600 Dia of Test Pile
600 Dia of Test Pile
Determination of Length of Fixity ( Ref. Amendment 3: Appendix 'C' of IS:2911 (part 1/sec 2)
Modulus of elasticity of concrete E = 5000 SQRT(fck)
E = 250000 kg/cm2
K1 = 0.2075 kg/cm3 (For K1 value Ref Annex-C : Table-3 of of IS:2911 -2010 ,
T = ((E*I)/(K1))^(1/5) (part1/sec 2)
T = 189.2 cm
For Fixed Head Pile in sand & normally loaded clay condition and assuming pile cut off level is below GL (i.e. L 1 = 0)
Lf /T = 2.175 (For Lf/T Refer Amendment-3, Appendix C-fig:2 of IS: 2911 (1/2)
Calculated length of fixity Lf = 4115 mm
Determination of Minimum eccentricity
Minimum eccentricity e = (L/500 + D/30 ) = 69 mm
OR e = 20 mm
Design minimum eccentricity = 69 mm
Bending moment due to eccentricity M = 4.49 T-m
Moment reduction factor = 0.825 (Ref fig. 3A of Appendix C-2 of IS: 2911 (1/2)
Reduced Moment = 10.18 T-m
Design Bending Moment, Mu = 10.18 T-m
d' = 68 mm
d'/D = 0.15
Pu/fckD^2 = 0.193
Mu/fckD^3 = 0.067
p'/fck = 0.060 Using Sp 16 chart no. 61
% of reinforcement required = 1.50
Min Design % Reinforcement = 0.40
Case 2 - Maximum tensile load + maximum horizontal load
The analysis is carried out by converting circular pile section to an equivalent square pile section.
Size of equivalent square section = 398.80 mm
d' = 68 mm
d'/D = 0.171
Tu/fck B D = 0.113
Mu/fck BD^2 = 0.076
p'/fck = 0.07 Using Sp 16 chart no. 85
Reinforcement requirement for Max. vertical & Max. horizontal load Min No of Bars=6
% of reinforcement Reqd = 1.50
Area of reinforcement reqd. = 2386 mm2
Reinforcement requirement for Max. tensile load & Max. horizontal load
% of reinforcement Reqd = 1.75 Min Ast,req Tu/0.87*fy
Area of reinforcement reqd. = 2783 mm2 Min area of reinf = 1034.48 mm2
CHECKING OF JOB PILE FOR ROUTINE LOAD TEST - FOR ONLY BENDING
Factored Lateral load = 6 TON
Fixed End Moment Mf Hu*(L1+LF)/2
12.34 KN
Moment reduction factor = 0.825 (FOR FIXED HEAD PILE FIG 5B IS -2911 -2010)
Mu 10.18 TON M
d' 68.00
d'/D 0.15
Pu 0.00
Pu/fckD² 0.00
Mu/fckD³ 0.067
p/fck = 0.05
p= 1.13
Ast req = 1789.24
PROVIDED AREA OF R/F. = 2865.25 mm^2
OK
DESIGN OF INITIAL TEST PILE - 600 mm Dia
A. Design Philosphy
Piles are designed as per IS 456: 2000 and IS 2911: 1979 (Part1 - Sec 2) using Limit State Method
Following load combinations are considered
1. Maximum horizontal load
2. Maximum vertical load
3. Maximum tensile load
Input Data
Load factor for horizontal load = 2 (as per IS:2911 -2010 ,(part1/sec 2))
Load factor for vertical load = 2.5
Diameter of Pile = 600 mm Pile area = 282743.34 mm2
Grade of concrete (fck) = 25 MPa Moment of Inertia of pile = 635850 cm4
Grade of reinforcement (fy) = 500 MPa
Clear cover to main reinforcement = 75 mm
Diameter of helical reinf = 8 mm
Length of Pile below Cut-off Level = 18 m
Pile Capacity
Vertical Compression (P) = 62.49 MT
Horizontal Load (H) = 4.40 MT
Uplift (T) = 14.14 MT ( UPLIFT WILL BE TAKEN MAXIMUM 14.14 MT IN DESIGN)