PENETRANT LIQUID CONTROL

TEST REPORT DE
CALIDAD
REPORTE : PT-001
PER VlGENCIA :2019
CUSTOMER ~ Tt;RMOFUSION PERU SAC
I PROJECT ; BRIDA DEACOPl..E PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
: BRIDA DIAMETER: 4" DATE DE INSPECTION: 26/1212019
: 112" PROCESS: SMAW REPORT N° : 001
MATERIAL : ASTM A· Gr B INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME 831.3

Aa : porosity
Bc: Aislated slag inclusion fa : Longitudinal Crack F : Undercut
Sa : Orientation instructions and varied fonn C: Lack of fusion Eb : Transversal Crack

Juntas : 01 Manufacturer or Contractor: I

Inspector : DAVID CHIRA Authorized by: TERMO FUSION SAC


Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALIDAD
REPORTE : PT -001
PERU VlGENCIA :2019
CUSTOMER : TERMOFUSION PERU SAC
PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
CODE : BRlDA DIAMETER: 6" DATE DE INSPECTION: 21/12/2019
THICKNESS : 1. 114" PROCESS: SMAW REPORT N° : 001
MATERIAL : ASTM A· Gr B INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINAnON
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE I
POST EXAMINATION
Cleaning (If Required): N I A
I
CODE OF PROCEDURE:
CODE OF INSPECTION: ASME 831.3

IDENTlFI~TlQN T e ~d location Qf dls~n!L;nu


;.;,;;;;;lti;.,e~
; ; s ~(~;;.;;
m~_4====l~===_='__=_=_=_"'=
__l==~~~
Re;;,;,m;;;;a;;.;:rk.;.;;;s=~="~11
II J·1 Sin Discontinuldades Refevantes. SI ACEPTADO
--~-----~-----------.~----------~-----~

Aa; porosity Bb: Alineated slag inclusions D : Indadecuate Penetration


Be: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
8a : Orientation instructions and varied form C: Lack of fusion Eb : Transversal Crack

Total Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA 5.... ... .. •• D~ __ • • Authorized by: TERMO FUSION SAC
DAVIIJ H SUAREZ
Level : NIVEL II NIVElU TTClART-l'f4T.lfl
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALIDAD
REPORTE : PT-001
PERU VJGENCIA :2019
CUSTOMER : TERMOFUSION PERU SAC
PROJECT ; BRlDA OEACOPLE PARA PRUE6A HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
: BRIDA DIAMETER: 4" DATE DE INSPECTION: 26/12/2019
ESS : 1/2" PROCESS: SMAW REPORT N° : 001
MATERIAL : ASTMA· GrB INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINAnON
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DfVELOPER.4

Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE


POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECnON: ASME 831.3

ACEPTAOO

Aa : porosity Bb: Alineated slag inclusions D : Indadecuate


Be: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Sa : Orientation instructions and varied fonn C: Lack of fusion Eb : Transversal Crack

Juntas ; 01 Manufacturer or Contractor: I

Inspector : DAVID CHIRA S-.n.iiii;;;~::-:.·~----. Authorized by: TERMO FUSION SAC


Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALIDAD
REPORTE : PT-001
PERU VlGENCIA :2019

CUSTOMER : TERMOFUSION PERU SAC


PROJECT : BruDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
CODE : BRiDA DIAMETER: 6" DATE DE INSPECTION: 21/1212019
THICKNESS : 1.1/4" PROCESS: SMAW REPORT N° : 001
MATERIAL : ASTM A· Gr B INSPECTION : 100% PAGE: :01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE-CHECK- REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODe OF INSPECTION: ASME 831.3

IDENTIFICATlQt:L T e and location ~f dlscon~nultles cm Remarks


J1a Sin Discontinuidades Relevantes. 51 ACEPTADO

Aa : po ..osity Bb: Alineated slag inclusions o : Indadecuate Penetration


Be: AisJated slag inclusion Ea : Longitudinal Crack F : Undercut
Sa : Orientation instructions and varied form C; Lack of fusion Eb : Transversal Crack

Total Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA S.~~--- ~M~ ______ Authorized by: TERMO FUSION SAC
DAVIIJ H SUAREZ
Level : NIVEL " N'V~LU TCIAIU-<'HIf4ff
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALI DAD
REPORTE : PT-001
PERU VIGENCIA :2019

CUSTOMER : TERMOFUSION PERU SAC


PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
: BRIDA DIAMETER: 4" DATE DE INSPECTION: 26/12/2019
ESS : 1.1/4" PROCESS: SMAW REPORT N° : 004
RIAL : ASTM A· Gr B INSPECTION : 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT OYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE 1REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME B31.3

J-1 Sin Discontinuidades Relevantes. SI ACEPTADO

Aa : porosity Bb: Alineated slag inclusions o : Indadecuate Penetration


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Ba : Orientation instructions and varied form c: Lack of fusion Eb : Transversal Crack

otal Juntas : 01 1rY-- - Manufacturer or Contractor:


Inspector : DAVID CHIRA S. ""'VC'M"'"
"' · ~·"'>"' lf[ G IART,~ <
Authorized by: TERMO FUSION SAC
Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALI DAD
REPORTE : PT-001
PERU VIGENCIA :2019
CUSTOMER : TERMOFUSION PERU SAC
PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
BRIDA DIAMETER: 8" DATE DE INSPECTION: 26/12/2019
1.114" PROCESS:SMAW REPORT N° : 006
: ASTM A- Gr B INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE-CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): NI A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME B31 .3

J-1 Sin Discontinuidades Relevantes. 51 ACEPTADO

Aa : porosity Bb: Alineated slag inclusions o : Indadecuate Penetration


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Ba : Orientation instructions and varied form , C: Lack of fusion Eb : Transversal Crack

Juntas : 01 Manufacturer or Contractor:


Inspector j - r.~~~:Z' Authorized by: TERMO FUSION SAC
: DAVID CHIRA S. -ri-;-i,-lri
'. l ~

Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALI DAD
REPORTE : PT-001
PERU VIGENCIA :2019

CUSTOMER : TERMOFUSION PERU SAC


PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROST ATlCA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
CODE : BRIDA DIAMETER: 10" DATE DE INSPECTION: 26/12/2019
THICKNESS : 1.1/4" PROCESS: SMAW REPORT N° : 002
TERIAL : ASTM A· Gr B INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE 1REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME 831.3

J-1 Sin Discontinuidades Relevantes. ACEPTADO

Aa: porosity Bb: Alineated slag inclusions o : Indadecuate


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Ba : Orientation instructions and varied form C: Lack of fusion Eb : Transversal Crack

Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA S. -6AViDUfiR~5LiAREi Authorized by: TERMO FUSION SAC
Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALIDAD
REPORTE : PT-001
PERU VIGENCIA :2019

CUSTOMER : TERMOFU~ONPERUSAC
PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
: BRIDA DIAMETER: 8" DATE DE INSPECTION: 26/1212019
: 1.114" PROCESS: SMAW REPORT N° : 007
MATERIAL : ASTM A· Gr 8 INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): NI A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME 831.3

Aa : porosity Bb: Alineated slag inclusions o : Indadecuate Penetration


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Ba : Orientation instructions and varied form C: Lack of fusion Eb : Transversal Crack

Total Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA S. nA\il·n:-~M.;i!.~Rl~ Authorized by: TERMO FUSION SAC
Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CAUDAD
REPORTE : PT-001
PERU VIGENCIA :2019

CUSTOMER : TERMOFUSION PERU SAC


PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
BRIDA DIAMETER: 10" DATE DE INSPECTION: 26/12/2019
ESS 1.1/4" PROCESS: SMAW REPORT N° : 003
RIAL : ASTM A· Gr B INSPECTION : 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE I REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME B31.3

J-2 Sin Discontinuidades Relevantes. 51 ACEPTADO

Aa : porosity Alineated slag inclusions o : Indadecuate Penetration


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Sa : Orientation instructions and varied form c: Lack of fusion Eb : Transversal Crack

otal Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA S. -".;-.:~.1'.~.'.---'-- Authorized by: TERMO FUSION SAC
Level : NIVEL II
PENETRANT LIQUID CONTROL
TEST REPORT DE
CALI DAD
REPORTE : PT-001
PERU VIGENCIA :2019

CUSTOMER : TERMOFUSION PERU SAC


PROJECT : BRIDA DE ACOPLE PARA PRUEBA HIDROSTATICA
DATA OF THE EQUIPMENT OR INSPECTED COMPONENT
CODE BRIDA DIAMETER: 6" DATE DE INSPECTION: 26/12/2019
THICKNESS 1.1/4" PROCESS: SMAW REPORT N° : 005
MATERIAL : ASTM A· Gr B INSPECTION: 100% PAGE: : 01
DATA OF THE TEST
PRE EXAMINATION
Surface Preparation:
EQUIPMENT DYE·CHECK· REMOVER: 1·3
Instrument Make: PENETRANT.2 DEVELOPER.4
METHOD OF INSPECTION
Dry: AGENTE VISIBLE 1REMOSION POR SOLVENTE
POST EXAMINATION
Cleaning (If Required): N I A

CODE OF PROCEDURE:
CODE OF INSPECTION: ASME 831.3

Aa : porosity Bb: Alineated slag inclusions D : Indadecuate Penetration


Bc: Aislated slag inclusion Ea : Longitudinal Crack F : Undercut
Ba : Orientation instructions and varied form C: Lack of fusion Eb : Transversal Crack

Total Juntas : 01 Manufacturer or Contractor:


Inspector : DAVID CHIRA S. Authorized by: TERMO FUSION SAC
Level : NIVEL "