AIR COOLED HEAT EXCHANGERS

INTRODUCTION
Water shortage and increasing costs, together with more recent concerns
about water pollution and cooling tower plumes, have greatly reduced
industry's use of water cooled heat exchangers. Consequently, when further
heat integration within the plant is not possible, it is now usual to reject heat
directly to the atmosphere, and a large proportion of the process cooling in
refineries and chemical plants takes place in Air Cooled Heat
Exchangers (ACHEs).
There is also increasing use of Air Cooled Condensers for power stations. The
basic principles are the same but these are specialized items and are
normally configured as an A-frame or "roof type". These condensers may be
very large—the condensers for a 4000 MW power station in South Africa have
over 2300 tube bundles, 288 fans each 9.1 m in diameter and a total plot
area 500 m × 70 m.
ACHEs for process plants are normally just called Aircoolers, but should not
be confused with devices for cooling air (best described as Air Chillers).
The design of an ACHE is more complex than for a Shell and Tube Heat
Exchanger, as there are many more components and variables.

CONSTRUCTION
The principle component of an ACHE is the tube bundle, of which there may
be many, normally comprising finned tubes terminating in header boxes. The
fins are most commonly spirally wound aluminum strips 12.7 × 10 −3 m or
15.9 × 10−3 m high and with 275 to 433 fins/m. There are two main types of
wound fin which are usually known as L-fin and G-fin. There are several
variations of the former type—single, overlapped, and knurled, but all suffer a
high contact resistance, which increases with temperature due to differential
expansion between the fin and the core tube. Embedded fins (G-fins) are
wound into a groove in the core tube which is then peened back providing a
mechanical bond. This gives better heat transfer but requires a thicker core
tube. Integral fins extruded from an aluminum sheath are often used for
more severe environments, and instead of embedded fins with expensive
core tubes. When an exceptionally long life is required in aggressive
environments galvanized steel fins can be the best choice, and these
frequently use elliptical tubes, which also have improved airflow
characteristics. Core tubes may be carbon steel, stainless steel or various
alloys and are usually of 25.4 × 10 −3 m outside diameter. For low pressure or
highly viscous applications the tubes can be up to 50.8 × 10 −3 m diameter.
Tube lengths vary to suit the installation, which will often be over a piperack,
but generally do not exceed 15 m. (See also Extended Surfaces Heat
Transfer).
Unlike most other pressure vessels an ACHE header box is normally
rectangular in cross-section, and the most widely used type has threaded
plugs opposite each tube for access. Various coverplate types may be used
for low pressures, and for high pressures (up to 500 bar) manifold headers
made from thick walled pipe or forged billets are needed. When there could
be a large temperature drop across a multipass tube bundle, split headers
may be necessary to accommodate differential expansion between passes.
The air is moved over the tubes in a single crossflow pass by axial flow fans,
which may be arranged for forced or induced draught. Forced draught is
suitable for most applications, has easier maintenance and is by far the more
common. Induced draught gives a more even air distribution across the
tubes, but requires more power as the fans are in the hot air stream. This
latter point also means that induced draught is not suitable for high process
temperatures, but is advisable for a close temperature approach as exit
velocities are higher and hot air recirculation less likely. For induced draught
installations with fan diameters greater than 2.4 m the motor and speed
reducer will normally be mounted below the tube bundles, with an extended
drive shaft, as shown in Figure 2 There are normally at least two fans in
each exchanger bay so that significant cooling is maintained in the event of a
partial failure, and it is preferable for fans to cover at least 40% of the total
bundle face area.

Figure 1. Typical forced draught air cooled heat exchanger.

Figure 2. Typical induced draught air cooled heat exchanger.

Installation
An ACHE is a large piece of equipment compared to other types of heat
exchangers, and requires free space around it for the cooling air flow. In
refineries and chemical plants ACHEs are usually mounted over a piperack,
saving plot space at grade and ensuring free airflow. A further advantage of
this elevated mounting is shorter pipe runs for column overheads, saving
both cost and pressure drop. In some cases an ACHE may be mounted on top
of a column to keep pressure loss to an absolute minimum, but this can make
maintenance more difficult. Rooftop mounting is sometimes used, particularly
for turbine steam condensers. When no suitable supporting structure is
available, or where there is ample space available, the cooler may of course
be ground mounted.

Design features
A typical face velocity for the air flowing across the tube bundle is 3 m/s.
Higher air flows increase both the heat transfer coefficient and the mean
temperature difference, thereby reducing the surface area required, but at a
higher power consumption. Increased airflow and power also mean greater
fan noise, which is an increasingly important factor.
The choice of design ambient temperature is the most critical factor affecting
the size of an ACHE. A dry bulb temperature that is not exceeded for 95% of
the year is the usual choice, accepting that there may be a cooling shortfall
on the hottest days. In some cases the plant loading may be reduced in the
summer, so that a lower design air temperature is appropriate. The majority
of ACHE designs have between 4 and 6 rows of tubes (in the airflow
direction). This may rise to 8 rows or more if there are plot restrictions, but
successive rows become less and less effective for heat transfer and costs
increase. If the core tubes are of high value material, fewer rows and
increased plot area will certainly be cheaper.
Small independent ACHEs can be quite expensive, and it is therefore normal
practice to install two or more small units in a shared fan bay. This is
particularly useful when several exchangers are to be mounted in a bank with
a common tubelength.

Noise
Sound pressure level limits in work areas within a plant are usually about 85
dB(A), but community noise levels need to be much lower and frequently
necessitate an analysis of overall sound power levels. In Europe the sound
power limits now tend to be more severe than the local sound pressure limits,
and in some cases control the ACHE design.
The principal source of noise in ACHEs is the fans. Moderate reductions in
noise levels can be achieved by reducing the fan speed and using more
blades or wider chord blades. Very low noise designs necessitate low face
velocities, with a consequent increase in surface area, so that the fans can
run very slowly and still generate sufficient pressure.
The extremely low noise restrictions now being applied on some sites has led
to the development of special fan designs, which are much quieter than
conventional fans while maintaining a reasonable airflow.
Thermal design
The tubeside heat transfer and pressure drop are calculated in the same way
as for Shell & Tube Heat Exchangers. For the airside heat transfer rate a
number of calculation methods are available, including correlations by Briggs
and Young (1963), PFR (1976) and ESDU (1986). As there is a temperature
gradient along the fin the calculated heat transfer is adjusted using the
concept of fin efficiency, which is the ratio of the actual heat transfer from a
given surface, to the heat which would be transferred from the same surface
at a uniform temperature equal to the fin root temperature—for details
see Extended Surfaces Heat Transfer. The fin efficiency is in the range
0.8 to 0.9 for fin types and dimensions generally used in ACHEs.
Several correlations exist for predicting the airside pressure loss across the
finned tube bank—those most commonly used are by Robinson and Briggs
(1966), PFR (1976), and ESDU (1986).
Typical values of overall heat transfer coefficient for various fluids are given
in ESDU (1993) and these may be used to obtain approximate sizes. This
item also describes the C-value method of comparing costs for various heat
exchanger types.
Control
Several options are available for controlling ACHEs. Simply switching fans on
and off is adequate in many cases, and can give quite close control if the
item has a large number of fans. The addition of louvre shutters, which can
be manually or pneumatically operated, will provide further improvement,
and two-speed motors are sometimes used.
The best control is obtained by the use of auto-variable pitch fans or variable
speed motors, both of which provide gradual airflow adjustment. Improved
electronics have made variable speed much more popular in recent years,
with the additional benefits of power consumption and noise always being
minimized.
The method of flooding condensers as frequently employed in shell and tube
heat exchangers is not practical for ACHEs, and reductions in the effective
surface area can only be achieved by valving off bundles.
Large variations in ambient temperature throughout the year will have a
considerable effect on the available range of control, especially if there is a
close approach at the design condition. Process engineers should be aware of
this and avoid building in large design margins when a high degree of
turndown is required, since for most of the year the ACHE will be massively
oversurfaced and a control problem created.
Controlled recirculation
If there is a possibility of freezing, waxing or hydrate formation, it will be
necessary to maintain a sufficiently high tube wall temperature to avoid this
under all conditions. In many cases this will not be a problem, or may be
easily solved by using reduced finning and/or cocurrent flow. However, in
extreme cases hot air recirculation will be required. This is achieved by
enclosing the ACHE in a cabin with inlet and outlet louvres, and a duct to
redirect some of the exhaust air to mix with the cold inlet air. The normal
arrangement is shown in Figure 3, although the recirculation duct may
occasionally be at a header end (external over end).

Process side enhancement


In the majority of ACHE designs the airside heat transfer coefficient is
controlling (i.e., much lower than the tubeside coefficient), and enhancement
of the inside coefficient would give very little overall improvement, such that
the additional cost of the enhancement device cannot be justified. However,
for viscous fluids where the flow in plain tubes would be laminar, wire wound
turbulator inserts are frequently used. The improved heat transfer coefficient
these inserts provide can also help to avoid pour point problems, since the
tube wall temperature will be closer to the bulk fluid temperature.
Figure 3. Hot air recirculation (external over side).

Fouling
Tubeside fouling factors normally follow shell and tube standard practice.
Airside fouling factors are sometimes specified but have little effect on the
already low airside heat transfer coefficient. The restriction to airflow of
fouling on the finned tubes is of greater significance, and occasional cleaning
is advisable to maintain cooling efficiency. In order to avoid fin damage,
particularly with wound aluminum fins, this cleaning should be carried out by
specialists.
Standards
The internationally accepted standard specification for refinery ACHEs is API
661. Many user companies now base their own specifications on this
standard, with their preferences given as amendments/supplements to the
API 661 clauses.