TOP ETHERNET COMMUNICATION MANUAL

IMPORTANT

CAUTION

NOTE

REFERENCE
AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

1 AB COMPACT/CONTROL LOGIX ETHERNET INTERFACE


LET‟S SEARCH HOW TO COMMUNICATE USING ETHERNET BETWEEN AB COMPACT/CONTROL
LOGIX PLC AND XTOP.

1.1 SYSTEM CONFIGURATION

THIS INDICATES THE SYSTEM CONFIGURATION AT THE TIME OF CONNECTING THIS DEVICE
AND AB COMPACT/CONTROL LOGIX PLC ETHERNET.

EXTERIOR COMMUNICATION
CABLE THIS DEVICE
DEVICE UNIT

COMPACT CPU
LOGIX ETHERNETPORT
CONTROL 1756-ENET/B ETHERNET
LOGIX 1756-ENET CABLE XTOP ALL TYPES
1756-ENBT (IEEE 802.3)
1761-NET-ENI
1768-ENBT
ALL CPU ETHERNET PORTS ARE POSSIBLE..

1.2 CONNECTION CONFIGURATION BETWEEN PLC AND THIS


DEVICE

THE FOLLOWING SHOWS THE CONFIGURATION DIAGRAM POSSIBLE TO CONNECT AB


COMPACT/CONTROL LOGIX AND TOP WITH ETHERNET.

MAX 16 PCS

……
……...

HUB

COMPACT/CONTROL LOGIX

IN CASE OF COMPACT/CONTROL LOGIX, IT IS POSSIBLE TO CONNECT UP TO MAX 16 PCS. OF


TOP.

2 AB COMPACT/CONTROL ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

2 COMPACT/CONTROL LOGIX PLC ETHERNET SET


IN ORDER THAT AB ETHERNET CARD IS WORKING, IT IS NEEDED TO SET BASICALLY AS
FOLLOWS: FOR BASIC SET OF ETHERNET CARD, IT IS POSSIBLE TO SET USING RSLOGIX 5000
OF PLC SOFTWARE.
SELECT ETHERNET INTERFACE OUT OF I/O CONFIGURATION LIST OF CONTROLLER
ORGANIZER SCREEN ON THE LEFT OF RSLOGIX 5000.

BY DOUBLE CLICKING THE SELECTED ETHERNET INTERFACE, THERE DISPLAYS MODULE


ATTRIBUTE SCREEN IN THE RIGHT.
BY SELECTING „PORT CONFIGURATION‟ TAP, IT IS POSSIBLE TO DO ETHERNET SET.

3 AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

ITEM PLC SET

IP ADDRESS SET IP OF PLC. NOTE THAT SETING SHOULD NOT BE

DUPLICATED TO IP OF TOP.

SUBNET MASK SET COINCIDING WITH NETWORK ENVIRONMENT.

GATEWAY ADDRESS GATEWAY IP ADDRESS OF NETWORK TO BE CONNECTED TO

PLC

AUTO-NEGOTIATE THIS SETS THE NETWORK SPEED BETWEEN 10/100MBPS

PORT SPEED AND DUPLEX AUTOMATICALLY.

(RECOMMENDING TO USE)

4 AB COMPACT/CONTROL ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

3 DEVICE MAPPING
FOR COMMUNICATING BETWEEN ETHERNET INTERFACE AND TOP, IT IS NECESSARY FOR

MAPPING BETWEEN DEVICE TO BE USED IN ETHERNET COMMUNICATION AND ACTUAL PLC

DEVICE. SELECT CONTROLLER TAGS‟ OUT OF THE CONTROLLER (PROJECT NAME) LIST OF

CONTROLLER ORGANIZER SCREEN IN THE LEFT OF RSLOGIX 5000.

BY DOUBLE CLICKING „CONTROLLER TAGS,‟ „CONTROLLER TAGS‟ SCREEN IS DISPLAYED.

5 AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

INPUT THE NAME OF DATA ARRAY ON THE NAME. THEN BY PUSHING „….‟ BUTTON OF DATA

TYPE, THE SCREEN FOR SELECTING DATA TYPE IS DISPLAYED.

RECORD THE NUMBER OF ARRAY TO BE USED IN DIM 0.

※ IT IS POSSIBLE TO USE ONLY ONE-DIMENSIONAL ARRAY AT THE TIME OF COMMUNICATING


TO TOP. (POSSIBLE TO USE ONLY [0~999] OF DIM0)

6 AB COMPACT/CONTROL ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL
AVAILABLE DATA TYPE AND AREA IS AS FOLLOWS:

TOP DEVICE
DATA TYPE DATA SIZE AVAILABLE AREA
NAME

INT 16BIT 0:0 ~ 999:999 N

DINT 32BIT 0:0 ~ 999:999 B

REAL 32BIT 0:0 ~ 999:999 F

BOOL 32BIT 0:0 ~ 999:999/32 B

FOR MAPPING THE CREATED DATA TYPE ARRAY TO THE ADDRESS FOR ETHERNET
COMMUNICATION, SELECT [LOGIC] -> [MAP PLC/SLC MESSAGES..] ON THE MENU.

BY CLICKING [MAP PLC/SLC MESSAGES..], MAPPING SCREEN IS DISPLAYED.

INPUT THE NAME OF DATA ARRAY IN THE CREATED NAME. BY INPUTTING FILE NUMBER

[0~999] AND CLICKING [OK] BUTTON, MAPPING IS COMPLETED.

※ IN USING SEVERAL DATA ARRAYS, FILE NUMBER MUST NOT BE OVERLAPPED.


USE THE MAPPING DATA ARRAY ON THE TOP DESIGNER.

7 AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

File Number Array Number

INT TYPE IS MAPPING TO N IN THE TOP DEVICE. AFTER SELECTING N DEVICE, INPUT FILE

NUMBER ON THE FIRST THREE FIGURES AND ARRAY NUMBER THE LAST THREE FIGURES,

RESPECTIVELY.

Bit Number

File Number

Array Number

IN CASE OF BOOL TYPE, MUST USE 32 BIT UNIT. IN TOP, BOOL[0~31] IS B[0] AND BOOL[32~63] IS

B[1]. FOR INSTANCE, IF FILE NUMBER IS 3 AND TH ADDRESS IS 33, IT IS TO BE B 00300101 IN

THE TOP. (003 -> FILE NUMBER, 001 -> ARRAY NUMBER, 01 -> BIT NUMBER)

4 DESIGNER AND MAIN MENU ETHERNET SET


4.1 DESIGNER SET
FOR ETHERNET COMMUNICATION TO ETHERNET INTERFACE OF AB COMPACT/CONTROL

8 AB COMPACT/CONTROL ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL
LOGIX PLC, SET AS FOLLOWS AT DESIGNER. THE FOLLOWING FIGURE IS THE DISPLAY AT THE

TIME OF SELECTING PROJECT]->[PROJECT INFO] ON THE MENU OF DESIGNER. FOR ETHERNET

COMMUNICATION TO TOP, FIRST SELECT THE OPTION OF “COMMUNICATION TO PLC WITH

ETHERNET.”THEN SELECT OPTION ACCORDING TO THE SERIAL COMMUNICATION ACCESS AS

WELL AS ETHERNET ON THE BODY.

FOR ETHERNET SET OF AB COMPACT/CONTROL LOGIX PLC, PUSH “SET” BUTTON.

ITEM DESIGNER SET

PLC OR CONTROL DEVICE AB CONTROL/COMPACT LOGIX ETHERNET

IP PLC IP ADDRESS

PORT 44818 (AB CONTROL/COMPACT LOGIX IS FIXED TO 44818.

4.2 MAIN MENU ETHERNET SET


THE ETHERNET SET ITEMS AND CONTENTS IN THE TOP ARE AS FOLLOWS:

BY PUSHING [COMMUNICATION SET] TAB ON THE MENU OF THE BODY AND KEY ON THE

RIGHT BOTTOM, IT IS POSSIBLE TO CONDUCT ETHERNET SET ON THE TOP.

ITEM BODY SET

IP ADDRESS IP ADDRESS OF TOP

SUBNET MASK SUBNET MASK. IF NOT USE, SET ALL ZERO “0.”

9 AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL


AB COMPACT/CONTROL LOGIX ETHERNET COMMUNICATION MANUAL

GATEWAY GATEWAY SET

PORT PORT NO. OF TOP.

PROTOCOL PROTOCOL FORMAT: TCP

TCP MUST BE SELECT „TCP‟ OF PROTOCOL ON THE TOP MENU.

CAUTION

10 AB COMPACT/CONTROL ETHERNET COMMUNICATION MANUAL