Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Cooling

total Cooling
Air flow capacity
NO. Equipment Core No. Level Unit. No Daikin model capacity ESP (Pa)
(CFM) sensible
(btu/hr)
(btu/hr)
1 AHU CL 1 BF AHU-CL-BF-1 DM2-0713B 4992 105423 86366 249
2 AHU PH 1 BF AHU-PH-BF-1 DM2-1013B 6817 160394 122695 249
3 AHU CORR 1 BF AHU-CORR-BF-1 DM2-0715B 6349 132194 119000 249
4 AHU EU 1 GF AHU-EU-GF-1 DM2-1315B 10000 222000 153000 249
5 AHU DI 1 GF AHU-DI-GF-1 DM2-1019B 10520 272000 205000 249
6 AHU OPD 1 L1 AHU-OPD-L1-1 DM2-1819B 16675 471000 330500 373.63
7 AHU OTD 1 L2 AHU-OTD-L2-1 DM2-1819B 14540 320000 238000 373.63
8 AHU OT1 1 L2 AHU-OT1-L2-1 DM2-0410B 2700 210000 81000 821
9 AHU OT2 1 L2 AHU-OT2-L2-1 DM2-0410B 2700 210000 81000 821
10 AHU OT3 1 L2 AHU-OT3-L2-1 DM2-0413B 3496 284000 112000 821
11 AHU ICU 1 L2 AHU-ICU-L2-1 DM2-1013B 7740 178000 129000 249
12 AHU CATH 1 L2 AHU-CATH-L2-1 DM2-0710B 4300 273000 144500 821
13 AHU CSSD 1 L3 AHU-CSSD-L3-1 DM2-0715B 5700 141700 111900 249.09
14 AHU GEN 1 L5 AHU-GEN-L5-1 DM2-1010B 6006 201700 114000 473
15 AHU GEN 1 L6 AHU-GEN-L6-1 DM2-0715B 5749 210000 125000 473