Professional Documents
Culture Documents
Best Relay Protection Practices Applied To Shunt Reactor1w
Best Relay Protection Practices Applied To Shunt Reactor1w
Home / Technical Articles / Best relay protection practices applied to shunt reactors, capacitors, SVCs and
STATCOMs
Table of contents:
1. Shunt reactor protection
1. Dry-type reactors
2. Oil-immersed reactors
2. Shunt capacitor bank protection
3. Static var compensator protection
1. Transformer protection
2. Bus protection
3. Typical protection schemes
4. Static compensator (STATCOM)
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">
1. Single-phase reactors, i.e. each phase is in its own tank. These are
usually applied on EHV transmission lines. There is no possibility of having a
phase-to-phase fault within the reactor enclosure although such a fault can
occur in the bus and bushings.
2. Three-phase reactors where all three windings are in the same tank.
These are primarily applied at lower voltages.
Figure 1 – Dry-
type shunt reactor connected to the power system between the phase and
ground phase and neutral point, phase and phase, and provides reactive
power. (photo credit: jwzn-teee.com)
Go back to contents ↑
Overcurrent relays must be set above the normal reactor load current. They
can detect phase-to-phase faults, and phase-to-ground faults if the grounding
impedance is low enough, and turn-to-turn faults if enough turns are involved to
produce high enough fault currents.
Since phase-to-phase and phase-to-ground faults also produce negative
sequence currents, a negative sequence relay, connected the same as the
overcurrent relay, can be used. Load is not a consideration with negative
sequence, but there must be enough current to operate the relay.
Figure 3 – Percentage
differential relay
Differential relays can provide sensitive protection but they do not see turn-to-
turn faults since the current entering a reactor with shorted turns is equal to the
current leaving the reactor. Instantaneous relays are not usually applied since
the only fault location that will produce enough current to operate
an instantaneous relay is at the phase end of the reactor or in the bus or
bushings.
These fault locations are usually protected by the bus differential relay.
Go back to contents ↑
Figure 4 shows the connection for an impedance relay (device 21). Protection
against low-level faults or mechanical failure involving the oil system is by
pressure, temperature or flow devices.
Go back to contents ↑
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">
The overvoltage is the result of the increased impedance of the series section
from which the faulty unit has been removed. As units are removed, the
impedance of that section increases. However, since there are many sections in
series the effect of the increased impedance in one section does not decrease
the phase current in the same relative proportion.
The result of the slightly reduced current flowing through the more markedly
increased impedance causes a higher voltage to appear across the remaining
units in that section.
Go back to contents ↑
A SVC can compensate for the voltage drop for load variations and maintain
constant voltage by controlling the gating of thyristors in each cycle. With fixed
capacitors and variable reactors, leading or lagging current can be provided to
the bus and will correct the voltage drop or rise.
Go back to contents ↑
The transformer guide should be applied to transformers that are part of the
SVC. The connection of the transformer windings determines the types of relay
and their connection.
Recommended reading:
Go back to contents ↑
In addition, ground fault currents on the SVC low-voltage bus should be limited
to 500–1500 A to prevent thyristor valve damage.
Go back to contents ↑
Overvoltage protection
In most installations, relays connected to the bus voltage transformers are
provided to protect the entire SVC system from excessive overvoltages. The
capacitors in the SVC are vulnerable to overvoltage and therefore determine
the relay settings.
The relaying would then trip the SVC main breaker, the faulted element would
then be removed and the remainder of the SVC installation returned to service.
Filter protection
Switching of SVC elements will introduce harmonics into the power system.
Depending upon the particular design, the manufacturer must provide the
necessary filters and should provide, or recommend, the protection required.
The magnitude of the harmonic voltage generated depends on the type of SVC,
the SVC configuration, the system impedance and the amount of reactance
switched.
In TSC branches, air-core reactors connected in series with the capacitors limit
the rate of change of inrush current generated from switching. This series
combination also provides tuned frequency filtering to a specific harmonic order.
In TSR branches, the triple harmonic currents (3, 9, 15, etc.) are removed by
a delta or wye ungrounded connection.
The even harmonics are removed by symmetrical gating of the TCR thyristors.
Thyristor protection
This protection is normally provided as a part of the thyristor control system.
Typical protection is provided for overvoltage, overcurrent, temperature and,
where applicable, coolant flow and conductivity.
Go back to contents ↑
Recommended reading:
Go back to contents ↑