3.1 Load Computation Usd
3.1 Load Computation Usd
Ceiling
Suspended metal lath and gypsum plaster 0.48 KPa
Acoustical fiber board 0.05 KPa
Electrical, Mechanical, Sanitary allowance 0.10 KPa
LC1: U = 1.4D
LC2: U= 1.2D + 1.6L + 0.5Lr
LC3: U = 1.2D + 1.6Lr + 0.5L
LC4: U = 0.9D + 1.0Ex
LC5: U = 0.9D + 1.0Ez
LC6: U= 1.2D + 1.0Ex + 0.5Lr
LC7: U= 1.2D + 1.0Ez + 0.5Lr
LC8: U = 1.2D + 1.0Wx + 0.5L + 0.5Lr
LC9: U = 1.2D + 1.0Wz + 0.5L + 0.5Lr
3.2 LOAD COMPUTATION (WSD)
Ceiling
Suspended metal lath and gypsum plaster 0.48 KPa
Acoustical fiber board 0.05 KPa
Electrical, Mechanical, Sanitary allowance 0.10 KPa
LIVE LOAD
Basic floor area 1.90 KPa
Exit facilities 4.80 KPa
Structural Period, T
T =C t (h n)3 /4
Total Weight, WT
TOTAL WEIGHT
W1 4709.117 kN
W2 4310.03 kN
W3 4310.03 kN
W4 4310.03 kN
W5 3135.31 kN
TOTAL 20774.517 kN
Structural Period, T
T =C t (h n)3 /4
3
4
T =0.0731 ( 16.3 )
T =0.5930
The total design base shear need not exceed the following
2.5 C a I
V= W
R
2.5 ( 0.44 )( 1.2 ) ( 1.0 )
V= ( 20774.517 )
8.5
V =3226.16 kN
The total design base shear shall not be less than the following
V =0.11 Ca IW
V =0.11 ( 0.44 ) ( 1.2 )( 1.0 )( 20774.517 )
V =1206.58 kN
In addition, for Seismic Zone 4, the total base shear shall also not be less than the following
0.8 ZN v I
V= W
R
0.8 ( 0.4 )( 1.2 ) ( 1.0 )
V= ( 20774.517 )
8.5
V =938.52 kN
Table 207B.2-1
Steps to Determine MWFRS Wind Loads for Enclosed, Partially Enclosed and Open Buildings of
All Heights
Step 1: Determine risk category of building or other structure, see Table 103-1
Step 2: Determine the basic wind speed, V, for the applicable risk category, see Figure 207A.55-
1A ,B or C
Step 3: Determine wind load parameters
Wind directionality factor, Kd , see Section 207A.6 and Table 207A.6-1
Exposure category B, C or D, see Section 207A.7
Topographic factor, Kzt , see Section 207A.8 and Table 207A.8-1
Gust Effect Factor, G, see Section 207A.9
Enclosure classification, see Section 207A.10
Internal pressure coefficient, (GCpi), see Section 207A.11 and Table 207A.11-1
Step 4: Determine velocity pressure exposure coefficient, Kz or Kh , see Table 207B.3-1
Step 5: Determine the velocity pressure qz or qh Equation 207B.3-1
Step 6: Determine external pressure coefficient, Cp, or CN
Figure 207B.4-1 for walls and flat, gable, hip, monoslope or mansard roofs
Figure 207B.4-2 for domed roofs
Figure 207B.4-3 for arched roofs
Figure 207B.4-4 for monoslope roof, open building
Figure 207B.4-5 for pitched roof, open building
Figure 207B.4-6 for troughed roof, open building
Figure 207B.4-7 for along-ridge/valley wind load case for monoslope, pitched or troughed
roof, open building
Step 7: Calculate wind pressure, p, on each building surface
Equation 207B.4-1 for rigid buildings
Equation 207B.4-2 for flexible buildings
Equation 207B.4-3 for open buildings
Section 207B.4.1 Enclosed and Partially Enclosed Rigid Buildings
Design wind pressures for the MWFRS of buildings of all heights shall be determined by the
following equation:
p=2.26(0.85)(−0.47)−2.26 (−0.18)
p=−0.50 kPa(Leeward Wall)
3.4 Frame Analysis Flowchart
Start
Perform analysis
End
Start
Given: Axial Load,Pu &
Design Moment, Mu
Combined Footing
Isolated Footing
Solve for
reinforcement,
dowels and
development length
End
3.6 Frame Analysis (SMRF)
FIG. 3.6.1. Geometric Model of Frame
FIG. 3.6.2. Load Combination 1 FIG. 3.6.5. Load Combination 4
LOAD DATA
COLUMN 1 COLUMN 2
Primary Load (KN) Axial (Fy) Primary Load (KN) Axial (Fy)
Dead Load 77.94 Dead Load 62.87
Live Load 233.81 Live Load 188.6
Wind Load (Wx) 0 Wind Load (Wx) 0
Wind Load (Wz) 0 Wind Load (Wz) 0
Earthquake Load (Ex) 0 Earthquake Load (Ex) 0
Earthquake Load (Ez) 0 Earthquake Load (Ez) 0