JG Summit Naphtha Cracker Project

Doc. No. : JGSNCP-EL-CS-005 Rev. 0

ATTACHMENT #1

SUMMARY OF LIGHTING CALCULATION FOR INDOOR AREA


REQUIRED ILLUMINANCE AND CALCULATION ILLUMINATION TABLE

1. PROJECT NAME :
2. CODE AND STANDARD :
3. CALCULATION METHOD : LUMEN METHOD
4. LOCATION :
5. CALCULATION TABLE
NO DESCRIPTION DEMENSION AREA REQ'D LAMP FIXTURE CAVITIES REF FACT CAVITY RATIOS EFF REF CU LLF REQ'D MIN'M CAL'D REMARK
W L H [M2] LUX TYPE NUM LUMEN TYPE MTG TYPE CAT NUM Hcc Hrc Hfc RC RW RF CCR RCR FCR ρcc ρfc [PU] [PU] No. No. LUX
101 HVAC Room 8.00 12.50 5.00 100.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 1.54 3.59 0.00 70 20 0.62 0.68 7.08 8 226
102 Cylinder Room 4.00 12.50 5.00 50.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 2.48 5.78 0.00 70 20 0.49 0.68 4.48 5 223
103 Computer Room 6.00 5.50 2.60 33.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 4.53 0.00 70 20 0.50 0.68 7.24 8 552
104 Female Locker Room 6.00 3.50 2.60 21.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.88 0.00 70 20 0.43 0.68 1.61 2 187
105 Male Locker Room 9.00 3.50 2.60 31.5 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.16 0.00 70 20 0.46 0.68 2.25 3 200
106 Battery Room 6.00 7.00 5.00 42.0 200 FL36W 2 6700 BAY PENDANT NO 20 1.50 3.50 0.00 70 50 20 2.32 5.42 0.00 70 20 0.51 0.68 3.62 4 221
109 Pantry 9.00 6.50 2.60 58.5 200 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 3.44 0.00 70 20 0.56 0.68 4.59 5 218
110 Control Room 24.00 14.00 3.00 336.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 3.00 0.00 70 50 20 0.00 1.70 0.00 70 20 0.67 0.68 55.04 56 509
111 Supervisor Room 24.00 6.50 2.60 156.0 500 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 2.54 0.00 70 20 0.61 0.68 28.07 29 517
114 Corridor 2.50 18.00 2.60 45.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.92 0.00 70 20 0.43 0.68 3.45 4 174
115 Corridor 2.50 24.00 2.60 60.0 150 FL36W 2 6700 LOUVER CEILING NO 23 0.00 2.60 0.00 70 50 20 0.00 5.74 0.00 70 20 0.44 0.68 4.49 5 167

COEFFICIENT UTILIZATION (IES FIG 9-12)


NOTES: 70-50-20 50-30-20
1.0 FOR LAMP LUMEN, REFER TO CROUSE HINDS (FL 2x36W : 6700 lm, HPS 150W : 16000lm). RCR NO 20 NO 23 NO 16
2.0 FOR THE REFLECTANCE FACTOR, REFER TO SECTION 5.2. BAY LOUVER BAY
3.0 EFFECTIVE REFLECTANCE FACTOR IS REFER TO SECTION 5.2. 0 0.94 0.79 0.86
4.0 FOR COEFFICIENT OF UTILIZATION, REFER TO IES STANDARD DATA.(IES FIG 9-12). 1 0.84 0.72 0.78
5.0 FOR LIGHT LOSS FACTOR, SEE JGSNCP-EL-DB-003 2 0.74 0.65 0.70
6.0 RCR IS CALCULATED FOLLOWING FORMULA. RCR = 5 x HRC x (W + L) / (W x L) 3 0.66 0.58 0.62
7.0 REQ'D N IS CALCULATED USING THE FORMULA: REQ'D N = Illuminance x Area / Lumens per Luminaire x CU x LLF 4 0.60 0.53 0.56
8.0 REQUIRED LUX IS CALCULATED USING THE FORMULA: CAL'D LUX = Number of Luminaires x Lumen per Luminaire x CU x LLF / Area 5 0.53 0.47 0.50
6 0.48 0.43 0.44
7 0.43 0.39 0.39
8 0.39 0.35 0.34
9 0.35 0.32 0.30
10 0.32 0.29 0.27