HVDC Operation Formats
HVDC Operation Formats
HVDC Operation Formats
FOR
HVDC STATIONS
STANDARD OPERATION FORMAT
FOR
HVDC STATION
DOC: D-03-13-10-01-01
Revision Department Date Signature Signature
00 CC/OS 10.11.03 Sd/- Sd/-
01 CC/AM 04.03.20
J P Bhanja
DGM(AM)
20. HVDC/OP/16 Daily Log Sheet for Diesel All HVDC stations
Generator set
21. HVDC/OP/17 Disturbance and Outage report All HVDC stations To be updated in
SAP also.
FORMAT NO-HVDC/OP/01
DAILY LOG SHEET FOR A C BUSES, LINES AND FILTER BAYS (BACK TO BACK STATIONS)
Region: Date:
Station: Day:
1300
1500
2000
2300
In case readings are being recoded in SCADA, readings to be taken on hourly basis.
Soft copy/print out to be kept as record keeping. Shift engineer/JE/Technician must certify that all data have been recorded correctly.
FORMAT NO-HVDC/OP/02
DAILY LOG SHEET FOR CONVERTER BAYS
Region: Date:
Station: Day:
Time POLE/ BLOCK SIDE-1 DC Measurement POLE/ BLOCK SIDE-2 Station Control
in Station RPC mode and target SCADA
hours Power Mode MW MV kA Tap Control Voltage Current Power Control MW MVAR kA Tap Power Master
Flow J/S AR position Angle KA (MW) Angle position (MW) Station
Direc (KV) Side-1 Side-2 RPC System
(V/Q) (V/Q) status A/ B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
0600
0800
1300
1500
2000
2200
Region: Date:
Terminal Station: Day:
In case readings are being recoded in SCADA, readings to be taken on hourly basis.
Soft copy/print out to be kept as record keeping. Shift engineer/JE/Technician must certify that all data have been recorded correctly.
POWER GRID CORPORATION OF INDIA LTD.
FORMAT NO-HVDC/OP/04
Region: Date:
Station: Day:
0800
1300
1500
2000
2200
In case readings are being recoded in SCADA, readings to be taken on hourly basis.
Soft copy/print out to be kept as record keeping. Shift engineer/JE/Technician must certify that all data
have been recorded correctly.
FORMAT NO-HVDC/OP/05
OPERATION LOG BOOK (EVENT LOG BOOK)
Region : Date________________
Station : Day_________________
Shift : Morning/ Evening/ Night Shift Incharge:
Junior Engineer: Technician:
BIPOLE FIELD
Bipole Power MW
UAC AC Voltage kV
Frequency Hz
Bus/ Feeder Availability
Filters connected
Filter not available
RPC Status
RPC Voltage Ref./ Set point
Reactive Power exchange MVAR (Exp/ Imp)
Control Room temp. °C
Aux. Power Available / Not Available
POLE FIELD
Parameters Pole- I Pole- II
Pole Power (MW) MW MW
Control Mode Power/ Current Power/ Current
Mode of Control * Joint/Separate Joint/Separate
Current Return MR/GR MR/GR
Conv. Cont. Sys. (Active) A or B A or B
Stability Control On/Off On/Off
Reduced Voltage Operation
Aux. Power Source
Cooling Water Temp. °C °C
Valve Hall Temperature °C °C
Valve Hall Humidity % %
Valve Hall ventilation
Any abnormality/ outages
Reduced voltage operation, if any:
Important Events:
Time (Hrs) Details of event
(Signature) (Signature)
FORMAT NO-HVDC/OP/06
SHIFT OPERATION LOG BOOK (EVENT LOG BOOK)
Important events:
Time Details of events
Remarks:
(Signature) (Signature)
Region: Date:
Station: Day:
Even
Night
Region: Date:
Station: Day:
Even
Night
Region: Date:
Station: Day:
Shift Line Pressure in Deluge valve pressure in kg/cm2 at Deluge valve pressure in
kg/cm2 Converter Transformer* kg/cm2 at Line Reactors/
(per block/ side) Smoothening reactors*
Hydrant Spray Air/ Water Water Air/Water Water
Line Line R Y B R Y B
Morn
Even
Night
Pump Status
Electrical Hydrant Electrical Spray Jockey pump
Status Mode Stop switch position Status Mode Stop switch position Status Mode Stop switch position Old New
Shift Time Auto Man On Off Pressed Released Auto Man On Off Pressed Released Auto Man On Off Pressed Released
Morn
Even
Night
Compressors status
Compressor-1 Compressor-2 Compressor-3 Levels in
Status Mode Stop switch position Status Mode Stop switch position Status Mode Stop switch position Water Fighting
Shift Time Auto Man On Off Pressed Released Auto Man On Off Pressed Released Auto Man On Off Pressed Released tank tank
Morn
Even
Night
Monitoring of water system pumps in pump house
Pump POLE-1 POLE-2
Shift Time Status Main Standby Main Standby Main Standby
Selected
Status On/ Off On/ Off On/ Off On/ Off On/ Off On/ Off
Morn Mode Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man
Selected
Status On/ Off On/ Off On/ Off On/ Off On/ Off On/ Off
Even Mode Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man
Selected
Status On/ Off On/ Off On/ Off On/ Off On/ Off On/ Off
Night Mode Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man Auto / Man
Header pressure Deluge valve pressure at Converter Transformer in Kg/ Sq. Cm Deluge valve pressure at smoothing
in Kg/ Sq. Cm reactor in Kg/ Sq. Cm
Pole- 1 Pole- 2 Pole- 1 Pole- 2
Shift R Y B R Y B
Hydrant Spray
Header Header Water Air Water Air Water Air Water Air Water Air Water Air Water Air Water Air
Time Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr. Pr.
Morn
Morning Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Evening Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Night Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Spray LCP
Charger -I Battery- I Charger-II Battery-II Battery Fuel Mode Main Control Engine Heater
Shift Time
Volt Amp Volt Amp selected Level Supply Supply Supply
Morning Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Evening Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Night Trickle / Boost Trickle / Boost I / II Auto / Man On / Off On / Off On / Off
Signature Shift Executive Shift Jr. Engineer Shift Tech.
Morning
Evening
Night
FORMAT NO-HVDC/OP/11
DAILY LOG SHEET FOR VALVE COOLING SYSTEM
Region: Date:
Station: Day:
Shift Converter Pump Pump Filter No. of Coolers Main system De-ioniser Ckt. N2 Pr at Air Tank Flow in Flow in main Chem.
Inlet temp running flow Diff Pr conductivity Conductivity Expansion Pr (Bar) Main system Tank level
/ in (Lit/ Sec) (Bar) in S in S tank ckt. (DI ckt)
service (Bar)
1 2 1 or 2 In Fans 1 2 Make Main
service running up System
M
E
N
Signature Shift Executive Shift Jr. Engineer Shift Tech.
Morning
Evening
Night
Note: This format is applicable for ALSTOM back to back system
FORMAT NO-HVDC/OP/12
DAILY LOG SHEET FOR VALVE COOLING SYSTEM
Region: Date:
Station: Day:
Note: This format is applicable for ABB & Siemens system. Format to be considered as per system ( Fine water system/ Raw water system)
FORMAT NO-HVDC/OP/13
RECORD OF PLCCC COUNTER READING
Region:
Station:
Evening
Night
Morning
Evening
Night
Morning
Evening
Night
*Columns to be added depending upon availability of PLCC ckts. This format is applicable to back to
back stations.
FORMAT NO-HVDC/OP/14
RECORD OF P.T.W./ S.F.T. ISSUED
MONTH: .................
Sr. PTW / Name of PTW/ SFT PTW/ SFT Cancellation PTW/SFT Remarks
No. SFT No. Equipment/ Issue of PTW/ SFT
work area Date Time Issued Received Date Time Returned Cancelled
by by by by
Message Date Time in From To RLDC1 RLDC2 CPCC1 CPCC2 Brief Sent By Recd. Remarks
No. dd/mm/yy Hrs Message By
FORMAT NO-HVDC/OP/16
Region: .....................
Substation: .....................
Daily Log Sheet for Diesel Generator Set