ATTACHMENT #1
1. PROJECT NAME :
2. CODE AND STANDARD :
3. CALCULATION METHOD : LUMEN METHOD
4. LOCATION :
5. CALCULATION TABLE
NO DESCRIPTION DEMENSION AREA REQ'D LAMP FIXTURE CAVITIES REF FACT CAVITY RATIOS EFF REF CU LLF REQ'D MIN'M CAL'D REMARK
W L H [M2] LUX TYPE NUM LUMEN TYPE MTG TYPE CAT NUM Hcc Hrc Hfc RC RW RF CCR RCR FCR ρcc ρfc [PU] [PU] No. No. LUX
101 HVAC Room 8.00 12.50 5.00 100.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 1.54 3.59 0.00 70 20 0.62 0.68 7.08 8 226
102 Cylinder Room 4.00 12.50 5.00 50.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 2.48 5.78 0.00 70 20 0.49 0.68 4.48 5 223
103 Computer Room 6.00 5.50 2.60 33.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 4.53 0.00 70 20 0.50 0.68 7.24 8 552
104 Female Locker Room 6.00 3.50 2.60 21.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.88 0.00 70 20 0.43 0.68 1.61 2 187
105 Male Locker Room 9.00 3.50 2.60 31.5 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.16 0.00 70 20 0.46 0.68 2.25 3 200
106 Battery Room 6.00 7.00 5.00 42.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 2.32 5.42 0.00 70 20 0.51 0.68 3.62 4 221
109 Pantry 9.00 6.50 2.60 58.5 200 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 3.44 0.00 70 20 0.56 0.68 4.59 5 218
110 Control Room 24.00 14.00 3.00 336.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 3.00 0.00 70 50 20 0.00 1.70 0.00 70 20 0.67 0.68 55.04 56 509
111 Supervisor Room 24.00 6.50 2.60 156.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 2.54 0.00 70 20 0.61 0.68 28.07 29 517
114 Corridor 2.50 18.00 2.60 45.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.92 0.00 70 20 0.43 0.68 3.45 4 174
115 Corridor 2.50 24.00 2.60 60.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.74 0.00 70 20 0.44 0.68 4.49 5 167
Page 1 of 5