Professional Documents
Culture Documents
Cijevni Termostati Siemens - Thermostats RAM-TR.., RAM-TW.. - en
Cijevni Termostati Siemens - Thermostats RAM-TR.., RAM-TW.. - en
RAM-TR RAM-TW
RAM-TR...
Strap-on Thermostats RAM-TW...
Electromechanical TR and TW
Use
Typical applications:
In heat generation plant (control or supervision of the water temperature, control of
pumps, valves, etc.)
For general use in heating, ventilation and air conditioning plant
Function
Changeover switch When the externally adjustable setpoint of the control thermostat (TR) is reached on
(S.P.D.T) rising medium temperature, contact connection C-1 changes over to C-2.
When the internally adjustable switch-off temperature of the thermal reset limit thermo-
stat (TW) is reached on rising medium temperature, contact connection C-1 changes
over to C-2.
When the temperature of the medium falls by the value of the switching differential, the
contact connection reverts (C-1 closes, C-2 opens).
CE1N1197en
2017-12-01 Building Technologies
Changeover contact
Contact C - 1
ON
W: Setpoint
A: Switching differential
T (°C)
OFF
A W
1197D01
Type summary
Setpoint or switch-off
Standard set Scope of delivery
temperature range
0...90 °C,
RAM-TR.2000M Fixing spring, Mounting Instructions
externally adjustable
0...90 °C,
RAM-TW.2000M Fixing spring, Mounting Instructions
internally adjustable
Ordering When ordering, please give type reference according to <<Type summary>>.
Mechanical design
The housing of the thermostat is made of PA6 (reinforced) and is designed for surface
mounting. The bimetal sensing element is mounted on a steel plate.
Notes
Stripping Max. 9 mm
Wiring must be made in accordance with the connection diagram and in compliance
Max. AC 250 V
with local regulations.
Caution: Before opening the housing, disconnect the thermostat from the mains supply.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
2/4
3/4
1197A01
<
C 2 1 3
E E
2 1
L
N
Dimensions
38
~42
88
~105
1197M06
min.16
38
~42
~105
88
1197M05
min.16
Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd 2003
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change
4/4