Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 15

Best relay protection

practices applied to shunt


reactors, capacitors, SVCs
and STATCOMs
By Edvard   | March, 11th 2020 | 3 comments  | Save to PDF
Share!    

Home / Technical Articles / Best relay protection practices applied to shunt reactors, capacitors, SVCs and

STATCOMs

Connections & required protections


This technical article explains the protection practices applied to shunt reactors
and capacitors as well as to static var compensators (SVCs) and static
compensators (STATCOMs). Dry-type and oil-immersed reactors usually use
overcurrent, negative sequence, percentage differential, or impedance relays
depending on some specific application.
Best relay protection practices applied to shunt reactors, capacitors, SVCs and
STATCOMs (on photo: Testing ABB RET670 transformer protection relay;
credit: Mahmoud Ahmed via Linkedin)
On the other hand, the main protection for capacitors is a function of their
installation within a station.

Capacitor overvoltage protection is provided by fuses supplied by


manufacturers. SVCs and STATCOMs are gaining increasing popularity as a
means of controlling both inductive and capacitive reactive deficiencies at the
point of their connection to the power system.

The protection is a combination of protection required for both reactors and


capacitors and the special requirements associated with the SVC and
STATCOM design.
This technical article also describes the possible protection schemes that
are required. It is important to note that SVC and STATCOM protection is a
complex combination involving station design, conventional equipment
protection and the specifics of the equipment design.
However, coordination with manufacturers is essential.

Table of contents:
1. Shunt reactor protection
1. Dry-type reactors
2. Oil-immersed reactors
2. Shunt capacitor bank protection
3. Static var compensator protection
1. Transformer protection
2. Bus protection
3. Typical protection schemes
4. Static compensator (STATCOM)
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">

1. Shunt reactor protection


Reactors are connected into a power system in either a series connection or a
shunt connection. The series reactor is used to modify the system reactance,
primarily to reduce the amount of short-circuit current available. The shunt
reactor is used to modify the system voltage by compensating for the
transmission line capacitance.

In general, the protection of reactors is very similar to that of transformers.

In considering the protection of shunt reactors, two configurations are involved:


The first one is dry-type, connected ungrounded-wye and connected to the
tertiary of a power transformer. The second configuration is oil-immersed, wye-
connected, with a solidly grounded or impedance-grounded neutral, connected
to the transmission system.
For both types of reactor construction, there are two more considerations that
have an effect on the protection.

1. Single-phase reactors, i.e. each phase is in its own tank. These are
usually applied on EHV transmission lines. There is no possibility of having a
phase-to-phase fault within the reactor enclosure although such a fault can
occur in the bus and bushings.
2. Three-phase reactors where all three windings are in the same tank.
These are primarily applied at lower voltages.

Figure 1 – Dry-
type shunt reactor connected to the power system between the phase and
ground phase and neutral point, phase and phase, and provides reactive
power. (photo credit: jwzn-teee.com)

Go back to contents ↑

1.1 Dry-type reactors


The faults encountered in dry-type reactors are the following.

1. Phase-to-phase faults on the tertiary bus, resulting in high-magnitude


phase current. These faults are rare since the phases of the reactors are
located physically at a considerable distance from each other.

2. Phase-to-ground faults on the tertiary bus resulting in low-magnitude fault


current depending on the size of the grounding transformer and resistor. These
faults are also rare since the reactors are mounted on insulators or supports
with standard clearances.
3. Turn-to-turn faults within the reactor bank, resulting in a very small
change in phase current. Winding insulation failures may begin as tracking due
to insulation deterioration which eventually will involve the entire winding.

The result is a phase-to-neutral fault which increases the current in the


unfaulted phases to a maximum of √3 times normal phase current.

Figure 2 – Overcurrent relaying


Fault protection for the dry-type reactor is achieved through overcurrent relays
connected as shown in Figure 2 and differential relays as shown in Figure 3.
This protection is the same as the overcurrent and differential relaying for
generators and transformers.

Overcurrent relays must be set above the normal reactor load current. They
can detect phase-to-phase faults, and phase-to-ground faults if the grounding
impedance is low enough, and turn-to-turn faults if enough turns are involved to
produce high enough fault currents.
Since phase-to-phase and phase-to-ground faults also produce negative
sequence currents, a negative sequence relay, connected the same as the
overcurrent relay, can be used. Load is not a consideration with negative
sequence, but there must be enough current to operate the relay.
Figure 3 – Percentage
differential relay
Differential relays can provide sensitive protection but they do not see turn-to-
turn faults since the current entering a reactor with shorted turns is equal to the
current leaving the reactor. Instantaneous relays are not usually applied since
the only fault location that will produce enough current to operate
an instantaneous relay is at the phase end of the reactor or in the bus or
bushings.

These fault locations are usually protected by the bus differential relay.

Go back to contents ↑

1.2 Oil-immersed reactors


The failures encountered with oil-immersed reactors are the following:

Failure № 1 – Faults resulting in large changes in the magnitude of phase


current such as bushing failures, insulation failures, etc. Because of the
proximity of the winding to the core and tank, phase-to-ground faults can occur,
the magnitude being dependent upon the location of the fault with respect to the
reactor bushing.
Failure № 2 – Turn-to-turn faults within the reactor winding, resulting in small
changes in the magnitude of phase current.
Failure № 3 – Miscellaneous failures such as loss of oil or cooling.
Relay protection for faults producing large magnitudes of phase current is
generally a combination of overcurrent, differential and distance relaying.
There are limitations to each of these protective schemes. Overcurrent relays
must be set above the normal load current and a differential relay cannot detect
a turn-to-turn fault.
An impedance relay can detect shorted turns since there is a significant
reduction in the 60 Hz impedance of a shunt reactor under such a condition.

Figure 4 shows the connection for an impedance relay (device 21). Protection
against low-level faults or mechanical failure involving the oil system is by
pressure, temperature or flow devices.

Figure 4 – Connection for impedance relay


One of the principal difficulties with shunt reactor protection is false relay
operation during energizing or de-energizing the iron core. During these
periods, DC offset with long time constants and low-frequency components of
the reactor energization current cause most of the problems.

High-impedance differential relays rather than low-impedance relays are


recommended if this problem occurs.

Go back to contents ↑
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">

2. Shunt capacitor bank protection


Capacitors are also installed as either a series or a shunt element in power
systems. The series capacitor is used primarily to modify the transmission line
reactance for stability or load flow considerations. The protection of fixed or
switched shunt capacitor banks requires an understanding of the capabilities
and limitations of both the capacitors and the associated switching devices.

Capacitor bank protective equipment must guard against a variety of


conditions:

Condition № 1 – Overcurrents due to faults between the bus and the


capacitor bank. The protection afforded is the conventional overcurrent relay
applied at the breaker feeding the capacitor bank.
Condition № 2 – System surge voltages. The protection afforded is
the conventional surge arresters  and spark gaps.
Condition № 3 – Overcurrents due to individual capacitor unit failure. The
manufacturer provides the necessary fuses to blow for an internal unit failure.
The fuse link should be capable of continuously carrying 125–135 % of the
rated capacitor current.
Condition № 4 – Continuous capacitor unit overvoltages.
Figure 5 shows the general arrangement for a high-voltage capacitor bank
consisting of parallel units to provide the required current capability and series
units to provide the desired capacitive rating.
Figure 5 – General
arrangement for a high-voltage capacitor bank
An overvoltage can be imposed across individual capacitor units as a result of
the loss of one or more units, usually by the operation of a unit fuse.

The overvoltage is the result of the increased impedance of the series section
from which the faulty unit has been removed. As units are removed, the
impedance of that section increases. However, since there are many sections in
series the effect of the increased impedance in one section does not decrease
the phase current in the same relative proportion.
The result of the slightly reduced current flowing through the more markedly
increased impedance causes a higher voltage to appear across the remaining
units in that section.

Go back to contents ↑

3. Static var compensator


protection
Static var compensators (SVCs) are devices which control the voltage at their
point of connection to the power system by adjusting their susceptance to
compensate for reactive power deficiencies. The basic reactive components of
SVCs are shunt reactors and shunt capacitors (Figure 6).

Reactor controls are either thyristor-controlled or thyristor-switched.


Capacitors are either fixed or thyristor-switched.

Figure 6 – Typical SVC installation


As the load varies, a variable voltage drop will occur in the system impedance.
This impedance is mainly reactive. Assuming the generator voltage remains
constant, the voltage at the load bus will vary. The voltage is a function of the
reactive component of the load current, and system and transformer reactance.

A SVC can compensate for the voltage drop for load variations and maintain
constant voltage by controlling the gating of thyristors in each cycle. With fixed
capacitors and variable reactors, leading or lagging current can be provided to
the bus and will correct the voltage drop or rise.

The protection scheme for SVCs is made up of a number of zones. In some


cases, faults in a zone should shut down the entire SVC system. In other cases,
the relaying can be coordinated so that only the faulted zone is cleared and the
SVC kept in operation with limited capabilities.
Sometimes, these protective functions can be provided as part of the integrated
protective system supplied by the manufacturer or they can be provided by the
user. In either case the settings must be coordinated between the manufacturer
and the user.

Go back to contents ↑

3.1 Transformer protection


Differential relays, phase and ground overcurrent relays, gas pressure, low oil
level and temperature relays have all been effectively applied in accordance
with standard transformer protection practice.

The transformer guide should be applied to transformers that are part of the
SVC. The connection of the transformer windings determines the types of relay
and their connection.

Recommended reading:

Go back to contents ↑

3.2 Bus protection


Phase fault protection
Conventional differential or time overcurrent relays are applicable. Time-
overcurrent relays are usually used for backup protection. For some
installations, the SVC bus is included in the protection zone of the transformer
differential relays.

Ground fault protection


The voltage supplied to SVC buses may be grounded through a resistance or
impedance in the main transformer or through a grounding transformer, or
ungrounded. Grounding transformers are sized such that ground fault currents
are limited to reduce damage, yet large enough to selectively operate ground
relays.

In addition, ground fault currents on the SVC low-voltage bus should be limited
to 500–1500 A to prevent thyristor valve damage.

Go back to contents ↑

3.3 Typical protection schemes


Typical protection schemes are as follows:

1. Time-overcurrent relays connected to CTs to measure the zero sequence


current in the main transformer or grounding transformer.
2. Time-overvoltage relays connected across the broken-delta secondary
winding of a voltage transformer as shown in Figure 7. This scheme does
not provide fast location of a fault since the ground fault could be anywhere
in the low-voltage bus or any of its branches.
Figure 7 – Broken delta-ground
detector

Overvoltage protection
In most installations, relays connected to the bus voltage transformers are
provided to protect the entire SVC system from excessive overvoltages. The
capacitors in the SVC are vulnerable to overvoltage and therefore determine
the relay settings.

Reactor branch protection


A thyristor-controlled or thyristor-switched reactor is usually considered a
separate zone of differential and coordinates with it. Conventional reactor
differential and overcurrent relays are used. In many designs, the reactor
branch is connected to the SVC bus by a relatively slow motor-operated
disconnect switch.

The relaying would then trip the SVC main breaker, the faulted element would
then be removed and the remainder of the SVC installation returned to service.

Capacitor branch protection


Conventional overvoltage and unbalance protection is applicable.

Filter protection
Switching of SVC elements will introduce harmonics into the power system.
Depending upon the particular design, the manufacturer must provide the
necessary filters and should provide, or recommend, the protection required.

The magnitude of the harmonic voltage generated depends on the type of SVC,
the SVC configuration, the system impedance and the amount of reactance
switched.

In TSC branches, air-core reactors connected in series with the capacitors limit
the rate of change of inrush current generated from switching. This series
combination also provides tuned frequency filtering to a specific harmonic order.
In TSR branches, the triple harmonic currents (3, 9, 15, etc.) are removed by
a delta or wye ungrounded connection.
The even harmonics are removed by symmetrical gating of the TCR thyristors.

Thyristor protection
This protection is normally provided as a part of the thyristor control system.
Typical protection is provided for overvoltage, overcurrent, temperature and,
where applicable, coolant flow and conductivity.

Go back to contents ↑

4. Static compensator (STATCOM)


A static compensator (STATCOM) provides variable reactive power from
lagging to leading, but with no inductors or capacitors for var generation. This
is achieved by regulating the terminal voltage of the converter.

The STATCOM consist of a voltage source inverter using gate turnoff


thyristors which produces an alternating voltage source in phase with the
transmission voltage, and is connected to the line through a series inductance.
If the terminal voltage of the voltage source is higher than the bus voltage,
STATCOM generates leading reactive power. If the voltage is lower than the
bus voltage, STATCOM generates lagging reactive power.
SVCs have generally proven to have lower equipment costs and lower losses.
STATCOMs have been used in transmission where land constraints, audible
noise or visual impact are of concern.

STATCOM can provide both reactive power absorption and production


capability whereas an SVC requires individual branches for capacitors for var
generation and reactors for var absorption.

Recommended reading:

Go back to contents ↑

Source:  Power system relaying by Stanley H. Horowitz and Arun G. Phadke

You might also like