HEAT LOAD CALCULATIONS

JOB NAME: FOOD COURT


SPACE FOR:
SIZE: 14020 Sq ft 182260 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 110 75 75
(Sq ft) (Btu/h.sq ft) ROOM 73 55 67
N - Glass 0 14 0.32 0 DIFFERENCE 37 XXXX XXXX XXXX 8
NE - Glass 780 12 0.32 2995
E - Glass 0 12 0.32 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 12 0.32 0 People X 5 CFM/Person 701
S - Glass 0 12 0.32 0 Sq ft X 0.06 CFM/Sq ft 841.2
SW - Glass 1157 100 0.32 37009 CFM VENTILATION= 2005
W - Glass 0 164 0.32 0
NW - Glass 242 123 0.32 9528 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
Indicated ADP = 55 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 55.0 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 16.56 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 22947.6
N - Wall 0 39 0.21 0
NE - Wall 457 39 0.21 3739
E - Wall 0 39 0.21 0
SE - Wall 0 42 0.21 0
S - Wall 0 48 0.21 0
SW - Wall 677 54 0.21 7677
W - Wall 0 48 0.21 0
NW - Wall 142 39 0.21 1160
Roof Sun 0 54 0.05 0
NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 100 Sqft/person
ITEM Area Temp. diff. U Light = 1.0 W/Sqft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 2.00 W/Sqft
All Glass 2179 37 0.92 74159 Air Change per hour = 0.66
Partition wall 3369 32 0.32 34494
Ceiling 0 32 1.7 0
Floor 0 25 0.32 0
INTERNAL HEAT GAIN
People 140 Nos X 245 34349
Light 14020 W X 1.25 3.4 59585
Eq. Load 28040 W X 3.4 95336
ROOM SENSIBLE HEAT (RSH) 360031
Supply duct heat Supply duct Heat gain from
gain + leak. loss + fan HP(%) 12.0 43973
Outside & Infiltered Air
CFM °F BF FACTOR
0 37 1 1.08 0
2005 37 0.08 1.08 6409
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 410413
LATENT HEAT
People 140 Nos X 205 28741
Permeation Load 0
Outside & Infiltered Air Safety factor % 5.0 1481
CFM GR/LB BF FACTOR
0 8 1 0.68 0
2005 8 0.08 0.68 873
EFFECTIVE ROOM LATENT HEAT (ERLH) 31094
EFFECTIVE ROOM TOTAL HEAT (ERTH) 441508
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 38.6
2005 37 0.92 1.08 73705 CFM / Sq ft = 1.64
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 305
CFM GR/LB 1 - BF FACTOR CFM/ TR = 499
2005 8 0.92 0.68 10034
HEAT SUB TOTAL 525247
Return duct heat Dehum. & Pipe 3.0 15757
gain & leak. loss + HP Pump + loss (%)
TONS 46 GRAND TOTAL HEAT 541004

46 22948 498.86957
56 29971 535.19643
Clear 13
Glass 8.2
ACP 4.8

134.5
0
HEAT LOAD CALCULATIONS
JOB NAME: FOOD COURT
SPACE FOR: 0
SIZE: 14020 Sq ft 182260 Cu ft Estimate for: MONSOON
HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 92 83 157
(Sq ft) (Btu/h.sq ft) ROOM 73 55 67
N - Glass 0 11 0.32 0 DIFFERENCE 19 XXXX XXXX XXXX 90
NE - Glass 780 11 0.32 2746
E - Glass 0 11 0.32 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.32 0 People X CFM/Person
S - Glass 0 13 0.32 0 Sq ft X CFM/Sq ft
SW - Glass 1157 127 0.32 47001 CFM VENTILATION
W - Glass 0 165 0.32 0
NW - Glass 242 100 0.32 7746 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.89
Indicated ADP = 54 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.0 °F
Area Eq. temp. diff. U Dehum. temp rise = 17.48 °F
(°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 18240
N - Wall 0 7 0.21 0
NE - Wall 457 13 0.21 1246
E - Wall 0 21 0.21 0
SE - Wall 0 21 0.21 0
S - Wall 0 21 0.21 0
SW - Wall 677 17 0.21 2417
W - Wall 0 15 0.21 0
NW - Wall 142 9 0.21 268
Roof Sun 0 38 0.05 0

TRANS. GAIN EXCEPT WALLS & ROOF NOTES


ITEM Area Temp. diff. U Occupancy = 100 Sqft/person
(Sq ft) (°F) (Btu/h.sq ft) Light = 1.0 W/Sqft
All Glass 2179 19 0.92 38089 Eq. Load = 28.04 W/Sqft
Partition wall 3368.56 14 0.32 15091
Ceiling 0 14 1.7 0
Floor 0 14 0.32 0
INTERNAL HEAT GAIN
People 140 Nos X 245 34349
Light 14020 W X 1.25 3.41 59585
Eq. Load 28040 W X 3.41 95616
ROOM SENSIBLE HEAT (RSH) 304154
Supply duct heat Supply duct Heat gain from
gain + leak. loss + fan HP(%) 12.0 36893
Outside & Infiltered Air
CFM °F BF FACTOR
0 19 1 1.08 0
2005 19 0.08 1.08 3291
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 344339
LATENT HEAT
People 140 Nos X 205 28741
Permeation Load
Outside & Infiltered Air Safety factor% 5.0 1928
CFM GR/LB BF FACTOR
0 90 1 0.68 0
2005 90 0.08 0.68 9816
EFFECTIVE ROOM LATENT HEAT (ERLH) 40485
EFFECTIVE ROOM TOTAL HEAT (ERTH) 384824
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
2005 19 0.92 1.08 37849
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
2005 90 0.92 0.68 112882
HEAT SUB TOTAL 535554
Return duct heat HP Pump + Dehum. & Pipe 3.0 16067
gain & leak. loss + loss (%)
TONS 45.97 TOTAL HEAT 551621
SPECTRAL SERVICES CONSULTANTS PVT. LTD.
HEAT LOAD CALCULATIONS
JOB NAME: FOOD COURT
SPACE FOR: 0
SIZE: 14020 Sq ft 182260.00 Cu ft Estimate for: WINTER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 43 41 XXXX
(Sq ft) (Btu/h.sq ft) ROOM 72 XXXX
N - Glass 0.32 0 DIFFERENCE 29 XXXX XXXX XXXX XXXX
NE - Glass 0.32 0
E - Glass 0.32 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.32 0 People X CFM/Person
S - Glass 0.32 0 Sq ft X CFM/Sq ft
SW - Glass 0.32 0 CFM VENTILATION
W - Glass 0.32 0
NW - Glass 0.32 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
Sky light 0 Indicated ADP = °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM =
N - Wall 0.21 0
NE - Wall 0.21 0
E - Wall 0.21 0
SE - Wall 0.21 0
S - Wall 0.21 0
SW - Wall 0.21 0
W - Wall 0.21 0
NW - Wall 0.21 0
Roof Sun 0.059 0
Roof Shaded 0.20 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 2179 29 0.92 29062
Partition 0 24 0.32 0
Ceiling 0 24 1.7 0
Floor 0 24 0.32 0
INTERNAL HEAT GAIN
People 140 Nos X 245 -17175
Light 14020 W X 1.25 3.41 -29793
Eq. Load 14020 W X 3.41 -47808
ROOM SENSIBLE HEAT (RSH) -65713
Supply duct heat gain Supply duct Heat gain from 12
+ leak. loss + fan HP(%) -350
Outside & Infiltered Air
CFM °F BF FACTOR
0 29 1 1.08 0
2005 29 1 1.08 62792
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) -3271
LATENT HEAT
People Nos X
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor % 5.0
OUTSIDE AIR
CFM GR/LB BF FACTOR
XXXX 1 0.68
EFFECTIVE ROOM LATENT HEAT (ERLH)
EFFECTIVE ROOM TOTAL HEAT (ERTH)
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
2005 29 0 1.08
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
XXXX 0 0.68
HEAT SUB TOTAL CHECK FIGURE
Return duct heat gain HP Pump + Dehum. & Pipe 3.0 -98
& leak. loss + loss (%) Sq ft / KW = -14226
kW -0.99 GRAND TOTAL HEAT -3369