Design Criteria
Design Criteria
Design Criteria
FOR
60MX16M HANGAR GATE
&SIDE COLUMN
DOCUMENT NO. HC-1814-01-R6
DEC, 2018
CLIENT:-
CPWD, NEW DLEHI
CONTRACTOR:
TEMPCON ENGINEERS
4, CENTRAL LANE BENGALI MARKET
NEW DELHI 110001
STRUCTURAL CONSULTANT:
The structural design will basically conform to the latest revision of codes
and recommendation of INDIAN STANDARDS specifications.
The following are the various Design Codes that shall be followed for the
structural design of the various components of structure. These shall be
supplemented, wherever required, by guidelines from various international
1.1
codes and literature issued by different Government of India Undertakings.
IS: 875-1987 Code of practice for Structural safety of building and loading
IS: 875(3)-2015 Code of practice for Design Loads for buildings and structures
The following are the various Design Codes that shall be followed for
1.2 the material specification.
IS: 2062-2006 Hot rolled Low, Medium & High tenile Structural Steel
IS: 1148-(Latest) Hot rolled steel river bar (upto 40mm dia.) for structural purpose
+A76
IS :816 Code of Practice for use of Metal Arc Welding for General Construction in
Mild Steel
IS:2502-1963 Code of practice for bending and fixing of bars for concrete reinforcement
IS: 9595 - 1980 Indian Standard Recommendations for Metal Arc Welding of Carbon
Manganese Steels
IS:4091-1979 Code of practice for design and construction of foundations for transmission
line towers and poles.
Wind Loads. Wind pressure effect on the structure as per clause wind pressure as per IS-
875-1987.
Load Considered :-
Following loads have been considered while designing the structural
drawing for the Hangar Door
1. Hangar Door Weight
2. Self contained weight (weight of steel structure)
3. Wind Load
4. Temperature Rise & Fall
Material Specification:
Steel:
Structural Steel As per IS: 2062 Quality 'B' Grade designation E250 (Fe 410 W) fully
killed & normalised/ controlled cooled.