FS-3500E
Instruction manual
We appreciate your purchase of TAKEX flame sensor.
Please read this instruction manual carefully for correct and effective use.
This sensor is designed to detect flames and to initiate an alarm, it is not a fire-preventing device.
TAKEX is not responsible for damage, injury or losses caused by accident, theft, Acts of God (Including inductive surge by lightning), abuse,
misuse, abnormal usage, faulty installation or improper maintenance.
This sensor detects Ultraviolet rays in the flames and initiates an alarm.
It does not detect smoke, heat.
s #HOICE OF SPOKEN MESSAGES OR ALARM SOUND
Features Message can be chosen from Japanese, English, Chinese, Korean, Spanish.
s 0OWER SUPPLY CAN BE SELECTED
DC power by wire or Battery (Batteries are not included.)
1 Parts Description
1-1 $ESCRIPTION Knockout Locking screw hole
Release lever
Terminals
Wiring hole
Wiring hole
Base unit
Wiring hole
Front mark
Battery connector
Detection window
Sensor unit
Volume switch
Mode selector
LED
Speaker
1 2 3 4 5 6 7 8 1 2 3 4
Tapping screw Sensor locking screw
(f4×25) × 2 pcs (f3×6) × 1 pc Language Message N.O./N.C.
Message Choice
Sensitivity
Message time
Message repeat Detection timer
1
2 ATTENTION
Description
Warning If this is ignored, people could face the possibility of death or serious injury.
Notice If this is ignored, people may suffer injury or personal property may suffer damages.
Warning
Do not modify the unit, it may cause fire or
Do not touch the unit with wet hand.
electric shock.
In case the water leaks into the unit, stop using When using batteries, ensure to keep the correct
the unit and power it off, contact the dealer. polarity.
Do not install the unit in a location that cannot Do not heat, remodel the battery, do not put it into
support its weight. water, fire.
Notice
Avoid subjecting the unit to impact. Do not install the unit in the following locations.
This model is designed for indoor use only. Construction site where welding
Do not install outdoor. is done. The arc lamp of welding
includes a very strong ultraviolet
rays which reach flame sensors
Use the designated battery only. even indirectly by the reflection.
Caution
When the patient who carries isotope treatment
Use designated battery only. comes near to detection area, Flame sensor may
issue an alarm, in this case set detection
sensitivity as "L".
Battery life may vary depending on usage and
When the performance of the installed sensor is
installation environment.
unstable and the cause cannot be specified, select
Sensitivity "L" and detection time one step longer
The magnetism or magnetic field which this than current setting.
sensor emits will give some influence to the
devices nearby. When the sensor window is soiled by dust, oil,
Check the situation prior to operation. cigarette smoke, clean with soft cloth moistened
with alcohol.
* Possible cause of false alarm. Do not install the * Followings are not detected by flame sensor
sensor nearby the followings.
Halogen lamp Flames through glass or transparent resin
Electric dischaging lamp such as mercury lamp Lit portion of cigarette
Electric sterilizer lamp Burning charcoal or briquet
Spark from welding Electric stove
Electric spark (Caused by motor, pantograph) Smouldering object
Sunlight
Lightning discharge
High voltage electric field
All objects which emit ultraviolet rays
Although this unit is for indoor use, when it is installed in semi-outdoor, the location must be under eaves without
sunshine and rain.
Also it is recommended to set Detection timer longer than 3 sec. and Sensitivity "L".
Semi-outdoor installation
1 sec H
Detection timer Longer Sensitivity
L
( Factory set : Sensitivity "H"
Detection timer 1 sec )
than 3 sec
This sensor is designed to detect ultraviolet rays in flames, and to output a warning message.
This unit is neither fire detector nor heat detector nor smoke detector. TAKEX is not responsible for damage, injury
or losses by fire, accident, calamity, Acts of God (Including inductive surge by lightning), abuse, misuse, abnormal
usage, faulty installation or improper maintenance.
This unit detects ultraviolet rays from a flame. Prior to the actual operation, adjust the detection
At the same time it detects ultraviolet rays from area carefully and test the performance.
other objects.
Ultraviolet rays are sometimes reflected by walls
This unit does not detect the objects which are or floors which causes unexpected detection
burning without flame. resulting in a false alarm.
3 DETECTION AREA
Detection area spreads out in Object : Flame of gas lighter (7cm)
front of the sensor at approx. approx. 120° Detection area Sensitivity : H
Detection timer : 1 sec.
120° conically.
[m] [m]
7 6 5 4 3 2 1 1 2 3 4 5 6 7 5 4 3 2 1 1 2 3 4 5
The size of the detection area is in proportion to
the size of the flame and detection time. 1 1
Confirm the detection area using a lighter prior 2 H 2 H
to actual operation. 3 3
4 4
5 5
Use the optional BCW-401 universal bracket if 6 6
area adjustment is required. 7 7
8 8
9 9
10 [m] 10 [m]
Sensitivity : L
3
4 WIRING
Terminal arrangement
1 2 3 4 5 6
<<Notice>>
1. In case connecting more than 2 sensors, the wiring distance is } Signal
divided by the number of units.
Control panel
2. Signal line can be connected as far as 1,000m by f0.65 OP wire.
5 INSTALLATION
1 Locate the installation site 4 Arrange power supply by wire or by battery.
Battery
By wiring
(1) Connect the wire to the power terminal.
4
5 Choose message language, set detection timer and
detection sensitivity and adjust message volume. [Installation of base]
Attach the sensor unit to base unit. This product is equipped with installation holes
6 (Pitch 3.29" or 83.5mm) to make installation easy
(1) Turn front marks of base unit and sensor unit to and sensor's direction adjustable.
point in the same direction.
(2) Insert sensor unit into base unit.
(3) Push sensor unit until release lever is locked. Installation hole
Marking
Installation
hole
5mm
(2) Drive the 2 pcs. of tapping
7 Check operation and area. screws (accessory) leaving
5mm exposed from the
surface.
6 FUNCTION
(1) Operation
Alarm (Basic action)
This product gives the following one-shot output only by detecting the flame continuing for the set time of
detection timer.
Detection Detection Detection Detection
ON OFF ON OFF ON OFF ON OFF
Flame
ON ON ON ON
Signal 2s 2s 2s 2s
Message
ON ON ON
Operation LED Blink Blink Blink
1 2 3 4 5 6 7 8 1 2 3 4
Volume setting
When volume switch is set to minimum, Language Message N.O./N.C.
the volume will be mute. Message Choice
Sensitivity
Message time
Detection timer
Message repeat
5
Language selection
Message can be chosen among Japanese, English, Chinese, Korean, Spanish, or just buzzer sound. (Approx. 10 sec.).
Only chosen message by dip switch will be announced.
When no message chosen, only buzzer sound will be announced.
The order of anouncement is Japanese Æ English Æ Chinese Æ Korean Æ Spanish which cannot be changed.
Chosen
Japanese Æ Chinese
1 2 3 4 5
Delete
Spanish English Æ Chinese Æ
Korean Korean
(Factory set : English)
Chinese
English Buzzer sound PiPiPiPi
Japanese
Announcement choice
(Non-smoking) or (Fire prohibition) modes are available.
There are short and long message choices respectively.
Long message
(1) JAP. [ここは禁煙です。お煙草はご遠慮ください。] (3.8s)
(2) ENG. [This is a non-smoking area. Please refrain from smoking in this area.] (5.6s)
(3) CHI. [ ] (3.9s)
6 7
(4) KOR. [ ] (5.0s)
(5) SPA. [Prohibido fumar. Absténgase de fumar en el servicio.] (4.2s)
Non-smoking
Short message
(1) JAP. [ここは禁煙です。] (1.8s)
(2) ENG. [This is a non-smoking area.] (2.6s)
(3) CHI. [ ] (2.1s)
6 7
(4) KOR. [ ] (2.4s)
(5) SPA. [Prohibido fumar.] (1.6s)
Long message
(1) JAP. [ここは火気厳禁です。火気の使用はお断りいたします。] (4.9s)
(2) ENG. [Open flame is prohibited. Please refrain from using open flame in this area.] (6.4s)
(3) CHI. [ ] (4.1s)
6 7
(4) KOR. [ ] (5.5s)
(5) SPA. [Prohibido encender fuego. No se permite el uso de productos inflamables en el servicio.] (5.9s)
Fire prohibition
Short message
(1) JAP. [ここは火気厳禁です。] (2.2s)
(2) ENG. [Open flame is prohibited.] (2.3s)
(3) CHI. [ ] (2.2s)
6 7
(4) KOR. [ ] (3.2s)
(5) SPA. [Prohibido encender fuego.] (2.1s)
6
The following setting is about detection performance.
Sensitivity
3%4 3%4
Detection sensitivity is selectable
H or L. ,å (å
&ACTORYåSETåå(
* Detection distance on "L" setting is 50% shorter than that on "H" setting.
* If the operation is unstable on "H", switch to "L".
så)MMEDIATEåDETECTIONåOFåFLAMEåOFåLIGHTERMATCH
åSEC åSEC
ååATåNO
SMOKINGåAREA
åSEC så&IREåDETECTION
åSEC så)NåTHEåUNFAVOURABLEåCIRCUMSTANCESåOFåTHEåSITE
* When the ultraviolet rays of flame are weak (it is related to size of flame and distance to the sensor), Alarm initiation may be
delayed beyond the set time.
* When installed semi-outdoor, set detection timer 3 sec or longer.
7 OPERATION CHECK
1 Turn power on. In case of battery operation, the 3 Warning message sounds intermittently and LED
buzzer "PiPiPi" sounds. In case of DC operated, no flashes.
buzzer sounds.
4 After turning off the lighter, check if the output
2 Ignite a lighter etc. within detection area for more stops at the set up time. (When external output is
than the set time. used by wiring, a continuous output is issued during
the above 3. and 4. alarm action. Confirm the
operation of the connected devices.)
8 TROUBLE SHOOTING
4ROUBLE
3OLVEåPROBLEMSåACCORDINGåTOåTHEåFOLLOWINGåTABLEå)FåNORMALåOPERATIONSåCANNOTåBEåRESTOREDå
BYåTHESEåCORRECTIVEåACTIONSåCONTACTåEITHERåTHEåDEALERåORå4!+%8
0OSSIBLEåCAUSE #ORRECTIVEåACTION
å.OåBATTERYåCONNECTED å#ONNECTåBATTERY
,OWåBATERY #HANGEåBATTERY
#OMPLETELYåINACTIVE å.OåPOWERåSUPPLYå"ROKENåWIREåORåIMPROPERåWIRE å#ORRECTåWIRINGå
,OWåVOLTAGEå7HENåPOWERåSUPPLYåWIRED !DJUSTåPOWERåVOLTAGE
å'LASSåORåTRANSPARENTåRESINåAREåINTERRUPTINGåTHEåSENSOR å2EMOVEåTHEM
å3ENSORåINSIDEåISåWETåBYåCONDENSATIONåETC å$RYåOUTåSENSORåINSIDEåREMOVEåTHEåCAUSEåOFåMOISTURE
å)MPROPERåAREAåSETTING å2ELOCATEåTHEåSENSORåTOåAPPROPRIATEåPOSITIONåOR
USEå"#7
å/PTIONAL åANDåADJUSTåTHEåANGLE
3OMETIMESåINACTIVE å$ETECTIONåWINDOWåISåSOILEDåWITHåDUST å#LEANåWITHåTHEåSOFTåCLOTHåMOISTENEDåWITHåALCOHOL
å,OWåBATTERY å#HANGEåBATTERY
å,OWåVOLTAGE å#ORRECTåPOWERåSUPPLY
å,ARGEåELECTRICALåNOISEåSOURCEåSUCHåASåAåRADIOåSTATIONåOR å2ELOCATEåTHEåSENSOR
HIGH
VOLTAGEåWIREåNEARBYå å2EMOVEåTHEåORIGINåOFåTHEåULTRAVIOLETåRAYS
!CTIVATEDåWITHOUTåFLAME
å5NEXPECTEDåULTRAVIOLETåRAYSåNEARBYå INTERRUPTåULTRAVIOLETåRAYSåORåRELOCATEåTHEåSENSOR
å3ENSORåINSIDEåISåWETåBYåCONDENSATIONåETC å$RYåOUTåSENSORåINSIDEåREMOVEåTHEåCAUSEåOFåMOISTURE
4HEåALARMå,%$åFLASHES
å,OWåBATTERY å#HANGEåTHEåBATTERYåIMMEDIATELY
åSECONCE
4HEåALARMå,%$åLIGHTSåONå
å4HEåVOLUMEåSWITCHåISåSETåATåMINIMUMå-UTE å!DJUSTåVOLUMEåSWITCH
BUTåNOåSOUNDåFROMåTHEåSPEAKER
4HEåALARMå,%$åANDåSPEAKER
å0OORåCONTACTåOUTPUTåCONNECTIONåORåBROKENåWIRE å#HECKåTHEåCONNECTIONåORåWIRE
WORKåBUTåTHEåWIRE
CONNECTED
å0ROBLEMåATåPANEL å#HECKåTHEåCONNECTEDåPANEL
DEVICESåAREåINACTIVE
Maintenance
When detector elements are stained, spray alcohol to the
When low battery LED blinks, elements and remove the stain.
change battery for new one immediately. Do not use such chemicals as mild detergent, thinner or benzine
If it is left, it could cause inactiveness to clean the detector elements.
of the sensor. When housing is stained, clean it with a soft cloth.
Check the operation once a week.
detector
elements
alcohol
9 SPECIFICATIONS
Model FLAME SENSOR WITH SPEAKER
10 DIMENSIONS (mm)
(8mm)
f4.72"
0.31"
Base unit
Model No. FS-3500E (W) FS-3500E (B) (f120mm)
(45mm)
1.77"
Detection distance 10m (7cm flame)
(10.5mm)
°
Power consumption Stand-by : 40mA or less
35
35
°
0.41"
(DC Power) Alarm : 300mA or less
0. .2mm
Indication : RED
17 )
(4
"
LED Alarm : Flash during message output
(34mm)
Low battery : Flash 0.1 sec every 5 sec
1.34"
• 5 language message 5-f0.17"
Non-smoking (5-f4.2mm)
(1) JAP. [ここは禁煙です。お煙草はご遠慮ください。] Wiring hole f0.35"
(2) ENG. [This is a non-smoking area. Please refrain from smoking in this area.] LED Detection window 2.63" (f9mm)
(3) CHI. [ ] (Red) (66.7mm)
R0.59"
(4) KOR. [ ] (R15mm) f3.29"
(5) SPA. [Prohibido fumar. Absténgase de fumar en el servicio.] (f83.5mm)
Fire prohibition
(1) JAP. [ここは火気厳禁です。火気の使用はお断りいたします。] MOUNT&WIRING HOLE
Message (2) ENG. [Open flame is prohibited. Please refrain from using open flame in this area.]
(3) CHI. [ ]
(4) KOR. [ ]
(5) SPA. [Prohibido encender fuego. No se permite el uso de
productos inflamables en el servicio.]
Buzzer sound
(1) [PiPiPiPi...]
• Long/Short message selectable
nOPTIONALS
• Message repeat : Once/twice selectable Ceiling/wall mount attachment (BCW-401)
• Volume : Mute - Max.80dB (1m from the sensor) The recorded message can be changed to custom order.
Relay contact output N.O./N.C. selectable
Output Detection time plus 2 sec.
Output DC30V, 0.1A ,IMITED 7ARRANTY
TAKEX products are warranted to be free from defects in material and
Relay contact output N.C. is issued when workmanship for 12 months from original date of shipment. Our warranty
Tamper the sensor unit is detached from the base unit does not cover damage or failure caused by Acts of God (including
AC/DC30V, 0.1A inductive surge by lightning), abuse, misuse, abnormal usage, faulty
Wiring By terminals installation, improper maintenance or any repairs other than those
provided by TAKEX. All implied warranties with respect to TAKEX,
-10°C to +60°C without condensation including implied warranties for merchantability and implied warranties
Ambient temperature (Battery performance may decrease under 0°C or beyond 40°C) for fitness, are limited in duration to 12 months from original date of
Istallation Indoor shipment. During the Warranty Period, TAKEX will repair or replace, at
its sole option, free of charge, any defective parts returned prepaid. Please
Weight 230g (Including 50g battery) provide the model number of the products, original date of shipment and
nature of difficulty being experienced. There will be charges rendered for
Appearance ABS resin (white) ABS resin (brown) product repairs made after our Warranty period has expired.