V
Vendor Docu
ument Reviiew Sheet 
   
 
 
 
PROJECTT TITLE / No.  E
ELEPHANT
 
VENDOR R NAME / PO O No.  R
RAJESH POW
WER SERVICESS PVT LTD
 
DOCUMENT TITLE  D
DESIGN CALC
CULATION FO
OR LA 
 
VENDOR R DOCUMENT NO  RPSPL‐CIVIL‐DOC-LA‐01
R
 
CLIENT D
DOCUMENT NO   
 
REVISION NO  R0 
R
VEENDOR DOCU UMENT REV VIEW FEEDBA ACK 
Permission to proceed does not constitute o or approval o
of Design dettail, calculatio
ons, Analysiss, Test 
methods or Materials developed d OR selectedd by vendor,, and does NOT relieve veendor from FFULL 
compliance with con ntractual obligations  
 
  AP ‐ Appproved  
   
  AN ‐ Approved with comments aas noted. 
  Proceedd with Fabriccation Incorpporating com
mments 
   
  CA ‐ Commmented Reesubmit revissed drawing for  
  Approvaal 
   
 
  RE ‐  Rejjected, Revissed and resubmit for app
proval 
 
 
By :________________________________________________________        Date : ___ _________________ 
 
__________________________________________________________________________________________ 
 
 
 
ne 
Disciplin
 
 
Packagee Details 
 

 
PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
1. REFERENCE CODES 
PROJECT : ELEPHANT PERSTORP INDUSTRIES INDIA PVT. LTD

REFERENCE CODES

The following Indian codes and standards will be generally used for design of civil works.
In all cases, the latest revisions with amendments, if any, will be followed.

General
IS:875 Code of practice for design loads for building and structures
IS:1893 Criteria for Earthquake resistant desing of structures
IS:1911 Schedule of unit weight to building materials
Foundation
IS:1080 Code of practice for design and construction of shallow foundation
on soils (Other than raft, ring and shell)
IS:1904 Code of practice for design and construction of foundatios in soils:
General requirements
IS:2950 Code of practice for design and construction of raft foundations
IS:2911 Code of practice for design and construction of pile foundations
Concrete & Structural steel
IS:456 Code of practice for plain and Reinforced concrete
IS:800 Code of practice for structure steel
IS:2062 Structural Steel (Standard quantity) & plates
IS:123, IS:4180, IS:1477 Code of practice for Painting
IS:7215 Tolerances for Fabrication & Erection
IS:13920 Ductile detailing of reinforced concrete structures subjected to
Seismic forces - Code of practice.
IS:1608 Code of practice for Tensile Test
IS:1599 Code of practice for Bend Test
IS:1757 Code of practice for Impact Test
IS:808 Code of practice for Dimension & Cutting Tolerance
IS:1852 Code of practice for Rolling & Cutting Tolerance
IS:228 Code of practice for chemical analysis for steel
IS:12427 Code of practice for Bolt spectification
Water retaining structures
IS:3370 Code of practice for concrete structures for the liquid retaining structures

All mentioned code are of latest revision


PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
2. DESIGN CONSIDERATIONS 
PROJECT: ELEPHANT PERSTORP INDUSTRIES INDIA LTD.

DESIGN CONSIDERATIONS FOR LA


Project : Elephant
(66 KV SWITCHYARD FOR PERSTORP INDUSTRIES INDIA PVT. LTD)

1. DESIGN LIFE
50 Years
2. LOCATION
Plot No. T/49 to T/54 at village Sayakha, Ankleswar, Gujarat, India
3. STRUCTURAL DIMENSION - LA
Height of structure 3.54 From F.G.L to bottom of equipment
Pedestal Height 0.3 m Plan area
Clear structure height 3.24
4. FOUNDATION
Type Bolted connection with pedestal
RCC Pedestal foundation Fixed support- With Pile foundation
5. MATERIAL
Structural steel Fe 250
Reinforcement steel Fe 500 (Conforming to latest Indian Standards)
6. DEAD LOAD
Self weight of steel equipment supporting structure and pedestal & foundation self weight
7. EQUIPMENT LOAD
200 Kg
8. WIND CONSIDERATION (As per IS:875-2015-(Part-3))
Basic wind speed 44 m/s
Risk Coefficients (k1) 1.07
Terrain category 1
Building class A
Factor (k2) 1.05
Topography-upwind slope < 3 deg
Topography factor (k3) 1
Imp factor for cyclinic regn (k4) 1.3
Ka = Area averaging factor 1
Kc=Combination fator 1
Kd=Wind directionality factor 1
9. Earthquake Load Calculations (As per IS:1893-Part 1 & 4)
Zone Factor iii
Importan Factor 2 (Industrial equipment supporting structure)
Response Reduction factor 4 (Steel frame with Concetric Bracing)
Sa/g (Based on time period) 2.5 (Considered on higher side)
Concrete Damping 5%
Steel Damping 2%
10. STRUCTURE TYPE
Steel truss column to support the equipment (Free standing structure)
PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
3. CALCULATION FOR WIND FORCE 
PROJECT: ELEPHANT PERSTORP INDUSTRIES INDIA PVT. LTD

CALCULATION FOR WIND FORCES


Reference Code : IS-800-2015, Part-III

Location = Sayakha, Ankleswar, Gujarat

Basic wind speed (Vb) = 44 m/s


K1 (Probability Factor) = 1
(Mean probable life of structure 50 years)
K2 = 1
Terrain height and structures size factor (Refer Table 2)
K3 (Topography factor) = 1
K4 (Importance factor for cyclonic region) =
(As per Clause 6.3.4)

Design Wind speed (Vz = Vb*K1*K2*K3) = 44 m/s


2
Design Wind pressure (Pz = 0.6*Vz ) = 1161.6 N/sq.m

Design wind pressure at any height (Pd) = Ka x Kc x Kd xpz


Ka = Area averging factor = 1 Clause 7.2.2
Kc= Combination factor = 1 Clause 7.3.3.13
Kd=Wind direction factor = 1 Clause 7.2.1

Design wind pressure at any height(P d) = 1161.6 N/sq.m


2
= 0.11616 t/m

Overall Force Co-efficient for Towers composed of Flat-Sided Members


(IS:875-Part-3, Page No. 47)

Solidity Ratio = 0.3


For Square Tower = 2.8

Wind load on tower = 3252.48 N/sq.m


2
= 0.325248 t/m

Load Applied on Vertical supporting Member as uniformly distributed load for


staad Model

Wind Load (w) = 0.008131 t/m


PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
4. EARTHQUAKE LOAD CALCULATIONS 
PROJECT: ELEPHANT PERSTORP INDUSTRIAL INDIA PVT. LTD

Earthquake Load Calculation Clause

Design horizontal seismic coefficient ref. Clause of


IS:1893-2016
Ah = Z I Sa 6.4.2
2 R g

Spectral accl. Co-eff. Sa/g is dependent on period T of the structure.

0.75
T = 0.085 x h

h = height of structure 7.6.2


= 2.380 m
d = base dimension in direction 7.6.2
of earthquake
= 0.35 m X-dir
= 0.35 m Z-dir

therefore, T= 0.16 sec for X-dir


T= 0.16 sec for Z-dir

for medium soil


Sa / g = 2.5 6.4.5
zone factor
Z= 0.16 for Zone-III table-2 cl. 6.4.2
Importance factor
I= 2.0 table-6 cl. 6.4.2
Response reduction factor
R= 4.0 table-7 cl. 6.4.2

Ah = 0.1

total vertical load contributing to seimic force

W = 0.3 T (from Staad Model, DL & EL)

therefore base shear

VB = 0.030 T

Base shear Force shall be applied at the top of structure on higher side calculation
PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
5. STAAD EDITER INPUT 
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 14-Apr-17
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
1 0 0 0; 2 0 3.228 0; 3 0.3 0 0; 4 0.3 3.228 0; 5 0 0 -0.3; 6 0 3.228 -0.3;
7 0.3 0 -0.3; 8 0.3 3.228 -0.3; 9 0 0.449 0; 10 0 0.898 0; 11 0 1.347 0;
12 0 1.796 0; 13 0 2.245 0; 14 0 2.694 0; 15 0.3 0.449 0; 16 0.3 0.898 0;
17 0.3 1.347 0; 18 0.3 1.796 0; 19 0.3 2.245 0; 20 0.3 2.694 0;
21 0 0.449 -0.3; 22 0 0.898 -0.3; 23 0 1.347 -0.3; 24 0 1.796 -0.3;
25 0 2.245 -0.3; 26 0 2.694 -0.3; 27 0.3 0.449 -0.3; 28 0.3 0.898 -0.3;
29 0.3 1.347 -0.3; 30 0.3 1.796 -0.3; 31 0.3 2.245 -0.3; 32 0.3 2.694 -0.3;
MEMBER INCIDENCES
1 1 9; 2 3 15; 3 5 21; 4 7 27; 5 2 6; 6 2 4; 9 9 10; 10 10 11; 11 11 12;
12 12 13; 13 13 14; 14 14 2; 15 15 16; 16 16 17; 17 17 18; 18 18 19; 19 19 20;
20 20 4; 21 1 15; 22 15 10; 23 10 17; 24 17 12; 25 12 19; 26 19 14; 27 14 4;
28 21 22; 29 22 23; 30 23 24; 31 24 25; 32 25 26; 33 26 6; 40 27 28; 41 28 29;
42 29 30; 43 30 31; 44 31 32; 45 32 8; 46 5 9; 47 9 22; 48 22 11; 49 11 24;
50 24 13; 51 13 26; 52 26 2; 53 7 21; 54 21 28; 55 28 23; 56 23 30; 57 30 25;
58 25 32; 59 32 6; 60 6 8; 61 3 27; 62 27 16; 63 16 29; 64 29 18; 65 18 31;
66 31 20; 67 20 8; 68 4 8; 69 1 3; 70 3 7; 71 5 7; 72 1 5;
DEFINE MATERIAL START
ISOTROPIC STEEL
E 2.09042e+007
POISSON 0.3
DENSITY 7.83341
ALPHA 1.2e-005
DAMP 0.03
END DEFINE MATERIAL
MEMBER PROPERTY INDIAN
1 TO 4 9 TO 20 28 TO 33 40 TO 45 TABLE ST ISA65X65X6
21 TO 27 46 TO 59 61 TO 67 69 TO 72 TABLE ST ISA50X50X6
5 6 60 68 TABLE ST ISA75X75X8
CONSTANTS
BETA 45 ALL
MATERIAL STEEL ALL
SUPPORTS
1 3 5 7 PINNED
LOAD 1 LOADTYPE Dead TITLE DL
SELFWEIGHT Y -1
LOAD 2 LOADTYPE Live TITLE EL
JOINT LOAD
2 4 6 8 FY -0.05
LOAD 3 LOADTYPE Seismic TITLE EQX
JOINT LOAD
2 4 6 8 FX -0.0075
LOAD 4 LOADTYPE Seismic TITLE EQZ
JOINT LOAD
2 4 6 8 FZ -0.0075
LOAD 5 LOADTYPE Wind TITLE WLX
MEMBER LOAD
1 3 9 TO 14 28 TO 33 UNI GX 0.0081
LOAD 6 LOADTYPE Wind TITLE WLZ
MEMBER LOAD
1 2 9 TO 20 UNI GZ -0.0081
LOAD COMB 7 COMBINATION LOAD CASE 7
1 1.0 2 1.0
LOAD COMB 8 COMBINATION LOAD CASE 8
1 1.0 2 1.0 3 1.0
LOAD COMB 9 COMBINATION LOAD CASE 9
1 1.0 2 1.0 4 1.0
LOAD COMB 10 COMBINATION LOAD CASE 10
1 1.0 2 1.0 5 1.0
LOAD COMB 11 COMBINATION LOAD CASE 11
1 1.0 2 1.0 6 1.0
PERFORM ANALYSIS PRINT ALL
LOAD LIST 7 TO 11
PARAMETER 1
CODE INDIAN
KY 1 ALL
KZ 1 ALL
TRACK 2 ALL
CHECK CODE ALL
STEEL TAKE OFF ALL
Page: 1
PROJECT: ELEPHANT                                                                                 PERSTORP INDUSTRIES INDIA PVT. LTD 

 
 
 
 
 
 
 
 
6. STAAD OUTPUT FILE 
Monday, March 30, 2020, 07:13 PM

****************************************************
* *
* STAAD.Pro *
* Version 2007 Build 04 *
* Proprietary Program of *
* Research Engineers, Intl. *
* Date= MAR 30, 2020 *
* Time= 19:11:45 *
* *
* USER ID: *
****************************************************

1. STAAD SPACE
INPUT FILE: LA.STD
2. START JOB INFORMATION
3. ENGINEER DATE 14-APR-17
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER MTON
7. JOINT COORDINATES
8. 1 0 0 0; 2 0 3.228 0; 3 0.3 0 0; 4 0.3 3.228 0; 5 0 0 -0.3; 6 0 3.228 -0.3
9. 7 0.3 0 -0.3; 8 0.3 3.228 -0.3; 9 0 0.449 0; 10 0 0.898 0; 11 0 1.347 0
10. 12 0 1.796 0; 13 0 2.245 0; 14 0 2.694 0; 15 0.3 0.449 0; 16 0.3 0.898 0
11. 17 0.3 1.347 0; 18 0.3 1.796 0; 19 0.3 2.245 0; 20 0.3 2.694 0
12. 21 0 0.449 -0.3; 22 0 0.898 -0.3; 23 0 1.347 -0.3; 24 0 1.796 -0.3
13. 25 0 2.245 -0.3; 26 0 2.694 -0.3; 27 0.3 0.449 -0.3; 28 0.3 0.898 -0.3
14. 29 0.3 1.347 -0.3; 30 0.3 1.796 -0.3; 31 0.3 2.245 -0.3; 32 0.3 2.694 -0.3
15. MEMBER INCIDENCES
16. 1 1 9; 2 3 15; 3 5 21; 4 7 27; 5 2 6; 6 2 4; 9 9 10; 10 10 11; 11 11 12
17. 12 12 13; 13 13 14; 14 14 2; 15 15 16; 16 16 17; 17 17 18; 18 18 19; 19 19 20
18. 20 20 4; 21 1 15; 22 15 10; 23 10 17; 24 17 12; 25 12 19; 26 19 14; 27 14 4
19. 28 21 22; 29 22 23; 30 23 24; 31 24 25; 32 25 26; 33 26 6; 40 27 28; 41 28 29
20. 42 29 30; 43 30 31; 44 31 32; 45 32 8; 46 5 9; 47 9 22; 48 22 11; 49 11 24
21. 50 24 13; 51 13 26; 52 26 2; 53 7 21; 54 21 28; 55 28 23; 56 23 30; 57 30 25
22. 58 25 32; 59 32 6; 60 6 8; 61 3 27; 62 27 16; 63 16 29; 64 29 18; 65 18 31
23. 66 31 20; 67 20 8; 68 4 8; 69 1 3; 70 3 7; 71 5 7; 72 1 5
24. DEFINE MATERIAL START
25. ISOTROPIC STEEL
26. E 2.09042E+007
27. POISSON 0.3
28. DENSITY 7.83341
29. ALPHA 1.2E-005
30. DAMP 0.03
31. END DEFINE MATERIAL
32. MEMBER PROPERTY INDIAN
33. 1 TO 4 9 TO 20 28 TO 33 40 TO 45 TABLE ST ISA65X65X6
34. 21 TO 27 46 TO 59 61 TO 67 69 TO 72 TABLE ST ISA50X50X6
35. 5 6 60 68 TABLE ST ISA75X75X8
36. CONSTANTS
37. BETA 45 ALL
38. MATERIAL STEEL ALL
39. SUPPORTS
40. 1 3 5 7 PINNED
41. LOAD 1 LOADTYPE DEAD TITLE DL
42. SELFWEIGHT Y -1
43. LOAD 2 LOADTYPE LIVE TITLE EL
44. JOINT LOAD
45. 2 4 6 8 FY -0.05
46. LOAD 3 LOADTYPE SEISMIC TITLE EQX
47. JOINT LOAD
48. 2 4 6 8 FX -0.0075
49. LOAD 4 LOADTYPE SEISMIC TITLE EQZ
50. JOINT LOAD
51. 2 4 6 8 FZ -0.0075

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 1 of 64
Monday, March 30, 2020, 07:13 PM
52. LOAD 5 LOADTYPE WIND TITLE WLX
53. MEMBER LOAD
54. 1 3 9 TO 14 28 TO 33 UNI GX 0.0081
55. LOAD 6 LOADTYPE WIND TITLE WLZ
56. MEMBER LOAD
57. 1 2 9 TO 20 UNI GZ -0.0081
58. LOAD COMB 7 COMBINATION LOAD CASE 7
59. 1 1.0 2 1.0
60. LOAD COMB 8 COMBINATION LOAD CASE 8
61. 1 1.0 2 1.0 3 1.0
62. LOAD COMB 9 COMBINATION LOAD CASE 9
63. 1 1.0 2 1.0 4 1.0
64. LOAD COMB 10 COMBINATION LOAD CASE 10
65. 1 1.0 2 1.0 5 1.0
66. LOAD COMB 11 COMBINATION LOAD CASE 11
67. 1 1.0 2 1.0 6 1.0
68. PERFORM ANALYSIS PRINT ALL

P R O B L E M S T A T I S T I C S
-----------------------------------

NUMBER OF JOINTS/MEMBER+ELEMENTS/SUPPORTS = 32/ 64/ 4

SOLVER USED IS THE IN-CORE ADVANCED SOLVER

TOTAL PRIMARY LOAD CASES = 6, TOTAL DEGREES OF FREEDOM = 180

LOADING 1 LOADTYPE DEAD TITLE DL


-----------

SELFWEIGHT Y -1.000

ACTUAL WEIGHT OF THE STRUCTURE = 0.160 MTON

LOADING 2 LOADTYPE LIVE TITLE EL


-----------

JOINT LOAD - UNIT MTON METE

JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z

2 0.00 -0.05 0.00 0.00 0.00 0.00


4 0.00 -0.05 0.00 0.00 0.00 0.00
6 0.00 -0.05 0.00 0.00 0.00 0.00
8 0.00 -0.05 0.00 0.00 0.00 0.00

LOADING 3 LOADTYPE SEISMIC TITLE EQX


-----------

JOINT LOAD - UNIT MTON METE

JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z

2 -0.01 0.00 0.00 0.00 0.00 0.00


4 -0.01 0.00 0.00 0.00 0.00 0.00
6 -0.01 0.00 0.00 0.00 0.00 0.00
8 -0.01 0.00 0.00 0.00 0.00 0.00

LOADING 4 LOADTYPE SEISMIC TITLE EQZ

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 2 of 64
Monday, March 30, 2020, 07:13 PM
-----------

JOINT LOAD - UNIT MTON METE

JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z

2 0.00 0.00 -0.01 0.00 0.00 0.00


4 0.00 0.00 -0.01 0.00 0.00 0.00
6 0.00 0.00 -0.01 0.00 0.00 0.00
8 0.00 0.00 -0.01 0.00 0.00 0.00

LOADING 5 LOADTYPE WIND TITLE WLX


-----------

MEMBER LOAD - UNIT MTON METE

MEMBER UDL L1 L2 CON L LIN1 LIN2

1 0.0081 GX 0.00 0.45


3 0.0081 GX 0.00 0.45
9 0.0081 GX 0.00 0.45
10 0.0081 GX 0.00 0.45
11 0.0081 GX 0.00 0.45
12 0.0081 GX 0.00 0.45
13 0.0081 GX 0.00 0.45
14 0.0081 GX 0.00 0.53
28 0.0081 GX 0.00 0.45
29 0.0081 GX 0.00 0.45
30 0.0081 GX 0.00 0.45
31 0.0081 GX 0.00 0.45
32 0.0081 GX 0.00 0.45
33 0.0081 GX 0.00 0.53

LOADING 6 LOADTYPE WIND TITLE WLZ


-----------

MEMBER LOAD - UNIT MTON METE

MEMBER UDL L1 L2 CON L LIN1 LIN2

1 -0.0081 GZ 0.00 0.45


2 -0.0081 GZ 0.00 0.45
9 -0.0081 GZ 0.00 0.45
10 -0.0081 GZ 0.00 0.45
11 -0.0081 GZ 0.00 0.45
12 -0.0081 GZ 0.00 0.45
13 -0.0081 GZ 0.00 0.45
14 -0.0081 GZ 0.00 0.53
15 -0.0081 GZ 0.00 0.45
16 -0.0081 GZ 0.00 0.45
17 -0.0081 GZ 0.00 0.45
18 -0.0081 GZ 0.00 0.45
19 -0.0081 GZ 0.00 0.45
20 -0.0081 GZ 0.00 0.53

FOR LOADING - 1
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
1-1.29241E-11-3.84455E-03 1.96714E-19-3.33703E-05-7.49482E-21-9.34370E-05
2 0.00000E+00-5.59304E-03-2.67536E-12-1.34989E-04-1.99862E-20-6.68581E-05
3 1.96714E-19-3.84455E-03 1.29241E-11-9.34370E-05-2.49827E-21 3.33703E-05
4-2.67536E-12-5.59304E-03 1.96714E-19-6.68581E-05 0.00000E+00 1.34989E-04

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 3 of 64
Monday, March 30, 2020, 07:13 PM
5 0.00000E+00-3.84455E-03-1.29241E-11 9.34370E-05-2.49827E-21-3.33703E-05
6 2.67536E-12-5.59304E-03 0.00000E+00 6.68581E-05 0.00000E+00-1.34989E-04
7 1.29241E-11-3.84455E-03 0.00000E+00 3.33703E-05 2.49827E-21 9.34370E-05
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
8 1.96714E-19-5.59304E-03 2.67536E-12 1.34989E-04 1.99862E-20 6.68581E-05
9 0.00000E+00-5.01946E-03 0.00000E+00-1.20133E-04 0.00000E+00 0.00000E+00
10 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00-1.20133E-04
11 0.00000E+00-5.01946E-03 0.00000E+00-1.20133E-04 0.00000E+00 0.00000E+00
12-2.40943E-12-5.01946E-03 0.00000E+00 4.99654E-21 0.00000E+00-1.20133E-04
13 0.00000E+00-5.01946E-03-4.81886E-12-1.20133E-04 0.00000E+00-9.99309E-21
14 7.83930E-12-5.42844E-03 0.00000E+00 9.99309E-21 2.49827E-21-1.28198E-04
15 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00 1.20133E-04
16 0.00000E+00-5.01946E-03 0.00000E+00-1.20133E-04 0.00000E+00 0.00000E+00
17 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00 1.20133E-04
18 0.00000E+00-5.01946E-03 2.40943E-12-1.20133E-04 0.00000E+00-4.99654E-21
19-4.81886E-12-5.01946E-03 0.00000E+00-9.99309E-21 0.00000E+00 1.20133E-04
20 0.00000E+00-5.42844E-03-7.83930E-12-1.28198E-04 2.49827E-21-9.99309E-21
21 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00-1.20133E-04
22 0.00000E+00-5.01946E-03 0.00000E+00 1.20133E-04 0.00000E+00 0.00000E+00
23 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00-1.20133E-04
24 0.00000E+00-5.01946E-03-2.40943E-12 1.20133E-04 0.00000E+00 4.99654E-21
25 4.81886E-12-5.01946E-03 0.00000E+00 9.99309E-21 0.00000E+00-1.20133E-04
26 0.00000E+00-5.42844E-03 7.83930E-12 1.28198E-04 2.49827E-21 9.99309E-21
27 0.00000E+00-5.01946E-03 0.00000E+00 1.20133E-04 0.00000E+00 0.00000E+00
28 0.00000E+00-5.01946E-03 0.00000E+00 0.00000E+00 0.00000E+00 1.20133E-04
29 0.00000E+00-5.01946E-03 0.00000E+00 1.20133E-04 0.00000E+00 0.00000E+00
30 2.40943E-12-5.01946E-03 0.00000E+00-4.99654E-21 0.00000E+00 1.20133E-04
31 0.00000E+00-5.01946E-03 4.81886E-12 1.20133E-04 0.00000E+00 9.99309E-21
32-7.83930E-12-5.42844E-03 0.00000E+00-9.99309E-21 2.49827E-21 1.28198E-04

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 1


LOADTYPE DEAD TITLE DL

CENTER OF FORCE BASED ON Y FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.149999999E+00
Y = 0.166364056E+01
Z = -0.149999999E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 1 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = -0.16
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -2.3978011E-02 MY= -8.9930573E-12 MZ= -2.3978011E-02

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 1 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = 0.16
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 2.3978011E-02 MY= 8.9930636E-12 MZ= 2.3978011E-02

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 1)


MAXIMUMS AT NODE
X = -1.47162E-04 22
Y = -4.20971E-04 6
Z = -1.56535E-04 28
RX= -2.39922E-06 3
RY= 5.99830E-06 2

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 4 of 64
Monday, March 30, 2020, 07:13 PM

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

SUPPORT=1
FOR LOADING - 2
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
2 0.00000E+00-5.00000E-02 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00
4 0.00000E+00-5.00000E-02 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00
6 0.00000E+00-5.00000E-02 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00
8 0.00000E+00-5.00000E-02 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 2


LOADTYPE LIVE TITLE EL

CENTER OF FORCE BASED ON Y FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.149999999E+00
Y = 0.322800002E+01
Z = -0.149999999E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 2 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = -0.20
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -2.9999998E-02 MY= 0.0000000E+00 MZ= -2.9999998E-02

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 2 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = 0.20
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 2.9999998E-02 MY= 1.7687766E-17 MZ= 2.9999998E-02

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 2)


MAXIMUMS AT NODE
X = -2.72946E-04 6
Y = -1.01982E-03 2
Z = 2.95770E-04 14
RX= -2.75267E-06 7
RY= 1.84949E-05 4
RZ= -3.54242E-06 3

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

SUPPORT=1
FOR LOADING - 3
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
2-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00
4-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 5 of 64
Monday, March 30, 2020, 07:13 PM
6-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00
8-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00 0.00000E+00

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 3


LOADTYPE SEISMIC TITLE EQX

CENTER OF FORCE BASED ON X FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.149999999E+00
Y = 0.322800002E+01
Z = -0.149999999E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 3 )


SUMMATION FORCE-X = -3.0000001E-02
SUMMATION FORCE-Y = 0.0000000E+00
SUMMATION FORCE-Z = 0.0000000E+00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 0.0000000E+00 MY= 4.5000000E-03 MZ= 9.6840001E-02

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 3 )


SUMMATION FORCE-X = 3.0000001E-02
SUMMATION FORCE-Y = -6.7984477E-16
SUMMATION FORCE-Z = -8.3997024E-17

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -1.5690989E-11 MY= -4.5000000E-03 MZ= -9.6840001E-02

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 3)


MAXIMUMS AT NODE
X = -2.51951E-02 2
Y = 1.65525E-03 4
Z = 5.51445E-04 9
RX= 5.71161E-06 27
RY= -2.93156E-05 22
RZ= 1.12165E-04 20

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

SUPPORT=1
1 0.00 0.00 0.00 0.00 0.00 0.00
-0.02 -0.16 0.00 0.00 0.00 0.00 111000

3 0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.16 0.00 0.00 0.00 0.00 111000

5 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.16 0.00 0.00 0.00 0.00 111000

7 0.00 0.00 0.00 0.00 0.00 0.00


-0.01 0.16 0.00 0.00 0.00 0.00 111000

FOR LOADING - 4
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
2 0.00000E+00 0.00000E+00-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00
4 0.00000E+00 0.00000E+00-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00
6 0.00000E+00 0.00000E+00-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00
8 0.00000E+00 0.00000E+00-7.50000E-03 0.00000E+00 0.00000E+00 0.00000E+00

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 6 of 64
Monday, March 30, 2020, 07:13 PM

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 4


LOADTYPE SEISMIC TITLE EQZ

CENTER OF FORCE BASED ON Z FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.149999999E+00
Y = 0.322800002E+01
Z = -0.149999999E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 4 )


SUMMATION FORCE-X = 0.0000000E+00
SUMMATION FORCE-Y = 0.0000000E+00
SUMMATION FORCE-Z = -3.0000001E-02

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -9.6840001E-02 MY= 4.5000000E-03 MZ= 0.0000000E+00

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 4 )


SUMMATION FORCE-X = 0.0000000E+00
SUMMATION FORCE-Y = -1.4352278E-15
SUMMATION FORCE-Z = 3.0000001E-02

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 9.6840001E-02 MY= -4.5000000E-03 MZ= -1.5521829E-11

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 4)


MAXIMUMS AT NODE
X = -5.58092E-04 15
Y = -1.68898E-03 8
Z = -2.52628E-02 4
RX= -1.13246E-04 32
RY= 2.78042E-05 22
RZ= 8.56504E-06 3

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

SUPPORT=1
1 0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.16 0.00 0.00 0.00 0.00 111000

3 0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.16 -0.02 0.00 0.00 0.00 111000

5 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.16 -0.01 0.00 0.00 0.00 111000

7 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.16 0.00 0.00 0.00 0.00 111000

FOR LOADING - 5
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
1 1.81845E-03 0.00000E+00 1.96714E-19 1.99862E-20 0.00000E+00-1.36081E-04
2 2.16270E-03 0.00000E+00 1.96714E-19-1.99862E-20 0.00000E+00 1.92480E-04
5 1.81845E-03 0.00000E+00 1.96714E-19 1.99862E-20 0.00000E+00-1.36081E-04
6 2.16270E-03 0.00000E+00 1.96714E-19-1.99862E-20 0.00000E+00 1.92480E-04
9 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11
10 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 7 of 64
Monday, March 30, 2020, 07:13 PM
11 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11
12 3.63690E-03 0.00000E+00 1.96714E-19 0.00000E+00 0.00000E+00 4.55235E-11
13 3.63690E-03 0.00000E+00 1.96714E-19 9.99309E-21 0.00000E+00-1.21396E-10
14 3.98115E-03 0.00000E+00 3.93429E-19-1.99862E-20 0.00000E+00-5.63995E-05
21 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11
22 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11
23 3.63690E-03 0.00000E+00 3.93429E-19 9.99309E-21 0.00000E+00-1.51745E-11
24 3.63690E-03 0.00000E+00 1.96714E-19 0.00000E+00 0.00000E+00 4.55235E-11
25 3.63690E-03 0.00000E+00 1.96714E-19 9.99309E-21 0.00000E+00-1.21396E-10
26 3.98115E-03 0.00000E+00 3.93429E-19-1.99862E-20 0.00000E+00-5.63995E-05

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 5


LOADTYPE WIND TITLE WLX

CENTER OF FORCE BASED ON X FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.000000000E+00
Y = 0.161400000E+01
Z = -0.149999999E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 5 )


SUMMATION FORCE-X = 5.2293606E-02
SUMMATION FORCE-Y = 0.0000000E+00
SUMMATION FORCE-Z = 4.7211442E-18

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 7.1393929E-18 MY= -7.8440406E-03 MZ= -8.4401878E-02

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 5 )


SUMMATION FORCE-X = -5.2293606E-02
SUMMATION FORCE-Y = 6.7984477E-16
SUMMATION FORCE-Z = 9.7767028E-17

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 1.8094007E-11 MY= 7.8440406E-03 MZ= 8.4401878E-02

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 5)


MAXIMUMS AT NODE
X = 1.68582E-02 6
Y = 9.97139E-04 6
Z = -4.33136E-04 9
RX= -3.89769E-06 27
RY= 2.43370E-05 28
RZ= -6.54379E-05 25

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

SUPPORT=1
1 0.00 0.00 0.00 0.00 0.00 0.00
0.02 0.14 0.00 0.00 0.00 0.00 111000

3 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.14 0.00 0.00 0.00 0.00 111000

5 0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.14 0.00 0.00 0.00 0.00 111000

7 0.00 0.00 0.00 0.00 0.00 0.00


0.02 -0.14 0.00 0.00 0.00 0.00 111000

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 8 of 64
Monday, March 30, 2020, 07:13 PM

FOR LOADING - 6
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
1 1.96714E-19 0.00000E+00-1.81845E-03-1.36081E-04 0.00000E+00-1.99862E-20
2 1.96714E-19 0.00000E+00-2.16270E-03 1.92480E-04 0.00000E+00 1.99862E-20
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
3 1.96714E-19 0.00000E+00-1.81845E-03-1.36081E-04 0.00000E+00-1.99862E-20
4 1.96714E-19 0.00000E+00-2.16270E-03 1.92480E-04 0.00000E+00 1.99862E-20
9 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
10 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
11 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
12 1.96714E-19 0.00000E+00-3.63690E-03 4.55235E-11 0.00000E+00 0.00000E+00
13 1.96714E-19 0.00000E+00-3.63690E-03-1.21396E-10 0.00000E+00-9.99309E-21
14 3.93429E-19 0.00000E+00-3.98115E-03-5.63995E-05 0.00000E+00 1.99862E-20
15 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
16 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
17 3.93429E-19 0.00000E+00-3.63690E-03-1.51745E-11 0.00000E+00-9.99309E-21
18 1.96714E-19 0.00000E+00-3.63690E-03 4.55235E-11 0.00000E+00 0.00000E+00
19 1.96714E-19 0.00000E+00-3.63690E-03-1.21396E-10 0.00000E+00-9.99309E-21
20 3.93429E-19 0.00000E+00-3.98115E-03-5.63995E-05 0.00000E+00 1.99862E-20

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 6


LOADTYPE WIND TITLE WLZ

CENTER OF FORCE BASED ON Z FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.149999999E+00
Y = 0.161400000E+01
Z = 0.000000000E+00

***TOTAL APPLIED LOAD ( MTON METE ) SUMMARY (LOADING 6 )


SUMMATION FORCE-X = 4.7211442E-18
SUMMATION FORCE-Y = 0.0000000E+00
SUMMATION FORCE-Z = -5.2293606E-02

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -8.4401878E-02 MY= 7.8440406E-03 MZ= -7.1393929E-18

***TOTAL REACTION LOAD( MTON METE ) SUMMARY (LOADING 6 )


SUMMATION FORCE-X = -9.0488597E-18
SUMMATION FORCE-Y = -8.0574194E-16
SUMMATION FORCE-Z = 5.2293606E-02

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 8.4401878E-02 MY= -7.8440406E-03 MZ= -1.8795371E-12

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 6)


MAXIMUMS AT NODE
X = -5.56012E-04 16
Y = 1.01317E-03 2
Z = -1.69012E-02 2
RX= -6.67610E-05 14
RY= -2.58614E-05 16
RZ= 7.57058E-06 3

EXTERNAL AND INTERNAL JOINT LOAD SUMMARY ( MTON METE )-

JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 9 of 64
Monday, March 30, 2020, 07:13 PM
SUPPORT=1
1 0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.14 0.00 0.00 0.00 0.00 111000

3 0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.14 -0.03 0.00 0.00 0.00 111000

5 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.14 -0.02 0.00 0.00 0.00 111000

7 0.00 0.00 0.00 0.00 0.00 0.00


0.00 -0.14 0.00 0.00 0.00 0.00 111000

LOAD COMBINATION NO. 7


COMBINATION LOAD CASE 7

LOADING- 1. 2.
FACTOR - 1.00 1.00

LOAD COMBINATION NO. 8


COMBINATION LOAD CASE 8

LOADING- 1. 2. 3.
FACTOR - 1.00 1.00 1.00

LOAD COMBINATION NO. 9


COMBINATION LOAD CASE 9

LOADING- 1. 2. 4.
FACTOR - 1.00 1.00 1.00

LOAD COMBINATION NO. 10


COMBINATION LOAD CASE 10

LOADING- 1. 2. 5.
FACTOR - 1.00 1.00 1.00

LOAD COMBINATION NO. 11


COMBINATION LOAD CASE 11

LOADING- 1. 2. 6.
FACTOR - 1.00 1.00 1.00

************ END OF DATA FROM INTERNAL STORAGE ************

69. LOAD LIST 7 TO 11


70. PARAMETER 1
71. CODE INDIAN
72. KY 1 ALL
73. KZ 1 ALL
74. TRACK 2 ALL
75. CHECK CODE ALL

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 1 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 10 of 64
Monday, March 30, 2020, 07:13 PM
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 L11 -------------|
| KL/R-Y= 17.6 | L8 FA = 142.2 |
| KL/R-Z= 35.6 + L11 fa = 2.9 |
| UNL = 449.0 | L8 L11 FCZ = 137.5 |
| C = 400.0 + L8 FTZ = 165.0 |
| CMY = 0.57 | L11 FCY = 165.0 |
| CMZ = 0.40 + L9 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.8 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.2 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.4 0.0 |
| LOADING 8 11 10 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.028 8 |
| 2.14 C 0.0 0.0 0.45 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 2 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L8 STRESSES |
|IN NEWT MM |L11 L8 IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L8 FA = 142.2 |
| KL/R-Z= 35.6 + L11 L8 fa = 2.9 |
| UNL = 449.0 | L8 FCZ = 137.5 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 11 of 64
Monday, March 30, 2020, 07:13 PM
| C = 400.0 + FTZ = 165.0 |
| CMY = 0.70 | L11 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L10 L8 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.5 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.2 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.4 0.4 |
| LOADING 10 11 11 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.025 10 |
| 2.16 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 3 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L9 STRESSES |
|IN NEWT MM | L9 IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 17.6 | FA = 142.2 |
| KL/R-Z= 35.6 + L9 fa = 2.9 |
| UNL = 449.0 | L9 FCZ = 137.5 |
| C = 180.0 +L9 FTZ = 165.0 |
| CMY = 0.58 | L9 L11 FCY = 165.0 |
| CMZ = 0.44 + L11 FTY = 165.0 |
| FYLD = 249.9 | L9 L8 fbz = 0.7 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 12 of 64
Monday, March 30, 2020, 07:13 PM
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.0 0.4 |
| LOADING 8 10 10 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.026 9 |
| 2.13 C 0.0 0.0 0.45 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 4 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | L10 IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L10 FA = 142.2 |
| KL/R-Z= 35.6 + L10 fa = 3.2 |
| UNL = 449.0 | L10 L10 FCZ = 137.5 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.72 | FCY = 165.0 |
| CMZ = 0.55 + L9 L9 L10 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.4 0.0 |
| LOADING 9 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 13 of 64
Monday, March 30, 2020, 07:13 PM
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.028 9 |
| 2.39 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 5 * | INDIAN SECTIONS | AX = 11.4 |
| * | ST ISA75X75X8 | --Z AY = 4.0 |
|DESIGN CODE * | | AZ = 4.0 |
| IS-800 * =============================== |
| * SZ = 8.1 |
| * |<---LENGTH (ME= 0.30 --->| RY = 2.9 |
|************* RZ = 1.5 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L11 -------------|
| KL/R-Y= 10.3 | FA = 150.0 |
| KL/R-Z= 20.7 + L11 fa = 0.0 |
| UNL = 300.0 | FCZ = 146.7 |
| C = 400.0 + L11 FTZ = 165.0 |
| CMY = 0.56 | L9 L9 FCY = 165.0 |
| CMZ = 0.49 + L11 FTY = 165.0 |
| FYLD = 249.9 | L9 L8 L8 L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS 7.1.2 BEND C 0.003 11 |
| 0.00 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 14 of 64
Monday, March 30, 2020, 07:13 PM

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 6 * | INDIAN SECTIONS | AX = 11.4 |
| * | ST ISA75X75X8 | --Z AY = 4.0 |
|DESIGN CODE * | | AZ = 4.0 |
| IS-800 * =============================== |
| * SZ = 8.1 |
| * |<---LENGTH (ME= 0.30 --->| RY = 2.9 |
|************* RZ = 1.5 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 10.3 | FA = 150.0 |
| KL/R-Z= 20.7 + L8 L7 fa = 0.1 |
| UNL = 300.0 | L11 L11 FCZ = 146.7 |
| C = 400.0 + L11 L11 FTZ = 165.0 |
| CMY = 0.56 | FCY = 165.0 |
| CMZ = 0.52 + L9 L7 FTY = 165.0 |
| FYLD = 249.9 | L8 L8 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.3 0.0 0.0 |
| LOADING 8 8 11 11 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.001 8 |
| 0.07 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 9 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 15 of 64
Monday, March 30, 2020, 07:13 PM
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | L10 IN NEWT MM|
|--------------- + L11 -------------|
| KL/R-Y= 17.6 | L10 FA = 142.2 |
| KL/R-Z= 35.6 + L11 fa = 2.9 |
| UNL = 449.0 | L10 FCZ = 137.5 |
| C = 180.0 + L11 FTZ = 165.0 |
| CMY = 0.88 | L10 FCY = 165.0 |
| CMZ = 0.47 + L9 FTY = 165.0 |
| FYLD = 249.9 | L9 L10 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.6 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.0 0.0 |
| LOADING 8 10 11 8 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.024 8 |
| 2.13 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 10 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== |
| * SZ = 4.7 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L10 L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.2 |
| UNL = 449.0 | L10 L11 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.81 | L10 L11 FCY = 165.0 |
| CMZ = 0.95 + L8 FTY = 165.0 |
| FYLD = 249.9 | L8 L8 fbz = 0.2 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 16 of 64
Monday, March 30, 2020, 07:13 PM
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.7 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.0 0.4 |
| LOADING 8 11 10 10 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.017 8 |
| 1.66 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 11 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== |
| * SZ = 4.7 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM |L11 IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.2 |
| UNL = 449.0 | L11 L10 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.76 | L10 L10 FCY = 165.0 |
| CMZ = 0.58 + L10 L11 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.6 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.0 0.4 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 17 of 64
Monday, March 30, 2020, 07:13 PM
| LOADING 8 10 11 11 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.017 8 |
| 1.61 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 12 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== |
| * SZ = 4.7 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- +L10 L11 -------------|
| KL/R-Y= 17.6 | FA = 142.2 |
| KL/R-Z= 35.6 + L10 L11 fa = 1.5 |
| UNL = 449.0 | FCZ = 137.5 |
| C = 180.0 + L11 L11 L11 FTZ = 165.0 |
| CMY = 0.83 | L11 FCY = 165.0 |
| CMZ = 0.71 + L10 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.0 0.4 |
| LOADING 8 11 10 10 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.012 8 |
| 1.13 C 0.0 0.0 0.00 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 18 of 64
Monday, March 30, 2020, 07:13 PM
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 13 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM |L11 IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 L10 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 0.7 |
| UNL = 449.0 | L11 L10 FCZ = 137.5 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L10 L10 FCY = 165.0 |
| CMZ = 0.49 + FTY = 165.0 |
| FYLD = 249.9 | L10 L11 fbz = 0.6 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.0 0.4 0.4 |
| LOADING 8 10 11 11 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.012 11 |
| 0.56 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 19 of 64
Monday, March 30, 2020, 07:13 PM
| * |=============================| ------------ |
|MEMBER 14 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.53 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L11 -------------|
| KL/R-Y= 21.0 | FA = 137.8 |
| KL/R-Z= 42.4 + L10 fa = 0.7 |
| UNL = 534.0 | FCZ = 136.3 |
| C = 180.0 + L11 FTZ = 165.0 |
| CMY = 0.49 | L11 L11 FCY = 165.0 |
| CMZ = 0.55 + L11 L11 L10 L10 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.5 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.6 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.5 0.5 0.0 |
| LOADING 10 10 11 11 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 10 |
| 0.55 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 15 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L11 STRESSES |
|IN NEWT MM | IN NEWT MM|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 20 of 64
Monday, March 30, 2020, 07:13 PM
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.0 |
| UNL = 449.0 | L11 FCZ = 137.5 |
| C = 400.0 + FTZ = 165.0 |
| CMY = 0.74 |L9 L9 L11 FCY = 165.0 |
| CMZ = 0.99 + L9 L9 L9 FTY = 165.0 |
| FYLD = 249.9 | L9 L11 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.5 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.4 0.4 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.016 10 |
| 1.46 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 16 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 1.9 |
| UNL = 449.0 | L11 FCZ = 137.5 |
| C = 180.0 + L11 L11 FTZ = 165.0 |
| CMY = 0.74 | L11 L11 FCY = 165.0 |
| CMZ = 0.55 + L11 FTY = 165.0 |
| FYLD = 249.9 | L8 L8 L11 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 21 of 64
Monday, March 30, 2020, 07:13 PM
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.016 10 |
| 1.43 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 17 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 1.3 |
| UNL = 449.0 | L11 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.74 |L9 L11 FCY = 165.0 |
| CMZ = 0.56 + L11 L11 L11 L9 FTY = 165.0 |
| FYLD = 249.9 | L9 L11 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.4 0.4 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 22 of 64
Monday, March 30, 2020, 07:13 PM
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 10 |
| 0.95 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 18 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 0.7 |
| UNL = 449.0 | L11 L11 L11 FCZ = 137.5 |
| C = 180.0 + L11 L11 FTZ = 165.0 |
| CMY = 0.47 | L11 L11 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L8 L8 fbz = 0.7 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.012 11 |
| 0.52 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 23 of 64
Monday, March 30, 2020, 07:13 PM

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 19 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L11 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 0.6 |
| UNL = 449.0 | L11 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.40 |L11L11 L11 L11 L11 FCY = 165.0 |
| CMZ = 0.45 + L11 FTY = 165.0 |
| FYLD = 249.9 | L9 L11 fbz = 0.5 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.6 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.4 0.4 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.010 11 |
| 0.44 C 0.0 0.0 0.45 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 20 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 24 of 64
Monday, March 30, 2020, 07:13 PM
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.53 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 21.0 | L11 FA = 137.8 |
| KL/R-Z= 42.4 + L9 fa = 0.7 |
| UNL = 534.0 | L9 FCZ = 136.3 |
| C = 180.0 + L11 L9 FTZ = 165.0 |
| CMY = 0.57 | L11 L11 FCY = 165.0 |
| CMZ = 0.52 + L9 L11 FTY = 165.0 |
| FYLD = 249.9 | L11 fbz = 0.5 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.6 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 11 |
| 0.54 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 21 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L11 L8 FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 L8 fa = 0.5 |
| UNL = 540.0 | L11 L8 FCZ = 145.6 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 25 of 64
Monday, March 30, 2020, 07:13 PM
| C = 400.0 + FTZ = 165.0 |
| CMY = 0.76 | L11 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.5 0.4 0.0 |
| LOADING 10 8 11 8 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 8 |
| 0.30 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 22 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 28.1 | FA = 125.9 |
| KL/R-Z= 56.3 + L8 fa = 0.7 |
| UNL = 540.0 | FCZ = 145.6 |
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.40 | L8 L10 L10 FCY = 165.0 |
| CMZ = 0.40 + L10 L10 L7 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 26 of 64
Monday, March 30, 2020, 07:13 PM
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 8 10 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.009 10 |
| 0.41 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 23 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L10 FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 L8 L8 fa = 0.5 |
| UNL = 540.0 | L8 FCZ = 145.6 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 8 7 8 7 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 27 of 64
Monday, March 30, 2020, 07:13 PM
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 8 |
| 0.26 C 0.0 0.0 0.41 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 24 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L8 FA = 125.9 |
| KL/R-Z= 56.3 + fa = 0.5 |
| UNL = 540.0 | L8 FCZ = 145.6 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L8 L10 L10 L10 L10 FCY = 165.0 |
| CMZ = 0.41 + FTY = 165.0 |
| FYLD = 249.9 | L9 L10 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 10 10 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 10 |
| 0.28 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 28 of 64
Monday, March 30, 2020, 07:13 PM

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 25 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L10 L8 FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 L8 L8 fa = 0.5 |
| UNL = 540.0 | FCZ = 145.6 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L10 L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 8 8 8 8 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 8 |
| 0.28 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 26 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 29 of 64
Monday, March 30, 2020, 07:13 PM
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L11 L11 L11 L11 FA = 150.0 |
| KL/R-Z= 56.3 + L11 fa = 0.4 |
| UNL = 540.0 | L11 FCZ = 145.6 |
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.47 | L11 FCY = 165.0 |
| CMZ = 0.54 + L8 FTY = 165.0 |
| FYLD = 249.9 | L11 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 8 11 7 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.005 8 |
| 0.24 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 27 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.61 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 31.8 | L10 FA = 118.2 |
| KL/R-Z= 63.8 + fa = 0.5 |
| UNL = 612.5 | FCZ = 144.1 |
| C = 180.0 + L10 L11 FTZ = 165.0 |
| CMY = 0.40 | FCY = 165.0 |
| CMZ = 0.77 + L10 L10 L10 L10 L11 FTY = 165.0 |
| FYLD = 249.9 | L11 L9 fbz = 0.2 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 30 of 64
Monday, March 30, 2020, 07:13 PM
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.6 0.0 |
| LOADING 8 10 11 11 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.006 8 |
| 0.31 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 28 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L10 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.8 |
| UNL = 449.0 | L10 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.95 | L9 L9 FCY = 165.0 |
| CMZ = 0.61 + L9 L10 L10 L10 FTY = 165.0 |
| FYLD = 249.9 | L8 L10 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 2.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 31 of 64
Monday, March 30, 2020, 07:13 PM
| LOADING 9 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.024 9 |
| 2.11 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 29 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== |
| * SZ = 4.7 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 17.6 | FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.5 |
| UNL = 449.0 | L10 FCZ = 137.5 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.88 | FCY = 165.0 |
| CMZ = 0.70 +L9 L9 L9 L9 L10 FTY = 165.0 |
| FYLD = 249.9 | L9 L9 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.4 0.4 |
| LOADING 8 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.019 8 |
| 1.85 C 0.0 0.0 0.00 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 32 of 64
Monday, March 30, 2020, 07:13 PM
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 30 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L10 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.1 |
| UNL = 449.0 | L10 L10 L10 FCZ = 137.5 |
| C = 180.0 + L10 L10 FTZ = 165.0 |
| CMY = 0.86 | L10 L10 FCY = 165.0 |
| CMZ = 0.76 + FTY = 165.0 |
| FYLD = 249.9 | L8 L8 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.6 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.017 9 |
| 1.59 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 33 of 64
Monday, March 30, 2020, 07:13 PM
| * |=============================| ------------ |
|MEMBER 31 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== |
| * SZ = 4.7 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 17.6 | FA = 142.2 |
| KL/R-Z= 35.6 + L10 fa = 1.8 |
| UNL = 449.0 | FCZ = 137.5 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.77 |L10L10 L10 FCY = 165.0 |
| CMZ = 0.65 + L10 L10 FTY = 165.0 |
| FYLD = 249.9 | L9 L9 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.4 0.4 0.4 0.4 |
| LOADING 8 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.013 8 |
| 1.33 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 32 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 34 of 64
Monday, March 30, 2020, 07:13 PM
|--------------- + -------------|
| KL/R-Y= 17.6 | L10 FA = 142.2 |
| KL/R-Z= 35.6 + L10 L10 L10 fa = 0.7 |
| UNL = 449.0 | L10 L10 FCZ = 137.5 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L10 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L8 L10 fbz = 0.7 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.013 10 |
| 0.55 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 33 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.53 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 21.0 | L10 FA = 137.8 |
| KL/R-Z= 42.4 + fa = 0.6 |
| UNL = 534.0 | FCZ = 136.3 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 |L8 L10 L10 L10 L10 FCY = 165.0 |
| CMZ = 0.47 + L8 FTY = 165.0 |
| FYLD = 249.9 | L10 L8 fbz = 0.6 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 35 of 64
Monday, March 30, 2020, 07:13 PM
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.8 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.5 0.5 0.5 0.5 |
| LOADING 8 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 10 |
| 0.46 C 0.0 0.0 0.53 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 40 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 17.6 | L9 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.6 |
| UNL = 449.0 | L8 FCZ = 137.5 |
| C = 180.0 + L9 L8 FTZ = 165.0 |
| CMY = 0.89 | L8 FCY = 165.0 |
| CMZ = 0.63 + L8 FTY = 165.0 |
| FYLD = 249.9 | L9 L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 9 10 8 9 |
| |
|**************************************************************************|
|* *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 36 of 64
Monday, March 30, 2020, 07:13 PM
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.022 9 |
| 1.91 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 41 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L8 STRESSES |
|IN NEWT MM | L8 IN NEWT MM|
|--------------- + L8 L8 -------------|
| KL/R-Y= 17.6 | L8 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 2.5 |
| UNL = 449.0 | L8 L8 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.94 | L8 FCY = 165.0 |
| CMZ = 0.87 + L8 L8 FTY = 165.0 |
| FYLD = 249.9 |L10 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.4 |
| LOADING 9 8 10 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.020 9 |
| 1.88 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 37 of 64
Monday, March 30, 2020, 07:13 PM

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 42 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | L9 IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 17.6 | FA = 142.2 |
| KL/R-Z= 35.6 + L9 fa = 1.9 |
| UNL = 449.0 | L9 FCZ = 137.5 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.85 | L9 L8 FCY = 165.0 |
| CMZ = 0.73 + L8 L8 FTY = 165.0 |
| FYLD = 249.9 | L8 L8 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 10 10 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.016 9 |
| 1.40 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 43 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 38 of 64
Monday, March 30, 2020, 07:13 PM
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L8 STRESSES |
|IN NEWT MM |L9 L8 IN NEWT MM|
|--------------- + L9 L8 -------------|
| KL/R-Y= 17.6 | L8 FA = 142.2 |
| KL/R-Z= 35.6 + L9 L8 fa = 1.8 |
| UNL = 449.0 | L9 FCZ = 137.5 |
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.86 | L9 FCY = 165.0 |
| CMZ = 0.59 + FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 1.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.4 |
| LOADING 9 11 10 9 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.015 9 |
| 1.34 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 44 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.45 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L9 L8 -------------|
| KL/R-Y= 17.6 | L9 L8 FA = 142.2 |
| KL/R-Z= 35.6 + fa = 1.2 |
| UNL = 449.0 | L9 L8 FCZ = 137.5 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 39 of 64
Monday, March 30, 2020, 07:13 PM
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.70 | L9 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.3 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.9 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 9 |
| 0.86 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 45 * | INDIAN SECTIONS | AX = 7.4 |
| * | ST ISA65X65X6 | --Z AY = 2.6 |
|DESIGN CODE * | | AZ = 2.6 |
| IS-800 * =============================== SY = 10.4 |
| * SZ = 6.1 |
| * |<---LENGTH (ME= 0.53 --->| RY = 2.5 |
|************* RZ = 1.3 |
| |
| 0.0( KN-METR) |
|PARAMETER | L8 STRESSES |
|IN NEWT MM | L8 IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 21.0 |L8 L8 FA = 137.8 |
| KL/R-Z= 42.4 + L8 fa = 1.0 |
| UNL = 534.0 | FCZ = 136.3 |
| C = 180.0 + L8 L8 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L9 L8 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 40 of 64
Monday, March 30, 2020, 07:13 PM
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.8 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.5 0.5 |
| LOADING 9 8 8 9 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.010 9 |
| 0.76 C 0.0 0.0 0.53 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 46 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L8 FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 fa = 0.8 |
| UNL = 540.0 | L8 L8 L8 FCZ = 145.6 |
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.65 | FCY = 165.0 |
| CMZ = 0.40 + L8 L11 FTY = 165.0 |
| FYLD = 249.9 | L11 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.5 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 11 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 41 of 64
Monday, March 30, 2020, 07:13 PM
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.009 11 |
| 0.46 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 47 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 28.1 | FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 fa = 0.1 |
| UNL = 540.0 | L8 L8 FCZ = 145.6 |
| C = 400.0 + L8 FTZ = 165.0 |
| CMY = 0.40 | L9 L8 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 1.0 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.6 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 11 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 8 |
| 0.05 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 42 of 64
Monday, March 30, 2020, 07:13 PM

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 48 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 28.1 | L8 FA = 125.9 |
| KL/R-Z= 56.3 + L8 fa = 0.0 |
| UNL = 540.0 | L8 L8 FCZ = 145.6 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.40 | L8 L8 FCY = 165.0 |
| CMZ = 0.40 + L9 FTY = 165.0 |
| FYLD = 249.9 | L9 L9 fbz = 0.8 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 11 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.008 8 |
| 0.02 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 49 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 43 of 64
Monday, March 30, 2020, 07:13 PM
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 28.1 | FA = 125.9 |
| KL/R-Z= 56.3 + L8 L8 L8 fa = 0.0 |
| UNL = 540.0 | L8 FCZ = 145.6 |
| C = 400.0 + L8 L8 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.40 + L9 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.6 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.4 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 9 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.006 8 |
| 0.02 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 50 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L8 FA = 125.9 |
| KL/R-Z= 56.3 + fa = 0.5 |
| UNL = 540.0 | L8 L8 L8 L8 FCZ = 145.6 |
| C = 180.0 + L8 FTZ = 165.0 |
| CMY = 0.40 | L8 L9 FCY = 165.0 |
| CMZ = 0.40 + L9 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.2 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 44 of 64
Monday, March 30, 2020, 07:13 PM
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 9 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.006 9 |
| 0.28 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 51 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L8 FA = 150.0 |
| KL/R-Z= 56.3 + fa = 0.4 |
| UNL = 540.0 | L8 L8 L8 L8 FCZ = 145.6 |
| C = 400.0 + L8 FTZ = 165.0 |
| CMY = 0.46 | L8 L8 FCY = 165.0 |
| CMZ = 0.55 + L10 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.4 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.5 0.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 45 of 64
Monday, March 30, 2020, 07:13 PM
| LOADING 9 8 8 8 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.006 9 |
| 0.24 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 52 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.61 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 31.8 | L8 FA = 118.2 |
| KL/R-Z= 63.8 + fa = 0.6 |
| UNL = 612.5 | L8 FCZ = 144.1 |
| C = 180.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.76 + L8 L8 L8 L10 FTY = 165.0 |
| FYLD = 249.9 | L9 L9 fbz = 0.2 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.6 0.0 |
| LOADING 9 8 10 10 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 9 |
| 0.31 C 0.0 0.0 0.00 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 46 of 64
Monday, March 30, 2020, 07:13 PM
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 53 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 28.1 | L9 L9 L9 FA = 125.9 |
| KL/R-Z= 56.3 + L9 fa = 0.8 |
| UNL = 540.0 | L9 FCZ = 145.6 |
| C = 180.0 + L9 FTZ = 165.0 |
| CMY = 0.62 | FCY = 165.0 |
| CMZ = 0.40 + L8 L10 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.5 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.009 10 |
| 0.47 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 47 of 64
Monday, March 30, 2020, 07:13 PM
| * |=============================| ------------ |
|MEMBER 54 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 28.1 | FA = 125.9 |
| KL/R-Z= 56.3 + L9 L9 fa = 0.1 |
| UNL = 540.0 | L9 FCZ = 145.6 |
| C = 180.0 + L9 L9 FTZ = 165.0 |
| CMY = 0.40 | L9 FCY = 165.0 |
| CMZ = 0.40 + L8 L8 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 1.0 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.6 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 10 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.011 9 |
| 0.04 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 55 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 48 of 64
Monday, March 30, 2020, 07:13 PM
|--------------- + -------------|
| KL/R-Y= 28.1 | L9 L9 FA = 125.9 |
| KL/R-Z= 56.3 + L9 fa = 0.1 |
| UNL = 540.0 | L9 L9 FCZ = 145.6 |
| C = 180.0 + L9 FTZ = 165.0 |
| CMY = 0.40 | L9 L9 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L10 L10 fbz = 0.7 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.5 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 10 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.008 9 |
| 0.03 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 56 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L9 FA = 125.9 |
| KL/R-Z= 56.3 + L9 L9 fa = 0.5 |
| UNL = 540.0 | L9 L9 FCZ = 145.6 |
| C = 180.0 + L9 FTZ = 165.0 |
| CMY = 0.40 | L9 L9 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 49 of 64
Monday, March 30, 2020, 07:13 PM
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 8 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.006 8 |
| 0.27 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 57 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L9 FA = 125.9 |
| KL/R-Z= 56.3 + L9 fa = 0.4 |
| UNL = 540.0 | L9 L9 L9 FCZ = 145.6 |
| C = 180.0 + L9 FTZ = 165.0 |
| CMY = 0.40 | L9 L9 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L10 L10 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 8 9 9 9 9 |
| |
|**************************************************************************|
|* *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 50 of 64
Monday, March 30, 2020, 07:13 PM
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 10 |
| 0.22 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 58 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L9 FA = 125.9 |
| KL/R-Z= 56.3 + fa = 0.5 |
| UNL = 540.0 | L9 L9 L9 FCZ = 145.6 |
| C = 180.0 + L8 L8 L9 FTZ = 165.0 |
| CMY = 0.40 | L9 FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.5 0.0 |
| LOADING 8 9 9 8 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 8 |
| 0.28 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 51 of 64
Monday, March 30, 2020, 07:13 PM

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 59 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.61 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 31.8 | L8 FA = 150.0 |
| KL/R-Z= 63.8 + fa = 0.4 |
| UNL = 612.5 | L8 FCZ = 144.1 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.68 | L8 L8 L8 L8 L8 FCY = 165.0 |
| CMZ = 0.51 + L10 FTY = 165.0 |
| FYLD = 249.9 | L10 L8 fbz = 0.5 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.6 0.0 0.0 0.4 0.0 |
| LOADING 8 8 9 9 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.006 8 |
| 0.25 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 60 * | INDIAN SECTIONS | AX = 11.4 |
| * | ST ISA75X75X8 | --Z AY = 4.0 |
|DESIGN CODE * | | AZ = 4.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 52 of 64
Monday, March 30, 2020, 07:13 PM
| IS-800 * =============================== |
| * SZ = 8.1 |
| * |<---LENGTH (ME= 0.30 --->| RY = 2.9 |
|************* RZ = 1.5 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 10.3 | FA = 150.0 |
| KL/R-Z= 20.7 + L10 L8 fa = 0.0 |
| UNL = 300.0 | L8 L8 FCZ = 146.7 |
| C = 400.0 + L10 L8 FTZ = 165.0 |
| CMY = 0.54 | L8 FCY = 165.0 |
| CMZ = 0.46 + L10 FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 8 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS 7.1.2 BEND C 0.003 10 |
| 0.01 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 61 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L10 L10 L8 FA = 125.9 |
| KL/R-Z= 56.3 + L10 L10 fa = 0.1 |
| UNL = 540.0 | L10 FCZ = 145.6 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 53 of 64
Monday, March 30, 2020, 07:13 PM
| C = 400.0 + FTZ = 165.0 |
| CMY = 0.49 | L10 L10 FCY = 165.0 |
| CMZ = 0.40 + L9 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.7 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 11 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.008 10 |
| 0.06 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 62 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 28.1 | FA = 125.9 |
| KL/R-Z= 56.3 + L10 fa = 0.1 |
| UNL = 540.0 | L10 FCZ = 145.6 |
| C = 180.0 + L10 L10 FTZ = 165.0 |
| CMY = 0.40 | L10 FCY = 165.0 |
| CMZ = 0.40 + L10 L9 L9 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.9 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.5 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 54 of 64
Monday, March 30, 2020, 07:13 PM
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.4 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 11 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.010 10 |
| 0.04 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 63 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L10 -------------|
| KL/R-Y= 28.1 | FA = 150.0 |
| KL/R-Z= 56.3 + L10 L10 L10 fa = 0.4 |
| UNL = 540.0 | L10 FCZ = 145.6 |
| C = 400.0 + L10 L10 FTZ = 165.0 |
| CMY = 0.51 | L9 L10 FCY = 165.0 |
| CMZ = 0.57 + FTY = 165.0 |
| FYLD = 249.9 | L8 fbz = 0.7 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 11 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 55 of 64
Monday, March 30, 2020, 07:13 PM
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.007 9 |
| 0.24 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 64 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L10 FA = 125.9 |
| KL/R-Z= 56.3 + fa = 0.5 |
| UNL = 540.0 | L10 L10 FCZ = 145.6 |
| C = 180.0 + L10 L9 L9 L10 FTZ = 165.0 |
| CMY = 0.40 | FCY = 165.0 |
| CMZ = 0.42 + L10 L9 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 11 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.007 11 |
| 0.28 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 56 of 64
Monday, March 30, 2020, 07:13 PM

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 65 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 28.1 | FA = 150.0 |
| KL/R-Z= 56.3 + L9 fa = 0.4 |
| UNL = 540.0 | FCZ = 145.6 |
| C = 400.0 + L9 L10 L10 L10 L10 FTZ = 165.0 |
| CMY = 0.66 | L10 FCY = 165.0 |
| CMZ = 0.58 + L9 FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 0.6 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.5 0.0 0.0 0.0 0.0 |
| LOADING 9 10 10 10 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.006 9 |
| 0.25 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 66 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.54 --->| RY = 1.9 |
|************* RZ = 1.0 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 57 of 64
Monday, March 30, 2020, 07:13 PM
| |
| 0.0( KN-METR) |
|PARAMETER |L10 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 28.1 | L10 FA = 125.9 |
| KL/R-Z= 56.3 + L9 L9 L9 L9 fa = 0.5 |
| UNL = 540.0 | L10 L9 FCZ = 145.6 |
| C = 180.0 + FTZ = 165.0 |
| CMY = 0.40 | L9 FCY = 165.0 |
| CMZ = 0.40 + L10 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.5 0.0 |
| LOADING 9 9 9 9 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.008 9 |
| 0.27 C 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 67 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.61 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 31.8 | L9 FA = 150.0 |
| KL/R-Z= 63.8 + fa = 0.4 |
| UNL = 612.5 | L9 FCZ = 144.1 |
| C = 400.0 + FTZ = 165.0 |
| CMY = 0.50 | L9 FCY = 165.0 |
| CMZ = 0.57 + L9 L9 L9 FTY = 165.0 |
| FYLD = 249.9 | L8 L8 L9 L8 fbz = 0.5 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 58 of 64
Monday, March 30, 2020, 07:13 PM
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.0 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -0.3 0.0 0.0 0.0 0.0 |
| LOCATION 0.6 0.0 0.0 0.5 0.0 |
| LOADING 9 9 11 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.006 9 |
| 0.25 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 68 * | INDIAN SECTIONS | AX = 11.4 |
| * | ST ISA75X75X8 | --Z AY = 4.0 |
|DESIGN CODE * | | AZ = 4.0 |
| IS-800 * =============================== SY = 18.0 |
| * SZ = 11.0 |
| * |<---LENGTH (ME= 0.30 --->| RY = 2.9 |
|************* RZ = 1.5 |
| |
| 0.0( KN-METR) |
|PARAMETER |L9 L9 L9 STRESSES |
|IN NEWT MM | L9 IN NEWT MM|
|--------------- + L9 -------------|
| KL/R-Y= 10.3 | L9 L9 FA = 148.2 |
| KL/R-Z= 20.7 + fa = 0.1 |
| UNL = 300.0 | FCZ = 146.7 |
| C = 180.0 + L9 L9 FTZ = 165.0 |
| CMY = 0.40 | FCY = 165.0 |
| CMZ = 0.40 + L8 FTY = 165.0 |
| FYLD = 249.9 | L9 fbz = 0.1 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.2 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.1 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.3 0.3 0.3 0.3 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 59 of 64
Monday, March 30, 2020, 07:13 PM
| LOADING 9 9 9 9 9 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.002 9 |
| 0.06 C 0.0 0.0 0.30 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 69 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.30 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER | L10 STRESSES |
|IN NEWT MM |L10 IN NEWT MM|
|--------------- + L10 L10 -------------|
| KL/R-Y= 15.6 | L10 FA = 150.0 |
| KL/R-Z= 31.2 + L10 fa = 0.0 |
| UNL = 300.0 | L10 L10 FCZ = 149.7 |
| C = 400.0 + L10 FTZ = 165.0 |
| CMY = 0.40 | L10 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 1.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.2 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.0 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.3 0.3 0.0 0.3 |
| LOADING 0 10 10 10 10 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.012 10 |
| 0.00 T 0.0 0.0 0.30 |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 60 of 64
Monday, March 30, 2020, 07:13 PM
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 70 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== |
| * SZ = 2.7 |
| * |<---LENGTH (ME= 0.30 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L11 STRESSES |
|IN NEWT MM | L11 L11 IN NEWT MM|
|--------------- + -------------|
| KL/R-Y= 15.6 | L11 L11 FA = 150.0 |
| KL/R-Z= 31.2 + L11 fa = 0.0 |
| UNL = 300.0 | L11 FCZ = 149.7 |
| C = 400.0 + L11 FTZ = 165.0 |
| CMY = 0.40 | L11 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L11 L9 fbz = 0.8 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 1.1 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.2 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.0 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.3 0.3 0.0 0.0 |
| LOADING 0 11 11 11 11 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.2 0.011 11 |
| 0.00 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 61 of 64
Monday, March 30, 2020, 07:13 PM
| * |=============================| ------------ |
|MEMBER 71 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.30 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | IN NEWT MM|
|--------------- + L8 -------------|
| KL/R-Y= 15.6 | L8 L8 FA = 150.0 |
| KL/R-Z= 31.2 + L8 fa = 0.0 |
| UNL = 300.0 | L8 L8 FCZ = 149.7 |
| C = 400.0 + L8 L8 FTZ = 165.0 |
| CMY = 0.40 | L8 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L10 fbz = 1.3 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.0 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.0 0.0 0.0 |
| LOADING 0 8 9 9 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.010 8 |
| 0.00 T 0.0 0.0 0.00 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

STAAD.PRO CODE CHECKING - (IS-800 )


********************************************

|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CM UNIT |
| * |=============================| ------------ |
|MEMBER 72 * | INDIAN SECTIONS | AX = 5.7 |
| * | ST ISA50X50X6 | --Z AY = 2.0 |
|DESIGN CODE * | | AZ = 2.0 |
| IS-800 * =============================== SY = 5.9 |
| * SZ = 3.7 |
| * |<---LENGTH (ME= 0.30 --->| RY = 1.9 |
|************* RZ = 1.0 |
| |
| 0.0( KN-METR) |
|PARAMETER |L8 STRESSES |
|IN NEWT MM | L8 IN NEWT MM|

D:\Project-2020\2013-Perstorp-Elephant-66kV Switchyard,Ankleswar\Structural Design & Calculations\LA\STAAD\LA.anl


Page 62 of 64
Monday, March 30, 2020, 07:13 PM
|--------------- + L8 -------------|
| KL/R-Y= 15.6 | L8 FA = 150.0 |
| KL/R-Z= 31.2 + L8 fa = 0.0 |
| UNL = 300.0 | L8 L8 FCZ = 149.7 |
| C = 400.0 + L11 FTZ = 165.0 |
| CMY = 0.40 | L11 L8 FCY = 165.0 |
| CMZ = 0.40 + FTY = 165.0 |
| FYLD = 249.9 | L11 fbz = 0.5 |
| NSF = 1.0 +---+---+---+---+---+---+---+---+---+---| fby = 0.0 |
| DFF = 0.0 0.0 FV = 100.0 |
| dff = 0.0 ABSOLUTE MZ ENVELOPE fv = 0.1 |
| (WITH LOAD NO.) |
| |
| MAX FORCE/ MOMENT SUMMARY ( KN-METR) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.0 0.0 0.0 0.0 0.0 |
| LOCATION 0.0 0.0 0.3 0.3 0.0 |
| LOADING 0 8 11 11 8 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY ( KN-METR) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS IS-7.1.1(A) 0.006 11 |
| 0.00 T 0.0 0.0 0.30 |
|* *|
|**************************************************************************|
| |
|--------------------------------------------------------------------------|

************** END OF TABULATED RESULT OF DESIGN **************

76. STEEL TAKE OFF ALL

STEEL TAKE-OFF
--------------

PROFILE LENGTH(METE) WEIGHT(MTON)

ST ISA65X65X6 12.91 0.075


ST ISA75X75X8 1.20 0.011
ST ISA50X50X6 16.61 0.074
----------------
TOTAL = 0.160

************ END OF DATA FROM INTERNAL STORAGE ************

77. FINISH

*********** END OF THE STAAD.Pro RUN ***********

**** DATE= MAR 30,2020 TIME= 19:11:46 ****

************************************************************