HPW Address
Address Meaning Description
For download, when the recipe transfer unit is triggered
by the user, software obtains the recipe group number
from HPW0 and then downloads the recipe to the
terminal. For upload, when the recipe transfer unit is
Group number of
HPW0 triggered by the user, software will obtain the recipe
recipe
group number from HPW0 and then save the recipe
from PLC upload to the place where the group is
located, and the original recipe data of the group will be
overwritten.
HSW Address
Address Meaning Description
Save
HSW0 Save the parameter of project when HSW0=1
parameter settings
Cancel parameter Cancel the parameter of project when HSW0 and
HSW1
Settings HSW1 is mutually exclusive
COM1 of HMI
HSW2 Reserved
station No.
COM1 of PLC
HSW3 Reserved
station No.
0: RS232
Type of COM1
HSW4 1: RS485
serial port
2: RS422
COM serial port with 0: COM1
HSW5
PLC 1: COM2
0: 2400
1: 4800
2: 9600
COM1 baud rate
HSW6 3: 19200
(BPS)
4: 38400
5: 57600
6: 115200
0: 7
HSW7 COM1 data bits
1: 8
0: None
1: Odd
HSW8 COM1 check bits
2: Even
3:SPACE
0: 1 Bit
HSW9 COM1 stop bit
1: 2 Bit
0: None
HSW10 COM1 flow control 1: Software
2: Hardware
COM1 number of
HSW11
retied
COM1 waiting
HSW12 Unit: millisecond
timeout
COM1 receiving
HSW13 Unit: millisecond
timeout
HSW14 Default screen No. The first screen after starting the HMI
0: language 1
HSW15 Display language 1: Language 2
2: Language 3
HSW16 Font Reserved
HSW17 Font size Reserved
HSW18 Font quality Reserved
0: True
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 2 of 11
0:Sunday
1:Monday
HSW126 Local time - week 2:Tuesday
3:Wednesday
4:Thursday
5:Friday
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 3 of 11
6:Saterday
0: normal beeping
HSW127 Beep
1: keep beeping (unlatched )
HSW128 Script running cycle
Script running
HSW129 cycle is whether
variable or not
HMI IP address 1
HSW136
(left to right)
HMI IP address
HSW137
2 (left to right)
HMI IP address
HSW138
3 (left to right)
HMI IP
HSW139 address 4 (left to
right)
HMI subnet mask 1
HSW140
(left to right)
HMI subnet mask
HSW141
2 (left to right)
HMI subnet mask
HSW142
3 (left to right)
HMI subnet mask
HSW143
4 (left to right)
HMI default gateway
HSW144
1 (left to right)
HMI default gateway
HSW145
2 (left to right)
HMI default gateway
HSW146
3 (left to right)
HMI default gateway
HSW147
4 (left to right)
HSW148 HMI port address
Security level
0: False
HSW157 password
1: True
independent
Reserved HSW160~HSW163,total 4 bytes,max input is
HSW160 Password
8 characters password
The register number
which the current
1: level 1
HSW168 security level
2: level 2
password
switched lower
COM 1 timeout
HSW169 Range: 0~65535
retried
COM 2 timeout
HSW170 Range: 0~65535
retried
COM1 IO delay
HSW173 Range: 0~65535
read or write
COM2 IO delay
HSW174 Range: 0~65535
read or write
COM3 IO delay
HSW175 0~65535
read or write
Painting or
0: not heavy painting or empty
HSW00176 empty history XY
1: heavy painting or empty
plot
Display an error 0: False
HSW189
message 1: True
Empty record data 0: False
HSW191
files 1: True
Empty system 0: False
HSW192
configuration files 1: True
Min range of
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 4 of 11
keyboard
HSW193~194 0~0xFFFFFFFF
input,double word
Max range of
HSW195~196 keyboard 0~0xFFFFFFFF
input,double word
The number of
HSW200
current bit alarm
The number of
HSW201
current word alarm
0: False
Empty bits alarm
HSW202 1: True
data
2: Delete
0: False
Empty words alarm
HSW203 1: True
data
2: Delete
1: clear all file under” \ \ Flash \ \ Data “
2: clear all file under”\ \ Flash \ \Data \ \ DL “
3: clear all file under”\ \ Flash \ \ Data \ \ AL “
Clear file under “\
4: clear all file under”\ \ CFDC \ \ Data “
Flash \ Data”,check
HSW205 5: clear all file under”\ \ CFDC \ \Data \ \ DL “
data after re-power
6: clear all file under”\ \ CFDC \ \Data \ \ AL “
on.
7: clear all file under”\ \ Udisk \ \ Data”
8: clear all file under”\ \ Udisk \ \Data \ \ DL "
9: clear all file under” \ \ Udisk \ \ Data \ \ AL “
Close pop-up
window (only for It is valid when hsw214=1(word switch is suggested,
HSW214
alarm window and script doesn't work)
builtin 1013 screen)
Keyboard case 0:capital
HSW216
switching 1:lowercase
Clear multi- 0:False
HSW217
language setting 1:True
Settings screen 0:False
HSW218
saver switch 1:True
Start time of screen
HSW219 Unit: second
saver countdown
Screen saver
HSW220 Unit: second
countdown
HSW221 Screen sleep Unit: second
0:True
HSW223 Beep when alarm
1:False
PLC station No. Of
HSW224 Range: 0~255
COM2
HMI station No. Of
HSW225 Range: 1~255
COM2
PLC station No. Of
HSW227 Range: 0~255
COM2
HMI station No. Of
HSW229 Range: 1~255
COM2
Save CF/SD card
HSW230 System occupied
data to U disk
Read data from 0: False (from ache)
HSW233
Script 1: True (from PLC)
HSW238 Bit alarm flag 1: True
HSW239 Word alarm flag 1: True
Group number of
HSW243 Range: 1~3
Discrete recipe
Recipe upload or 1: upload
HSW244
download 2: download
HSW245 Clear alarm record Clear alarm record
Type of
HSW247 0: RS485
COM3 serial port
0: 2400
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 5 of 11
1: 4800
2: 9600
3: 9600
HSW248 COM3 baud rates 4: 19200
5: 38400
6: 57600
7: 115200
0: 7
HSW249 COM3 data bits
1: 8
0: None
1: Odd
HSW250 COM3 parity
2: Even
3: SPACE
0: 1 Bit
HSW251 COM3 stop bit
1: 2 Bit
0: None
HSW252 COM3 flow control 1: Software
2: Hardware
COM3 number of
HSW253
reties
COM3 waiting
HSW254 Unit: millisecond
timeout
COM3 receiving
HSW255 Unit: millisecond
data timeout
Save parameters of
0:True
HSW256 group No.0 data
1:False
record
Sampling period of
HSW257 group No.0 data Unit: second (0 ~ 65535)
record
Autosave period of
HSW258 group No.0 data Unit: minutes (0 ~ 65535)
record
The type of saving 0:According to setting to save data
HSW259 data of group No.0 1:save data to CF/SD card, data in HMI will be
data record cleared automatically
Save parameters of
0:True
HSW260 group No.1 data
1:False
record
Sampling period of
HSW261 group No.1 data Unit: second (0 ~ 65535 )
record
Autosave period of
HSW262 group No.1 data Unit: minutes( 0 ~ 65535)
record
The type of saving
0:According to setting to save data
HSW263 data of group No.1
1:save data to CF/SD card, data in HMI will be cleared
data record
… … …
Save parameters of
0:True
HSW296 group No.10 data
1:False
record
Sampling period of
HSW297 group No.10 data Unit: second (0 ~ 65535 )
record
Autosave period of
HSW298 group No.10 data Unit: minutes(0 ~ 65535)
record
The type of saving
0:According to setting to save data
HSW299 data of group
1:save data to CF/SD card, data in HMI will be cleared
No.10 data record
... ... ...
HSW456 Save parameters of
group No.50 data 0:True
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 6 of 11
record 1:False
Sampling period of
HSW457 group No.50 data Unit: second (0 ~ 65535 )
record
Autosave period of
HSW458 group No.50 data Unit: minutes(0 ~ 65535)
record
The type of saving
0:According to setting to save data
HSW459 data of group
1:save data to CF/SD card, data in HMI will be cleared
No.50 data record
Default level of parts
HSW501
security
HSW502 Current level of
parts security
Import group No. of
HSW503
recipe
export group No. of
HSW504
recipe
HSW505=0,No operation
HSW505=1,Copy your choose files to _T(“\\flash\\recp”)
HSW505=2,Copy all files to _T(“\\flash\\recp”)
HSW505=3,Copy the same files between _T
(“\\flash\\recp”) and your choose files to “file list path”
HSW505=4,Copy _T("\\flash\\recp") to “file list path”
HSW505=5,Delete your choose files in “file list path”
HSW505=6,Delete all files in “file list path”
HSW505 Delete the file list
HSW505=7,Delete the same files in _T(“\\flash\\recp”)
and your choose files in the file list
HSW505=8,Delete all files in _T(“\\flash\\recp”)
HSW505=9,Delete the files in _T(“\\flash\\recp”) and
your choose files in the file list
HSW505=10,Delete all files in _T(“\\flash\\recp”) and in
the file list
HSW505=11,Update the list in _T(“\\flash\\recp”)
Clear the current
HSW506
event list
Clear history event
HSW507
list
Delete EVReg.dat
HSW508
files
Parts security
HSW509
password separated
Whether opening
HSW500
parts password
X position of
HSW543
touching
Y position of
HSW544
touching
U disk state for print
HSW546 HSW546=1
part
State of saving HSW547=1:Saving
HSW547
picture HSW547=2:Saved
Screen No. of
HSW545
screen saver
HSW542 =1 Memory is full
HSW661~HSW666,Means year, month, day,
HSW661 File list
hour,minute,second for File list
HSW667=10000:importing
HSW667=10000+group:Import success
HSW667 File list import HSW667=20000:Import failure
export state HSW667=30000:Exporting
HSW667=30000+group:Export success
HSW667=40000+group:Export failure
HSW668=0: default value.HSW668=0 when using the
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 7 of 11
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 8 of 11
action of the
component;
Unenable: response
part click action, set
address to be
written value)
Read or write data by this area frequently may damage
HSW744~HSW1255 Latched address
FLASH
= 1: Refresh the file list and automatically zero when
HSW10385 Refresh file list
done
Data record auto
HSW10400 =1: Auto refresh shows 500 data records
refresh
Valid when HSW677 = 2. When the data is transferred
from HMI flash to the USB flash drive, a directory of
Folder name XXX is created in the root directory of the USB flash
HSW10463~HSW10470
register drive, and "XXX" is the text defined by HSW10463-
10470. (Text cannot only be numeric, alphabetic (the
letters are case sensitive))
Whether display the operation result in HSW244.
Recipe operation
HSW10475 = 1: Yes
tips
= others: No
HSX10000.0 User login Switch ON
HSX10000.1 Change password Switch ON
HSX10000.2 User launch Switch ON
HSX10000.3 Add user Switch ON
HSX10000.4 Delete user Switch ON
Add user from one
HSX10000.5 Switch ON
group
Delete user from
HSX10000.6 Switch ON
one group
HSX10000.8 Delete profile Switch ON
HSX10000.9 Export profile Switch ON
HSX10000.10 Import profile Switch ON
Export operation
HSX10000.11 Switch ON
records
Delete operation
HSX10000.12 Switch ON
records
=1,Insufficient authority to operate
=2,User doesn’t exist
=3,User has exised
=4,Wrong password
=5 ,login successfully
=6,Input password is inconsistent twice
=7,Change password successfully
=8,Add user successfully
=9,Delete user successfully
=10,Over the max number of user
Result display when
HSW10001 =11,User has existed in the group
user is operating
=12,User has been added in the group successfully
=13,User doesn’t exist in the group
=14,Remove user successfully
=15,Import file successfully
=16,Import file unsuccessfully
=17,Export file successfully
=18,Export file unsuccessfully
=19,User launch
=20,Delete profile successfully
=21,Delete operation records successfully
HSW10002 Old password When user is changing password,it still works
HSW10006 New user password
HSW10010 New user password Confirm new user password
HSW10014 New user name
Current system time
HSW10022~HSW10039 Display the time which included login and launch
display
mk:@MSITStore:C:\Program%20Files%20(x86)\LeviStudioU\EN_HmiHelp.chm::/10/10.... 3/27/2020
Address List Page 9 of 11
HDW3500~7999 Reflecting the word MODBUS RTU master is the address from 40 to 499.
address of For example ,HDW3500 means 40 and HDW3510