Professional Documents
Culture Documents
American International University-Bangladesh: Department of Electrical and Electronic Engineering
American International University-Bangladesh: Department of Electrical and Electronic Engineering
American International University-Bangladesh: Department of Electrical and Electronic Engineering
Introduction:
Most of the faults occur on power systems are unsymmetrical faults, which may consist of
unsymmetrical short circuit, unsymmetrical faults through impedances, or open conductors.
In this experiment, unsymmetrical fault analysis in the simulation environment will be
analyzed.
Most of the faults that occur on power systems are unsymmetrical faults :
1. Unsymmetrical short, circuits
2. Unsymmetrical faults through impedances
3. Open conductors
Unsymmetrical faults occur as:
1. Single line-to-ground faults
2. Line-to-line faults
3. Double line-to-ground faults
Pre-Lab Homework:
Relevant theories must be studied from class lectures, text book and reference books.
© Dept. of EEE, Faculty of Engineering, American International University-Bangladesh (AIUB) 1
Software Requirement:
A single-line diagram of the power system is shown in Figure 1, where negative- and zero-sequence
reactance are also given. The neutrals of the generator and ∆-Y transformers are solidly grounded.
The motor neutral is grounded through a reactance Xn. Calculate the per-unit sub-transient currents
in phase a, b, and c for a bolted three-phase-to-ground short-circuit at bus 2 (in figure 1). Pre-fault
voltage is 1.05 on a 100 MVA, 13.8 KV base in the generator zone. Also calculate the unsymmetrical
fault currents.
Experimental Procedure:
Reference(s):
Matlab Code:
clear all
close all
clc
% Ratings
%[X,Y] = pol2cart(pi*2/3,1);
%a = X+Y*j;
a = 1*exp(1i*pi*2/3);
alpha_mat = [1 1 1; 1 a^2 a; 1 a
a^2];
% Generator Rating
generator_apparent_power = 100e6;
generator_voltage = 13.8e3;
generator_positive_subtransient_reactance = 0.15j;
generator_negative_subtransient_reactance = 0.17j;
generator_zero_subtransient_reactance = 0.05j;
% Transformer-1 Rating
transformer_apparent_power = 100e6;
turns_ratio_1 = 13.8/138;
transformer_1_reactance = 0.1j;
%Transmission line
transmission_reactance_pos_neg = 20j;
transmission_reactance_zero = 60j;
% Transformer-2 Rating
transformer_apparent_power = 100e6;
turns_ratio_2 = 138/13.8;
transformer_2_reactance = 0.1j;
% Motor Rating
motor_apparent_power = 100e6;
motor_voltage = 13.8e3;
motor_positive_subtransient_reactance = 0.2j;
motor_negative_subtransient_reactance = 0.21j;
motor_zero_subtransient_reactance = 0.1j;
current_limitting_reactance = 0.05j;
% Base values
base_apparent_power = 100e6;
base_voltage_1 = 13.8e3;
base_voltage_2 = 138e3;
base_voltage_3 = 13.8e3;
base_impedance_1 =
base_voltage_1^2/base_apparent_power;
base_impedance_2 =
base_voltage_2^2/base_apparent_power;
base_impedance_3 =
base_voltage_3^2/base_apparent_power;
base_current_1 =
base_apparent_power/base_voltage_1/sqrt(3);
base_current_2 =
base_apparent_power/base_voltage_2/sqrt(3);
base_current_3 =
base_apparent_power/base_voltage_3/sqrt(3);
Ia2_double_line_to_ground = -v2_dltg/z_negative;
Ia0_double_line_to_ground = -v0_dltg/z_zero;