Continuous Gas Weight Monitoring System


A comprehensive approach
to monitor weight of fire extinguishing agent
Introduction weight is to be measured. After Gas Weight Monitor. When the weight
measuring the weight, again cylinders of the gas is reduced below 10% or
Continuous Gas Weight Monitoring are to be re fixed and re 5% (according to the requirement of
System is used in Gas based Fire commissioned for proper function. standard and type of gas system - For
Extinguishing system like CO2, FE-13, CO2 gas 10%, and FM200/ NAF SIII
FM-200, Inert System, NAF S-III This is time-consuming process for gas 5%), the Low weight is indicated,
System, FE-227 System to monitor maintenance department with highly by means of LED indication.
weight of the agent in the cylinder to skilled manpower.
meet NFPA & OISD standard. Gas weight monitor Control Panel
System Description provides required supply for weight
Necessity of the System monitoring unit. This panel also
The system consists of supervises the wire connection for
As per the OISD standards 142 1996 open and short condition. On receipt
(Ref. Clause 7.2.2), Fixed Carbon di- 1. Continuous Gas Weight of Low weight Indication from the
oxide Fire Extinguishing system. e. Monitor Electronic LED Type cylinder bank; the panel gives Audio
Refilling: (Model No. CGWM-E) - Part and Visual Indication. 2 set of
No.IH007 potential free NO and NC contacts are
Loss in weight of cylinders shall be available for remote indication or any
checked once in 3 months. Refilling other relevant signaling.
should be done if loss in weight is ENDLINE PLUG LOW
WEIGHT

CONTINUOUS GAS WEIGHT MONITOR


CONTROL PANEL

more than 10%.


LAMP TEST ACKNOWLEDGE RESET

SHORT OPEN LOW WEIGHT SYSTEM ON


AGNI
CONTR

CHENNOLS

LOW
WEIGHT

AGNI
CONTR

CHENNOLS

LOW
WEIGHT

As per NFPA-12, quantity of gas MANIFOLD


AGNI
CONTR

CHENNOLS

LOW
WEIGHT

should be checked at least once in 6 AGNI


CONTR

CHENNOLS

months.

Advantage of the System

Fire extinguishing efficiency depends


on the correct design concentration of
FRAME

extinguishing gas. If the gas loss due


to leakage or any other reason,
cylinder has to be refilled for designed
quantity. It is very obvious, continuous
monitoring of the gas weight is 2. Continuous Gas Weight The panel works on 230 V AC or 24 V
required. Monitor Control Panel DC from Fire alarm panel. Maximum
(Model No. CGWM-CP) - 20 Nos. of gas weight monitor can be
This requirement is simply fulfilled by Part No.IH009 connected with the Control Panel.
Continuous Gas Weight Monitoring
System.
Working Principle
Without this system, once in 3 months
Each cylinder requires one Gas
/ 6 months each cylinder is to be
weight Monitor. The cylinder should
removed from the cylinder bank and
be fixed in hanging condition through
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

Continuous Gas Weight Monitoring System


MODEL No.:CGWM-E, PART No.: IH007
General ! Hanger rod of standard length is used
with ring to hang the cylinder.
! Low weight indication can be calibrated
Continuous Gas Weight Monitor is used in
gas based fixed fire extinguishing system at the site if required.
! Device is powered directly by two wires
like CO2, FE-13, FM 200, Inert Systems,
NAF SIII, FE 227 to monitor weight of the from Continuous Gas Weight Monitor
agent in the cylinder to meet the NFPA control panel model no. CGWM-CP.
! Plug in type simple connection from
requirement.
one device to another.
! One device is required for each
Features
cylinder
! 24V Signal supply is derived from
! LED indication for low weight of agent. control unit. No current consumption
! Cylinder ring matches the standard by Gas Weight Monitor during normal
thread of cylinder neck. condition. While low weight indication
! For non-standard threads, suitable ring is ON maximum current consumption
will be provided. will be 10mA.

CONTINUOUS GAS WEIGHT MONITOR


CONTROL PANEL:
MODEL No.:CGWM-CP, PART No.: IH009
General low weight indication per zone.
[Individual low weight indication is
available on gas weight monitor].
Continuous Gas Weight Monitor Control !
Panel supervise and indicate the status of This is single zone control panel.
gas weight monitors, which are holding the ! Inbuilt low weight indication buzzer
gas cylinders, used in gas based fire (intermediate tone).
suppression/ extinguishing system. ! Supervision facility for open and short
of connecting cable of gas weight
monitor.
Features ! Maximum gas weight monitor per unit
restricted to 20 nos.
! Input supply voltage available in 24V ! Provision of one set of low weight fault
DC / 230V AC / 110V AC, 50Hz repeating potential free NO and NC
! Operating voltage 24V DC. contact of rating 6 amp at 24V DC.
! ! Wall mounting type suitable for indoor
Lamp test, acknowledge and reset
control switches. application.
! ! Multi zones control panel are
System ON Green LED, Low weight
orange LED, open and short Yellow available.
LED.
! Inbuilt fault buzzer of continuous tone.
! Two wire style B wiring is provided to
connect gas weight monitor.
! Control Panel provides only common

OTHER MODELS
Continuous Gas Weight Continuous Gas Weight Continuous Gas Weight
Monitor—Mechanical Counter Weight Monitor—Bottom Resting Type Monitor—Mechanical Counter Weight
Type Type with explosion proof limit switch
Model No.CGWM-M Model No.CGWM-BR/M LED Model No.CGWM-M.ex

Company Registration No. 5717368 • V.A.T No. 883908672


Tel: 00-44-8450751042 • Fax: 00-44-8450751043 • Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4PY | UNITED KINGDOM

Continuous Gas Weight Monitor


Model No.: CGWM-E, Part No.: IH007
Continuous Gas Weight Monitor monitors the
weight of agent continuously and gives alarm if
agent [CO2] weight is reduced below 10% or
Agent [Halocarbon] weight is reduced below 5%.

Construction
Gas Weight Monitor consists of calibrated spring,
low weight switch contact, 5 mm yellow LED to
indicate low weight. 18 gauge MS sheet
enclosure suitable for indoor application. Center
shaft moves through solid MS bas carries the
hanger supporter. Hangers with ring hold the
cylinder neck. Identical socket on both sides
provide easy connection from one device to
another.

Installation
Gas Weight Monitor is supported on the cylinder
rack as shown in the figure. Hanger support
piece is fixed on center rod using threads.
Cylinder is hanged using hanger ring. 2 pin
A GN
I CO
NT
CHE RO
NN LS
AI

connector is used to connect one device to


another. Last device is connected with 2 pin plug
wired with End Line Resistor.

Specification

24V Signal supply is derived from control unit. No


current consumption by Gas Weight Monitor
during normal condition. While low weight
indication is ON maximum current consumption
will be 10mA.

Size: 550mm Height x 90mm Width


Weight: 3.5kg.
Packing: Single Unit Packing and Double Unit.
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

CONTINUOUS GAS WEIGHT MONITORING SYSTEM


Introduction 1. Continuous Gas Weight Monitor
–Electronic LED Type (Model
Continuous Gas Weight Monitoring System is No. CGWM-E) - Part No.IH007
used in Gas based Fire Extinguishing system
like CO2, FE-13, FM-200, Inert System, NAF 2. Continuous Gas Weight Monitor
S-III System, FE-227 System to monitor Control Panel (Model No.
weight of the agent in the cylinder to meet CGWM-CP) - Part No.IH009
NFPA & OISD standard.
Necessity of the System
As per the OISD standards 142 – 1996 (Ref.
Clause 7.2.2), Fixed Carbon di-oxide Fire
Extinguishing system. e. Refilling:
Loss in weight of cylinders shall be checked
once in 3 months. Refilling should be done if
loss in weight is more than 10%.
As per NFPA-12, quantity of gas should be
checked at least once in 6 months. Working Principle
Advantage of the System Each cylinder requires one Gas weight
Monitor. The cylinder should be fixed in
Fire extinguishing efficiency depends on the hanging condition through Gas Weight
correct design concentration of extinguishing Monitor. When the weight of the gas is
gas. If the gas loss due to leakage or any reduced below 10% or 5% (according to
other reason, cylinder has to be refilled for the requirement of standard and type of
designed quantity. It is very obvious, gas system - For CO2 gas 10%, and
continuous monitoring of the gas weight is FM200/ NAF SIII gas 5%), the Low weight
required. is indicated, by means of LED indication.
This requirement is simply fulfilled by Gas weight monitor Control Panel
Continuous Gas Weight Monitoring System. provides required supply for weight
Without this system, once in 3 months / 6 monitoring unit. This panel also
months each cylinder is to be removed from supervises the wire connection for open
the cylinder bank and weight is to be and short condition. On receipt of Low
measured. After measuring the weight, again weight Indication from the cylinder bank;
cylinders are to be re fixed and re the panel gives Audio and Visual
commissioned for proper function. Indication. 2 set of potential free NO and
NC contacts are available for remote
This is time-consuming process for indication or any other relevant signaling.
maintenance department with highly skilled
manpower. The panel works on 230 V AC or 24 V DC
from Fire alarm panel. Maximum 20 Nos.
System Description of gas weight monitor can be connected
The system consists of with the Control Panel.

Company Registration No. 5717368 • V.A.T No. 883908672


Tel: 00-44-8450751042 • Fax: 00-44-8450751043 • Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4PY | UNITED KINGDOM

CONTINUOUS GAS WEIGHT MONITORING SYSTEM


Introduction System Description

Continuous Gas Weight Monitoring System is The system consists of


used in Gas based Fire Extinguishing system
like CO2, FE-13, FM-200, Inert System, NAF 1. Continuous Gas Weight Monitor
S-III System, FE-227 System to monitor –Electronic LED Type (Model
weight of the agent in the cylinder to meet No. CGWM-E) - Part No.IH007
NFPA & OISD standard.
2. Continuous Gas Weight Monitor
Necessity of the System Control Panel (Model No.
CGWM-CP) - Part No.IH009
As per the OISD standards 142 – 1996 (Ref.
Clause 7.2.2), Fixed Carbon di-oxide Fire Working Principle
Extinguishing system. e. Refilling:
Each cylinder requires one Gas weight
Loss in weight of cylinders shall be checked
Monitor. The cylinder should be fixed in
once in 3 months. Refilling should be done if
hanging condition through Gas Weight
loss in weight is more than 10%.
Monitor. When the weight of the gas is
As per NFPA-12, quantity of gas should be reduced below 10% or 5% (according to
checked at least once in 6 months. the requirement of standard and type of
gas system - For CO2 gas 10%, and
Advantage of the System FM200/ NAF SIII gas 5%), the Low weight
is indicated, by means of LED indication.
Fire extinguishing efficiency depends on the
correct design concentration of extinguishing Gas weight monitor Control Panel
gas. If the gas loss due to leakage or any provides required supply for weight
other reason, cylinder has to be refilled for monitoring unit. This panel also
designed quantity. It is very obvious, supervises the wire connection for open
continuous monitoring of the gas weight is and short condition. On receipt of Low
required. weight Indication from the cylinder bank;
the panel gives Audio and Visual
This requirement is simply fulfilled by Indication. 2 set of potential free NO and
Continuous Gas Weight Monitoring System. NC contacts are available for remote
indication or any other relevant signaling.
Without this system, once in 3 months / 6
months each cylinder is to be removed from The panel works on 230 V AC or 24 V DC
the cylinder bank and weight is to be from Fire alarm panel. Maximum 20 Nos.
measured. After measuring the weight, again of gas weight monitor can be connected
cylinders are to be re fixed and re with the Control Panel.
commissioned for proper function.

This is time-consuming process for


maintenance department with highly skilled
manpower.
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

INSTALLATION PROCEDURE FOR CONTINUOUS GAS


WEIGHT MONITORING SYSTEM
Installation Procedure
turn anti clockwise and Low Weight Indication
Continuous Gas Weight Monitor main unit referred will go). In order to check the system, while
as 1. is to be fixed in the channel referred as 2. by cylinder in hanging condition, if the cylinder is
using mounting nut referred as 3. After fixing the slightly raised around 5mm. then Low weight
main unit, fix cylinder hanger holder referred as 4. Indication will on. Again when the cylinder
Cylinder ring and holding rods, which are referred as lowered, Low weight Indication will go. Using
5&6, are to be fixed in the cylinder neck. Normally the connecting cables, which are
80mm Dia ring of standard thread to suit cylinder interchangeable, all gas weight monitors are
neck is supplied. (On specific requirement other size connected. The last gas weight monitor will be
cylinder rings will be made available.) After fixing the fitted with end line resistor plug. If this plug is
ring, cylinder hanger rod can be mounted on not fitted, control panel will show open
cylinder hanger plate. To lift the cylinder, using Allen Indication in the wiring circuit. No separate
key of size 14, cylinders can be raised or lowered. power is required. Only 2 core cable from control

CONTINUOUS GAS WEIGHT MONITOR


CONTROL PANEL

LAMP TEST ACKNOWLEDGE RESET

SHORT OPEN LOW WEIGHT SYSTEM ON


AGN
I CON
CHENTRO
LS
NAI

AGN
I CON
CHENTRO
LS
NAI

AGN
I CON
CHENTRO
LS
NAI

AGN
I CON
CHENTRO
LS
NAI

Commissioning panel is to be used as shown in the data


sheet / drawing.
Initially cylinder will be resting on the floor. Gas
Reference Documents :
Weight Monitor will show Low Indication. (If there is 1) Catalogue for Continuous Gas Weight Monitor,
no Low Indication, use field setting slot and specified Doc No. AC0002-11-2003
star screw driver turn clock wise and Low Weight 2) DataSheet for Continuous Gas Weight Monitor,
Drg No. 065
Indication will “ON”.) When Cylinder with correct 3) Catalogue for Continuous Gas Weight Monitor
weight gas is hanged Low Weight Indication will go. Control Panel, Doc No. AC0003-11-2003
(If Low weight indication is continued to “ON”, then 4) DataSheet for Continuous Gas Weight Monitor
Control Panel, Drg No. 003
using field setting slot and specified screw driver

Company Registration No. 5717368 • V.A.T No. 883908672


Tel: 00-44-8450751042 • Fax: 00-44-8450751043 • Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4PY | UNITED KINGDOM

CONTINUOUS GAS WEIGHT MONITOR CONTROL PANEL


MODEL No.: CGWM-CP, PART No.: IH009
General

DRAUGE IF Continuous Gas Weight Monitor


Control Panel supervise and indicate the status of
gas weight monitors, which are holding the gas
cylinders, used in gas based fire suppression/
extinguishing system.
Features
x Input supply voltage – available in 24V DC /
230V AC / 110V AC, 50Hz
x Operating voltage 24V DC.
x Lamp test, acknowledge and reset control
switches.
x System ON Green LED, Low weight orange
LED, open and short Yellow LED.
x Inbuilt fault buzzer of continuous tone.
x Two wire style B wiring is provided to connect
gas weight monitor.
x Control Panel provides only common low
weight indication per zone. [Individual low CONTINUOUS GAS WEIGHT MONITOR
CONTROL PANEL

weight indication is available on gas weight


monitor]. LAMP TEST ACKNOWLEDGE RESET

x This is single zone control panel. SHORT OPEN LOW WEIGHT SYSTEM ON

x Inbuilt low weight indication buzzer


(intermediate tone).
x Supervision facility for open and short of
connecting cable of gas weight monitor.
x Maximum gas weight monitor per unit
restricted to 20 nos.
x Provision of one set of low weight fault
repeating potential free NO and NC contact of
rating 6 amp at 24V DC.
x Wall mounting type suitable for indoor
application.
x Multi zones control panel are available.
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

CONTINUOUS GAS WEIGHT MONITOR


CONTROL PANEL - HORIZONTAL
DATA SHEET ROTIN M HG EW SA U C
-LENAPORTC LATNOZIRH

CONTINUOUS GAS WEIGHT MONITOR

#
CONTROL PANEL

TRANSFORMER SECONDARY

LAMP TEST ACKNOWLEDGE RESET


SPARE

SHORT OPEN LOW WEIGHT SYSTEM ON


POTENTIAL FREE NO & NC INPUT
OPEN / SHORT FAULT INDICATION

SPARE

POTENTIAL FREE NO & NC OUTPUT


LOW WEIGHT INDICATION

SPARE

TO WEIGHING DEVICE ##
SPARE

24V DC INPUT SUPPLY

EARTH

230V AC
INPUT SUPPLY

#
##

Company Registration No. 5717368 • V.A.T No. 883908672


Tel: 00-44-8450751042 • Fax: 00-44-8450751043 • Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4PY | UNITED KINGDOM

CONTINUOUS GAS WEIGHT MONITOR


ANALOGUE LED TYPE / ASSEMBLY DETAILS
R O T S I UH N G A M E W C
DATA SHEET
S L I A Y T E D UP B G M O / N
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

CONTINUOUS GAS WEIGHT MONITOR


ANALOGUE LED TYPE / ASSEMBLY DETAILS
R O T S I UH N G A M E W C
DATA SHEET
S L I A Y T E D UB P GM O / N

Company Registration No. 5717368 • V.A.T No. 883908672


Tel: 00-44-8450751042 • Fax: 00-44-8450751043 • Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4PY | UNITED KINGDOM

CONTINUOUS GAS WEIGHT MONITOR(MECHANICAL)


EXPLOSION PROOF TYPE - ASSEMBLY DETAILS
DATA SHEET )LACINHEM(ROTGWSU
-TYPEROFXLSIN DETAILSMBY
FIREGUARD SAFETY EQUIPMENT CO. LTD.

www.fireguard-uk.com

CONTINUOUS GAS WEIGHT MONITOR(MECHANICAL)


EXPLOSION PROOF TYPE - ASSEMBLY DETAILS
DATA SHEET )LACINHEM(ROTGWSU
-TYPEROFXLSIN DETAILSMBY

Company Registration No. 5717368 • V.A.T No. 883908672

You might also like