Professional Documents
Culture Documents
Pel TP 00 Ins DS 011
Pel TP 00 Ins DS 011
00+000p
PEL-TP-00-INS-DS-011 DATASHEET FOR TEMPERATURE GAUGE Page 3 of 5
CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA
TABLE OF CONTENT
00+000 p
PEL-TP-00-INS-DS-011 DATASHEET FOR TEMPERATURE GAUGE Page 4 of 5
CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA
2 Service
3 Line Number / Equipment Number See List
4 Location / P&ID Number See List
5 Line Size Line Schedule See List TBA
6 Area Classification Not Classified
7 Fluid State Liquid
8 Operating Temperature 60 deg C
PROCESS DATA
Tapered
44 Construction Type
(Note 2)
45 Internal Connection 1/2" NPT (F) (*)
46 Lagging Extension (*)
47 Length "U" Bore diameter (*) (*)
48 Treatment Tip diameter Mf'r Std. (*)
49 Stamping Yes
50 Overall length (*)
51 Manufacture (Note 4)
PURCHASE
52 Model No (*)
53 PO Number (*)
54
55
Note :
* Vendor to advise.
1 Temperature Gauge and Well requirements and specifications shall be comply to General Specification for Instrument
2 NDT shall be performed on thermowell, include dye penetration test on all welds and hydrotest as per ANSI B16.5.
3 Vendor shall provide thermowell calculation as per ASME PTC 19.3.
4 Refer to Approved Manufacturer List.
5 Vendor shall be responsible for correct model selection.
6 Thermowell shall be installed in pipe size 4" and larger, whichever pipe size is smaller than 4", than pipe
enlargement is required
JASA KONSULTASI PERENCANAAN PEKERJAAN INSTRUMENTASI TANKI STORAGE
CPO DI PERAK
00+000 p
PEL-TP-00-INS-DS-011 DATASHEET FOR TEMPERATURE GAUGE Page 5 of 5
CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA