT PLAN
Z03 SUPPLIER FAT REPORTS
Z04 SUPPLIER SAT REPORTS
Z05 RELIEF DEVISE SET PRESSURE TEST
AND CERTIFICATION
Z06 SHIPPING AND BREAKDOWN ASSEMBLY
DRAWINGS INCLDUING LIFTING PICKING
AND RIGGING INSTRUCTIONS
Z07 TSE FREE CERTIFICATE

FURTHER UNIQUE DOCUMENTS TO BE


DETAILED BELOW
@ : COPIES SHALL GO TO
CLIENT
IBR Certificate (Form IIIC). D-2 D-2 Week D-2 Week 6P@+2
Week E
ANNEXURE - 6

INDICATIVE INSPECTION & TEST PLAN**


PROJECT : RSPL CHEMICAL COMPLEX SHEET 1 OF 2

EQUIPMENT / ITEM DESCRIPTION: VORTEX FLOWMETER VENDOR : Emerson Process


Management
P.O. NO. :
RSPL/CCG/KS/PO/289/2016-17
EQUIPMENT / ITEM TAG NO. :
TEST & INSPECTION AS PER : PR/PS NO.44PS5400-000-JJ-11A-
(CODES & SPECIFICATIONS) : 0026
EQUIPMENT INSPECTION CODE : A DRG. NO.
A 1 WITNESS INSPECTION AND / OR DOCUMENT REVIEW BY OWNER / PMC
C
T 2 WITNESS INSPECTION AND / OR DOCUMENT REVIEW BY THIRD PARTY
I INSPECTION AGENCY (TPIA) / STATUTORY AUTHORITY
V 3 WITNESS INSPECTION BY SUB VENDOR,VENDOR & CPC CONTRACTOR
I
T 4 CERTIFICATES / DATA TO BE SUBMITTED BY CPC CONTRACTOR /
Y VENDOR FOR APPROVAL / REVIEW BY TPI A / OWNER / PMC

1 H H X PRE-INSPECTION MEETING TO BE CONDUCTED AFTER ISSUE OF PO


/ PR / PS. AGENDA TO BE PREPARED BY CPC CONTRACTOR
2 A A R X DETAILED INSPECTION & TEST PLAN AFTER ISSUE OF PO/ PR / PS

3 A R X INSPECTION & TEST PROCEDURES


4 A X PACKING PROCEDURE / SHIPPING DRAWING OF COMPLETED ITEMS
5 R R X SUMMARY OF ALL SUPPLIMENTARY REQUIREMENTS AS SPECIFIED
IN THE ORDER / PS / PR
6 A W X WELDING PROCEDURE SPECIFICATION AND PROCEDURE
QUALIFICATION RECORD
7 A W X WELDERS’ QUALIFICATION / WELDERS’ QUALIFICATION RECORDS
FOR STELLITING AND CASTINGS REPAIR
8 R R X MANUFACTURERS’ TEST CERTIFICATES FOR METER BODY,
WETTED PARTS, ACCESSORIES ETC. AS PER BSEN 10204, 3.1
9 H W X NDT (RT, UT, MT, PT ETC, AS SPECIFIED) EXAMINATION RECORDS
*
10 H W X VISUAL CHECK OF ALL ASSEMBLED FLOWMETER
11 H W X DIMENSIONAL CHECK (100% BY VENDOR & AT RANDOM BY TPI)
12 H W X HYDROTEST FOR FLOW METER BODY (100% BY VENDOR & AT
RANDOM BY TPI)
13 H W X FUNCTIONAL/CALIBRATION CHECK ON FLOW METER
14 R R X TEST REPORT FOR DEGREE OF PROTECTION / HAZARDOUS AREA
OF APPLICATION FOR ACCESSORIES
15 R W X VERIFICATION OF IBR CERTIFICATE & MARKING WHEREVER
APPLICABLE.
16 R W X VERIFICATION OF FIRE SAFE DESIGN WHEREVER APPLICABLE
17 R R X REVIEW OF CABLIBRATION RECORDS FOR TESTING INSTRUMENT.
ANNEXURE - 6

INDICATIVE INSPECTION & TEST PLAN**


PROJECT : RSPL CHEMICAL COMPLEX SHEET 2 OF 2
EQUIPMENT / ITEM DESCRIPTION: VORTEX FLOWMETER VENDOR :
P.O. NO. :
EQUIPMENT / ITEM TAG NO. :
TEST & INSPECTION AS PER : PR/PS NO.
(CODES & SPECIFICATIONS) : DRG. NO.
EQUIPMENT INSPECTION CODE : A
A 1 WITNESS INSPECTION AND / OR DOCUMENT REVIEW BY OWNER / PMC
C
T 2 WITNESS INSPECTION AND / OR DOCUMENT REVIEW BY THIRD PARTY
I INSPECTION AGENCY (TPIA) / STATUTORY AUTHORITY
V 3 WITNESS INSPECTION BY SUB VENDOR,VENDOR & CPC CONTRACTOR
I
T 4 CERTIFICATES / DATA TO BE SUBMITTED BY CPC CONTRACTOR /
Y VENDOR FOR APPROVAL / REVIEW BY TPI A / OWNER / PMC

18 H W X PAINTING PROCEDURE / INSPECTION


19 H W X FINAL DOCUMENTATION
20 H X SPARES & PACKING LIST CHECK. PACKING & LOADING OF
EQUIPMENT AS PER SHIPPING DRWING.
21 H H INSPECTION RELEASE CERTIFICATE

LEGENDS : H – HOLD, W – WITNESS, R – REVIEW, A - APPROVAL, I - INFORMATION, X – SUBMIT


PO – PURCHASE ORDER, PR – PURCHASE REQUISITION, PS – PURCHASE SPECIFICATION
** NOTE : THIS IS AN INDICATIVE INSPECTION AND TEST PLAN IDENTIFYING SCOPE OF INSPECTION
/REVIEW OF DOCUMENTS AS A MINIMUM REQUIREMENT, DETAILED INSPECTION AND TEST PLAN
INDICATING ALL SPECIFIED REQUIREMENTS AFTER ISSUE OF PO / PR TO BE GENERATED BY
VENDOR AND SAME DULY APPROVED BY TPI A TO BE SUBMITTED TO OWNER/PMC FOR APPROVAL.
* TPI A TO CARRY OUT INSPECTION AT SUB-VENDORS’ WORKS.
OWNER/PMC RESERVES RIGHT TO WITNESS INSPECTION OF ANY ITEM AT ANY STAGE WHICH SHALL BE INDICATED ON QAP /
INSPECTION & TEST PLAN AT THE TIME OF APPROVAL AND SAME TO BE COVERED AS PART OF PURCHASE ORDER CONDITION
ISSUED BY CONTRACTOR.
ANNEXURE – 8

CONCESSION REQUEST
Part A - To be completed by SUPPLIER
Project No. 44PS5400 1. Name & Location 2. Request No. CR 3. Issue No.

Client: RSPL RSPL Chemical Complex, 4. Date raised


Jamnagar, Gujarat.
5. PO No. 6. Description:
RSPL/CCG/KS/PO/289/2016
-17

7. PO Item No. 8. Supplier Ref. No. 9. Sub-Order No.

10. Tag/Equipment No. 11. Sub-Supplier 12. Sub-Assembly Part No.

13. Drawing & documents affected by Request:

14. Description of Request 15. Attachments


 Yes  No
LIST: -

16. Justification

Signature: Position:
17. Effect on delivery: 18. Effect on Cost if granted
______________If Granted

______________If not  Increase?  Decrease?  Unchanged?


Granted
OTHER FACTORS AFFECTED: (Delete if not applicable) Attach additional sheets providing details
 Strength  Function  Code Compliance  Integrity/Reliability
 Maintenance  Performance  Interchange ability  QA/QC
 Contractual  Approval by CA  Safety/Fitness  Item Life

PART B: - To be completed by Jacobs


1.Resolution Category 2.Amendment to PO 3.Design Change 4.CA Approval
Requirement
Level 1  - Engineering, Yes No Yes No Yes No
Supply Mgmt. Project &
Client
Level 2  - Level 1 + Cert. Reference No. Reference No. Letter No.
Authority
5. Conditions of Acceptance/Usage/Reason for rejection

6. Decisions Approved Signature Date 7. CR Close-out


Engg. Discipline Yes No Name
Purchase Yes No Signature
Inspector/Supplier Yes No Date
Surveillance
Coordinator
Project Manager Yes No Inspection Report Ref:
Client Yes No
Certifying Yes No
Authority
Concession Request (CR)

Concession Request

Requisition No: - 44 PS5400-000-JJ-11A-0026

Procedure For Concession Request Origination & Completion

When a vendor wants to request for a Concession Request, he shall contact the Inspection Manager
(or JE inspection Coordinator) who shall provide a serial number for the request. The Concession
request, properly numbered, shall be addressed to Inspection Manager.

The Q.C. Reports with a complete Concession Request section or a Concession Request shall be
submitted to the Originating Engineer for their evaluation by Inspection Manager (or JE inspection
Coordinator). The request may be submitted to the client Representative and / or A Certifying Authority
when the Originating Engineer has confirmed that this was required.

The Inspection Co-ordinator shall notify the vendor/ contactor of the final decision by returning a copy
of the completed Concession Request Form. Distribution to other Project Personnel shall be
confirmed to project requirements.

The Inspection Co-ordinator / Inspector shall Verify that the deviation approved by the Concession
request has been incorporated into design and / or project documentation.

The Inspection Co-ordinator / Inspector when the vendor / contractor has complied with the condition
approved by the Concession Request, shall complete the ` CR Close Out ‘box on the sellers copy of
the CR form attachment. If a concession has been requested for an order with no inspection, the CR
will be closed out by the appropriate discipline.
REQUISITION No.
ANNEXURE 9 Coding Rev.No.
Area Code Doc type Sequence no
NON – CONFORMITY NOTICE (NCN) Project No.
4 4 P S 5 4 0 0 0 0 0 J J 1 1 A 0 0 2 6 0
PROJECT NAME: RSPL CHEMICAL COMPLEX. STATUS (Enquiry/ Order /Amendment)
REQUISITION TITLE VORTEX FLOW METER

Project No: 44PS5400 NCN No:


Client: RSPL
Location: Jamnagar, Gujarat. Issue Date: 02/07/2017
Plant: RSPL Chemical Complex
PO No: Main Vendor:
RSPL/CCG/KS/PO/289/2016- EMERSON
17 ROSEMOUNT
Sub-order No:
Equipment/Item No: Sub-Vendor:
Non-Conformity Description:

Vendor Representative Signature: ____________ Jacobs Inspector Signature: _____________


Corrective Action Proposed by Vendor:

Vendor Representative Signature: _____________________________________________________


Corrective Action Required by Jacobs:

Per Vendor Proposal: Yes / No

Other (State):
Verified Complete by Jacobs: Client Acceptance: Certifying Authority Acceptance:

Distribution
SPECIFICATION NO : 44PS5400-000-JN-02B-0008

TITLE : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS

PROJECT REFERENCE :

JACOBS Project No : 44PS 5400


Project Title : RSPL CHEMICAL COMPLEX
Client : M/s. RSPL Limited
Project Location : Jamnagar, Gujarat

SHEETS : Sheet Description Pages Page Number


: Cover Page 1 Page Sheet 01 of 12
: Explanation 1 Page Sheet 02 of 12
: Table -1B : Supplier Identifier 1 Page Sheet 03 of 12
: Annexure - I : Process 1 Page Sheet 04 of 12
: Annexure - I : Piping 1 Page Sheet 05 of 12
: Annexure - I : MEG 1 Page Sheet 06 of 12
: Annexure - I : FEG 1 Page Sheet 07 of 12
Annexure - I : Architectural, Civil 1 Page Sheet 08 of 12
and structural
:
: Annexure - I : Electrical 1 Page Sheet 09 of 12
: Annexure - I : Instrumentation 1 Page Sheet 10 of 12
Annexure - II : Sample Deliverable 1 Page Sheet 11 of 12
: list
Annexure - III : JE Revision 1 Page Sheet 12 of 12
: Identification Procedure

- Project Manager Authorisation : Mr. J.M. Badbade Date: 06.03.2013


- Client Authorisation : Mr. V.N. Desai Date:

APPROVALS
Rev. Issue Pages Revision Description By Check Approved
No. Date
A 06.03.2013 12 FOR ENGINEERING SP NVK NVK

 Entire Specification SPECIFICATION ISSUED FOR:


Issued this Revision  In-house Review  Purchase
 Revised Pages Only  Client Approval  Construction
Issued this Revision  Enquiry
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS Page : 2 of 12
Discipline : GENERAL Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.2013
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS


Description Remarks / Notes
Unit Number of Operations 44' to be used
Project Number PS 5400' to be used
Unit Area number / Supplier Identifier Refer Table -1A / 1B
Code of Issuing Authority Refer Table -2
Depart./Group/Discipline Identifier Refer Table -3
Document Type Refer Table -4
Sequential Number identifier commencing from 0001
A
JE 44 PS5400 001 J L 01A 0001
Vendor 44 PS5400 100 V L 01A 0001
Standard UU VVVVVV WWW X1 X2 YYY ZZZZ

Table -1A Table -1B " to be allocated by project as and when LOI / PO is issued to suppliers.
WWW Unit Area number', if X1 is 'J'
000 General Area
001 Brine Preparation & Purification REFER 'TABLE-1B', Page 3 of 12
002 Lime Kiln and Gas Cleaning
A
Lime Grinding, distillation, absorption and Liquid
003 Ammonia Storage
004 Compression and Carbonation
005 Filtration and calcination
006 Densification
007 Soda Ash Storage and Bagging
008 RO & DM Plant
009 DM Water Storage
010 Effluent Treatment Plant
011 Lignite Handling
012 Steam Generation System
013 Steam distribution & power Generation
014 Chilling water system
015 Instrument & Plant Air
016 Salt stockpiling, dissolving and salt wash plant
017 Lime Stone & Coke handling
018 Sea Water Intake Package
019 66 kV Switch yard
Plant General Roads, yards, storm water, effluent
020 Drain
021 Inter plant Pipe rack
022 Substation
023 Central Control Room
024 Fire Fighting System
A
025 Ammonia Unloading Storage and Transfer System
026 HSD & LDO unloading, Storage and transfer system A

027 Spare
028 Spare
029 Spare Table - 3
030 Spare X2 Department / Group / Discipline Identifier
Table -2 A Architectural
X1 Code of Issuing Authority B Spare
J Jacobs C Civil
V Vendor / Contractor
E Electrical
Table -4 F Fired Equipments
YYY Document Type G Safety & Environmental
01X Drawings / Diagrams/ details/ Sketches H Building Services
02X Design basis and Specifications
03X Schedules J Instruments / Control Systems
04X Datasheets K HO Construction
05X calculations L Piping
06X Reports M Mechanical / HVAC
07X Manuals (O&M), databooks etcs N Project Management
08X Material Take-off
09X Material Requisition
10X Purchase Requisition
11X Technical Bid Analysis.
12X Spare P Process
03
Note : For 'X' refer the Annexure Q Quality
R Procurement . Contracts
Table -5 ( DELETED) 03 S Structural
A_ T Document Control
U Contracts Administration
V Vessels / Fabricated Equipments
W Estimating, cost control, planning
X Commissioning
Y Validation
Z Field Construction
Document Title :NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : Table -1B : SUPPLIER IDENTIFIER Page : 03 of 12
Discipline : PROCESS Revision :A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

WWW Supplier Identifier, if X1 is 'V'


>100. PO / LOI No Equipment / Services Vendor / Contractor
100 LOI - dtd 21.06.12 Process Licensor M/s. Niochim
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 04 of 12
Discipline : PROCESS Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


P Process

Code : YYY Description


01A Flow Diagrams / Process Data Diagrams
01D Process P&ID's
02A Specification
02B Design Basis
03A Schedule
04B Equipment Data Sheet
05B Design Calculations
06A Reports
07A Manual

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 05 of 12
Discipline : PIPING Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


L Piping

Code : YYY Description


01A Plot Plans & Equipment Layouts
01B Piping General Layouts
01C Isometrics
01D Pipe Supports
01E Tie-in Schedules & Pipe Supports
01F Fire Fighting System
01G Hazardous Area Classification Drawings
01H Header Distribution Diagrams
01J Interconnection Diagrams
01M Pipe Rack Layouts
01N Nozzle Orientation
01S Sketches
02A Specification
02B Design Basis
04A Data Sheet
05A Calculations
08A Material Take Off
09A Material Requisition Form
10A Technical Bid Analysis
11A Purchase Requisition Form

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 06 of 12
Discipline : MEG Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


M Mechanical / HVAC

Code : YYY Description


01B Equipment Layout
01E Equipment Details
01S Sketches / Schematics
01X Xrefs
02A Specification
02B Design Basis
03A Schedules / List
04A Data Sheet
05B Design Calculations
06A Reports
09A Material Requisition Form
10A Technical Bid Analysis
11A Purchase Requisition Form

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 07 of 12
Discipline : FEG Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


F Fired Equipments

Code : YYY Description


01A Vessels
01B Tanks
01C Columns
01D Heat Exchangers
01E Reactors
02A Specification
02B Design Basis
08A Material Take Off
05A Calculations
09A Material Requisition Form
09B Vendor Document Requirements
10A Technical Bid Analysis
11A Purchase Requisition Form

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 08 of 12
Discipline : ARCHITECTURAL/ CIVIL/ STRUCTURAL Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


A Architectural
S Structural
C Civil

SUB GROUP : ARCHITECTURE (A')


Code : YYY Description
01A General Plans
01B Elevations
01D Development Studies
01E Building Elevations
01G Building Sections
01J Stairs: Lifts: Escalators
01K Detailed Floor/Room Layouts
01L Room Elevations & Sections
01M Wall Sections
01N Interior Finishes
01P Interior Plans
01S Sketches
02A Specification
02B Design Basis
08A Material Take Off
06H Squad Check Register

SUB GROUP : STRUCTURAL (S')


Code Description
01A Steel Drawings
02A Specification
02B Design Basis
05A Calculations
05A Calculations

SUB GROUP : CIVIL (C')


Code Description
01B Site Grading Drawing & Details
01C Foundation Drawings
01D Roads & Drainage
01S Sketches
02A Specification
02B Design Basis
08A Material Take Off
05A Calculations

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 09 of 12
Discipline : ELECTRICAL Revision :A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


E Electrical

Code : YYY Description


01A Single Line Diagrams
01B Control Schematic Diagrams
01C Power ,Lighting & Earthing Layouts
01D Lightning Protection Layouts
01E FA,PA & Communication System Layouts
01G Substation / Room Layout
01H Cable Tray / Trench Layouts
01J Instrument Interface Drawings
01K Symbols
01N Standard Installation Details
01S Sketches
02A Specification
02B Design Basis
03A Schedule ( Cable Schedule,Drum Schedule,Panel Schedule,Interconnection Schedule)
04A Data Sheet
08A Material Take Off
05A Calculations
06A Reports
06V Document Master Register
07A Manual
08A Material Requisition
09B Vendor Document Review
10A Technical Bid Analysis
11A Purchase Requisition

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : ANNEXURE -1 Page : 10 of 12
Discipline : INSTRUMENTATION Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

X2 Department / Discipline Identifier


J Instruments / Control Systems

Code : YYY Description


01A Instrument Drawings / Loop Diagrams ( Drawings)
01B Control Room Layout
01C Analyser Room Layout
01D Logic Diagrams
01E Location Plans
01F Installation Details
01H Hook Ups Drawings
01S Sketches
02A Specification
02B Design Basis
03A Schedule
04A Datasheet
08A Material Take Off
05A Calculations
09A Material Requisition Form
09B Vendor Document Requirements
10A Technical Bid Analysis
11A Purchase Requisition Form

Note : Above Numbers are selected Codes extracted from JPI documentation type list.
Page 11 of 12
Document Title : Sample Deliverable List Format Grade Comments as indicated, revise & resubmit, work may
Discipline : to be filled by discipline / Supplier ANNEXURE - II proceed subject to incorpotration of changes as
Project : RSPL CHEMICAL COMPLEX A indicated.
Client : M/s. RSPL B Comments as indicated, revise & resubmit. Work may
IFC Issued for Construction
Updated on : 28-Feb-13
Area Code of
Prime Doc. Type Sequence
Unit No. Code Issuing Dprt. Milestone -1 Milestone -2 Milestone -3 Milestone -4 Milestone -5 Reciept Date Return Date Rev/ Info
Sr (44)
Number
(Three Authority Identifier
(Two No. Document Number Document Description WBS Code Workhours
(xxxx) (xxxx) (xxxx) (xxxx) (xxxx)
REMARKS
(DD/MM) (MM/DD)
Rev. Grade Remarks
(Vendor)
(PS5400) digit) (4 digit)
digit) (J/V)
UU VVVVVV WWW X1 X2 YYY ZZZZ
1 44 PS5400 100 J C 02B 1000 44PS5400-100-JC-02B-1000 Project Civil Design Basis
2 ----
3 ----
4 ----
5 ----
6 ----
7 ----
8 ----
9 ----
10 ----
11 ----
12 ----
13 ----
14 ----
15 ----
16 ----
17 ----
18 ----
19 ----
20 ----
21 ----
22 ----
23 ----
24 ----
25 ----
26
27
28
----
----
----
SAMPLE
29 ----
30 ----
31 ----
32 ----
33 ----
34 ----
35 ----
36 ----
37 ----
38 ----
39 ----
40 ----
41 ----
42 ----
43 ----
44 ----
45 ----
46 ----
47 ----
48 ----
49 ----
50 ----
51 ----
52 ----
53 ----
54 ----
55 ----
56 ----
57 ----
58 ----
59 ----
60 ----
61 ----
62 ----
63 ----
64 ----
65 ----
66 ----
67 ----
68 ----
69 ----
70 ----
71 ----
72 ----
73 ----
74 ----
75 ----
76 ----
77 ----
78 ----
79 ----
80 ----
81 ----
82 ----
83 ----
84 ----
85 ----
86 ----
87 ----
88 ----
89 ----
90 ----
91 ----
92 ----
93 ----
94 ----
95 ----
96 ----
97 ----
98 ----
99 ----
100 ----

As Sold : 0

Deliverable List
Package : Bauxite Handling Package ( Page 11 of 13)
3/6/2013 ; 11:43 AM
Document Title : NUMBERING SYSTEM FOR DRAWINGS AND DOCUMENTS
Sheet : JE REVISION IDENTIFICATION Page : 12 of 12
Discipline : GENERAL Revision : A
Client : M/s. RSPL LIMITED. Dated : 28.02.13
ANNEXURE - III Project : RSPL CHEMICAL COMPLEX Prepared : PS
Project Number : 44 PS5400 Checked : NVK

This revision identification procedure is based on JE Standard Operating Procedure : S101f2S101f2.doc

The following issue stages (as applicable to specific documents) shall be used for identifying the revision status of
such documents. This is not applicable to general project documentation such as Minutes of Meeting, general
communications, Project Reports, Cost Reports, Project Notes etc.

The first issue of the document shall have the letter ‘P’ in the revision number box.
All subsequent internal revisions of the preliminary document (i.e. not issued outside of the Jacobs organisation)
shall carry the ‘P’ with a number (i.e. P1, P2, P3 etc.) and a new date of issue.

When the preliminary document is ready for client approval and or is to be issued “out” of the office for the first time
say, for enquiry it shall be designated as Revision ‘A’.
All subsequent external issues will have an alphabetical revision notation following on from ‘A’ (i.e. B, C, D,.....).

Where it is necessary to issue further revisions for internal use only, the latest alphabetical revision shall take a
sequential numeric suffix (e.g. B1, B2, etc.). When the document is ready for the next external issue, it shall be
given the next alphabetic revision designator.

Key documents, such as plot plans, equipment arrangements and P&IDs, are ‘Issued for Design’ or ‘Issued for
Engineering’. This issue takes place after client approval and shall be the next letter revision. When no client
approval is required, it shall be designated as Revision ‘A’. All subsequent revisions shall be the next letter revision
(i.e. B, C, D….).

When the document is Approved for Construction and/or Purchase, it shall be issued as Revision ‘0’ (zero). All
subsequent revisions shall be numeric (i.e. 1, 2, 3, ......).

After Revision A and after Revision ‘0’ changes to Technical Documents (such as drawings, specifications, etc.)
shall be identified by using, for example, clouds/bubbles/triangles indicating areas which have changes, with
appropriate annotations describing the change in the revision box. Documents shall be appropriately checked and
approved commensurate with the stage at issue, irrespective of the reason for revision. This does not apply to
single issue documents such as correspondence, minutes, project notes, reports.

When the document is issued at the “As-Built” status, it shall be issued at Revision ‘X’. If necessary, subsequent as-

The originator is responsible for the correct revision identification of the document. The revision sub-division on the
title block shall always reflect the revision status of the document.

DOCUMENT COMPLETENESS

Every document which is composed of multiple pages issued under a single identification number shall be page
numbered on every page of the document (1 of N.. to .. N of N, where N is the total number of pages in the
document), and will also show the appropriate revision number on each page, in the manner illustrated in this
procedure document (see page header above for example). This permits verification of the completeness of any
document.

Where a document composed of multiple pages is to be issued as a complete document the authorising signature