JASA KONSULTASI PERENCANAAN PEKERJAAN

INSTRUMENTASI TANKI STORAGE CPO DI PERAK

00+000p
PEL-TP-00-INS-DS-012 DATASHEET FOR CONTROL VALVE Page 3 of 5
CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA

TABLE OF CONTENT

No. Document No. Page Tittle Remarks


1 PEL-TP-00-INS-DS-012 1 COVER
2 PEL-TP-00-INS-DS-012 2 REVISION HISTORICAL SHEET
3 PEL-TP-00-INS-DS-012 3 TABLE OF CONTENT
4 PEL-TP-00-INS-DS-012 4 GENERAL NOTE
5 PEL-TP-00-INS-DS-012 5 DATASHEET TCV-001 TO TCV-006
JASA KONSULTASI PERENCANAAN PEKERJAAN
INSTRUMENTASI TANKI STORAGE CPO DI PERAK

00+000p
PEL-TP-00-INS-DS-012 DATASHEET FOR CONTROL VALVE Page 4 of 5
CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA

GENERAL NOTE

1. Each individual instrumentation that include at control valve package, e.g. valve body, trim, actuator, regulator, positioner, etc.
Shall have a 316 SS label with information about P.O, S/N, material, manufacture, model and, size as minimum,
engraved in 1/4" minimum high lettering.
2. The label shall be permanently attached to each instrumentation using 316 SS screws or rivets.
3. Each Instrument shall supplied with SS identification tags.
4. Vendor shall furnish sizing calc. shall be as per ISA S75.01, indicating Rated CV, % travel, noise, trim size, body size,
valve type and valve characteristic, shall be provided for purchaser's review and approval.
5. The air filter regulator shall be suitable to handle 130% of maximum instrument air supply pressure.
6. All Control valves noise shall not exceed 85 dB (A) at points 3 feet away from the valve and 3 feet downstream.
7. Vendor is required to submit noise calculation and select anti noise trim to comply maximum noise 85 dBA.
If noise exceed
Vendor 85 dBA
shall provide and Choke/Cavitation/Flashing,
detail Vendor
data sheet of control valve and shall provide(actuator,
it's accessories special trim.
Regulator, Filter, etc),
8.
include catalogue and instruction manual.
9. Vendor shall provide calibration certificate and certificate of origin.
10. Vendor shall be responsible for the correct sizing and the model selection of control valve and pressure regulator valve.
JASA KONSULTASI PERENCANAAN PEKERJAAN INSTRUMENTASI TANKI STORAGE
CPO DI PERAK

00+000 p
PEL-TP-00-INS-DS-012 DATASHEET FOR CONTROL VALVE Page 5 of 5

CLIENT APPROVAL
REV DATE DESCRITION PREPRARED CHECKED APPROVED
BY DATE
0 8-Aug-16 IFB YF DW BA
1 6-Feb-17 IFB ND DW BA

1 Tag Number TCV-001 / 002 / 003 / 004 / 005 / 006


2 Quantity 6 ea
GENERAL

3 Location Tank Area


4 P&ID No. PEL-TL-00-PRO-DWG-001
5 Service Steam line on Tank
6 Line No. Inlet Tank T-001 / 002 / 003 / 004 / 005 / 006
7
8 Fluid : Steam Process
9 Units Maximum Normal Minimum
10 Flow Rate m3/hr 3.08 2.8 1.68
11 Inlet Pressure Barg 2 2 2
12 Pressure Drop Bar VTA VTA VTA
13 Inlet Temperature deg C 100 100 100
SERVICE CONDITIONS

14 Specific Gravity 1.118 1.118 1.118


15 Specific Heat Ratio Cp/Cv 1 1 1
16 Mol Weight 18 18 18
17 Viscosity cP 0.8 0.8 0.8
18 Gas Compressibility 0.00072 0.00072 0.00072
19 Vapour Pressure Barg 0.06 0.06 0.06
20 Cricital Pressure / Temperature Barg deg C 221.2 374.1 221.2 374.1 221.2 374.1
21 Design Pressure / Temperature Barg deg C 10 180 10 180 10 180
22 Required Cv Gen. Note 10 (*) Gen. Note 10 (*) Gen. Note 10 (*)
23 Travel % Open Gen. Note 10 (*) Gen. Note 10 (*) Gen. Note 10 (*)
24 Allowable / Predicted SPL dBA Gen. Note 7 (*) Gen. Note 7 (*) Gen. Note 7 (*)
25
26 Pipe Line Size In : 1" Sch TBA 66 Stroking : (*)
LINE

27 and Schedule Out : 1" Sch TBA 67 Handwheel : N/A


ACTUATOR

28 Pipe Line Insulation N/A 68 Actuator orientation : Vertical


29 Type : Globe, General Note 10 (*) 69 Supply Type : Instrument air
30 Size : 1 inch (*) ANSI Class : 150# 70 Return Connection : 1/4" NPT (*)
Mfr. & model
31 Working Press/Temp : (*) 71 : As per Vendor List & (*)
32 Mfr & Model : As per Vendor List & (*) 72
VALVE BODY / BONNET

33 Body / Bonnet Matl : (*) 73 Tag No. : TY-001 / 002 / 003 / 004 / 005 / 006
34 Liner Material / ID : N/A 74 Type : Electric to Pneumatic
35 End Connection In : ANSI 150#RF(*) 75 On incr. Signal output : Increased (*)
36 Out : ANSI 150#RF(*) 76 Gauge: Yes By-pass : N/A
POSITIONER

37 Flg Face Finish : (*) 77 Cam characteristic : Linier (*)


38 Flow direction : Flow to Open (*) 78 Signal input / Output : 4 - 20 mA (*)
39 Type of bonnet : Bolted 79 Electrical connection : 1/2" NPT (*)
40 Lub. & Iso. Valve : N/A 80 Area classification : (*)
41 Packing Material : PTFE (*) 81 Enclosure class : IP 65, Weather to corrosion proof
42 Packing Type : (*) 82 Lightning / Surge Protection : Yes
43 MFR and Model No. : As per Vendor List & (*) 83 Mfr. & model : As per Vendor List & (*)
44 84
45 Type : MFR Std 85 Set Pressure : 30 psig (*)
46 Port Size : (*) Rated Travel :(*) 86 Filter / Gauge : Yes, Required
AIR SET

47 Characteristic : Equal % (*) 87 Material : 316 SS


48 Balanced / Unbalanc : Balanced (*) 88 Tubing Conn./ Gauge Con: Yes, Required, 1/4" NPT
49 Rated Cv : (*) Fd : (*) XT: (*) 89 Mfr & Model : As per Vendor List & (*)
50 Plug Material : 316 SS 90
TRIM

51 Plug Form : MFR Std. 91 Hydro pressure : Yes, ANSI/ISA-75.19.01-2007


TEST

52 Guide Type : Cage - Guided(*) 92 Leakage test : Yes, ANSI/FCI/70.2


53 Guide Material : (*) 93 Function test : Yes, Required
54 Stem/shaft material : 316 SS 94
55 Seat Material : 316 SS
56 ANSI / FCI Leakage Class/ Thight Shutoff : Class V (*)
57
58 Type : Spring - Diaphragm (*)
59 Size : (*) EFF. Area : (*)
ACTUATOR

60 ON / OFF : Yes (*) Throttling : Yes (*)


61 Fail Positio : Close
62 Maximum allowable pressure : (*)
63 Available gas supply pressure : 80 - 110 Psig
64 Bench Range : (*)
65

Note :
* VTA = Vendor to Advice ( Control Valvea are appplicted at Steam Process)
1 Vendor shall be responsible for calculate Required CV, Travel and Allowable / Predicted SPL.
2 TBA = To be Advice