PID500 Full Featured Pid Temperature Controller: Description
PID500 Full Featured Pid Temperature Controller: Description
Description:
CONTROLLERS
Lower Display: 7mm high green LED (selectable)
Hysteresis: Programmable
Display alternating between
Annunciator: Programmable
! PV and '-AL1’ during AL1 alarm
Reset Action: Programmable: automatic or latched
PID
! PV and '-AL2' during AL2 alarm
Standby Mode: Programmable: enable or disable
! PV and 'AL12' during AL1 and AL2 alarm
Probe Break Action: Upscale
Tuning indicated by blinking decimal point.
LED Status Annunciators: 11. HEAT - COOL PID MODE: (Setting for set 2)
! Relay on Control: PID or ON/OFF
! Alarm Output: Time Proportioning
! Manual mode Cycle time: Programmable
SENSOR BREAK Indicated on display, relay off Proportional gain: Programmable
SENSOR REVERSE Indicated on display, relay off Heat/Cool Dead band Overlap: Programmable
12. REMOTE SET POINT INPUT: (optional)
2. POWER: Input type: 0/4 to 20mA
AC Versions: 85 VAC min. to 270 VAC max. @ 50 or 60 Hz, 5 VA Input Resistance: 100
max. Over range: -5% to 105%
DC Versions (Optional): 24VAC /DC (AC: 50/60Hz) Scale Range: -1999 to 9999 fixed 1oC for TC/RTD
(as per dp selected for AIN)
3. SETTINGS: Via four keys on front panel. 13. HEATER CURRENT MONITOR INPUT: (optional)
Type: Single phase, full wave
4. MEMORY: Nonvolatile EEPROM retains all programmable monitoring of load currents
parameters and values. controlled by main output.
Input: 100 mA AC output from current
5. MAIN SENSOR INPUT: (Universal) transformer
Sample period : 250msec Display Scale Range: 0.0 to 999.9 A
Digital Filtering : 0 to 99 sec Input Resistance: 47
Failed Sensor Response : Auto/Manual Accuracy: ±0.5 % of full scale ±1 Digit.
Main Control Output(s) : Programmable:- option to switch Frequency: 50 to 400 Hz.
to manual output at the last output Alarm Mode: LA / HA / BAND.
value. Over range: 105% Capacity
o
Temperature units : C / oF Overload: 150 mA (continuous).
Resolution : 1 / 0.1oC for TC/RTD
14. SERIAL COMMUNICATIONS: (optional)
1/0.1/0.01/0.001 for AIN.
Interface standard: RS485
Thermocouple
Communication Address: 1 to 99, max of 32 units per line
J : -200 to 750oC
Protocol: Modbus
K : -200 to 1350oC
T : -200 to 400oC 15. ENVIRONMENTAL CONDITIONS:
R : 0 to 1750oC Operating Range: 0 to 50oC
S : 0 to 1750oC Storage Range: -20 to 75oC
C : 0 to 2300oC Humidity: 85% max. RH
E : - 200 to 750oC (non-condensing) from 0 to 50oC
B : + 149 to 1820oC 16. ISOLATION BREAKDOWN RATINGS:
N : -200 to 1300oC AC line with respect to all inputs and outputs: 2000 Volts
L : - 200 to 900oC All other inputs and outputs with respect to relay contacts:
U : - 200 to 400oC 2000VAC
W : 0 to 2300oC
17. COMPLIANCE: CE
Platinel II : 0 to 1390oC
PT100 : -100 to 850oC 18. ELECTROMAGNETIC COMPATIBILITY:
NOTE: Other TCs / RTDs available on request. Emissions in compliance with BSEN 50081-2
Signal inputs RF interference: BSEN 55011
Linear mV : -5.00mV to 56 mV Power mains class A
Voltage : 0 to 10 V DC Enclosure class A
Current : 0 to 20mA DC Immunity in compliance with BSEN 50082-2
Electrostatic discharge: BSEN 61000-4-2
6. INDICATION ACCURACY: +/-0.25% of span or 1oC whichever is Level 2; 6 kV contact
greater (After 20min. warm-up) Level 3; 8 kV air
Electromagnetic RF fields: BSEN 61000-4-3
7. CONTROL AND ALARM OUTPUTS: (Heating, Cooling or Alarm) Level 3; 10 V/m
Relay output (Main): 5A @ 250VAC or 30VDC 80 MHz - 1 GHz
Aux / Alarm outputs: 5A @ 250VAC or 30VDC Fast transients (burst): BSEN 61000-4-4
Relay 3 (Alarm): 5A @ 250VAC or 30VDC Level 3; 2 kV power
Life expectancy: 100000 cycles at max. load rating RF conducted interference: BSEN 61000-4-6
Logic / SSR drive: main control output only Level 3; 3 V rms
150 KHz - 100 MHz
8. MAIN CONTROL: Power frequency magnetic fields: BSEN 61000-4-8
Control: PID or ON/OFF Level 4; 30 A/m
Output: Time proportioning or Linear DC Voltage dips / interference: BSEN 61000-4-11
Cycle time: Programmable Reduction 100%
Auto-tune: When selected, sets Proportional band, Integral Duration: 0.5 cycle / each polarity
time, Derivative time, Cycle time, and other 19. CONNECTION: Wire clamping screw terminals.
parameters.
20. WEIGHT: 195 grams.
Probe Break Action: Programmable % output
21. CONSTRUCTION:
9. ANALOG DC OUTPUT ( optional on Main control output / Black plastic alloy case and collar style panel latch.
Retransmission) Bezel assembly with circuit boards can be removed from
Range : 4 - 20 mA/ 0 - 10V / 0 - 5V the case to change the output board without removing the case
Action: Control or retransmission from the panel or disconnecting wiring. Unit meets IP66
Update rate: 100msec requirements for indoor use.
TERMINAL CONNECTIONS ORDERING CODE -
PID500-A-B-01 PID 500 A B XX
PID500-A-B-00 PID500-A-B-02
A : Output 1
L 1 11 6 N L 1 11 6 N
TC+ TC+ 0 Relay
NO2 / RTD1 NO2 / RTD1
2 12 7 SSR+ 2 12 7 12VDC
SSR+ 1
SSR drive 00 Only Output 1 & Output 2
COM2 / COM2 /
3 13 8 SSR - 3 13 8 2 Current
SSR -
TC TC 01 Output 3 ( Relay )
RTD2 3 Voltage
NO1 / RTD2 NO1 /
Output 3 (12VDC SSR drive )
SSR+ SSR+
4
NO3 /
14 9 02
ANA OP +
4 14 9 ANA OP + SSR+ RTD3
RTD3 03 Communication RS485
COM1 / COM1 / COM3 / B : Output 2
SSR - 5 15 10 SSR - 5 SSR - 15 10 04 Output 3 ( Relay ) +
ANA OP - ANA OP - 0 Relay Communication RS485
12VDC 05 Output 3 (12VDC SSR drive ) +
1 Communication RS485
PID500-A-B-04 SSR drive
PID500-A-B-03 PID500-A-B-05
06 CT Input
07 Output 3 ( Relay ) + CT Input
L 1 RS485 + 11 6 N L 1 RS485 + 11 6 N
08 Output 3 (12VDC SSR drive ) +
TC+ TC+ CT Input
NO2 /
RS485 - 12 RTD1 NO2 /
RS485 - 12 RTD1
SSR+ 2 7 SSR+ 2 7
09 CT Input + Communication RS485
COM2 / COM2 / Second Analog Input ( valve positioner
SSR - 3 13 8 SSR - 3 13 8 10
TC TC type )
NO1 / RTD2 NO1 / RTD2
SSR+ SSR+ Second Analog Input ( valve positioner
4 14 9 4 NO3 / 14 9 11
ANA OP + RTD3 ANA OP +
SSR+ RTD3 type ) + Communication RS485
COM1 / COM1 /
COM3 /15 Second Analog Input ( Remote set point
SSR - 5 15 10 SSR - 5 10 12
ANA OP - ANA OP - SSR - type )
Second Analog Input ( Remote set point
13
type ) + Communication RS485
PID500-A-B-07
PID500-A-B-06 PID500-A-B-08
L 1 CT + 11 6 N L 1 CT + 11 6 N
TC+ TC+
NO2 /
CT - RTD1 NO2 /
CT - RTD1
SSR+ 2 12 7 SSR+ 2 12 7
COM2 / COM2 / ORDERING EXAMPLE
SSR - 3 13 8 SSR - 3 13 8
TC TC Note: Input is user selectable.
NO1 / RTD2 NO1 / RTD2
SSR+
4 14 9 SSR+
4
NO3 /
14 9
Only output needs to be specified in the ordering code.
ANA OP + RTD3 ANA OP + SSR+ RTD3
COM1 / COM1 /
1. PID500 3 0 01
COM3 /
SSR - 5 15 10 SSR - 5 SSR - 15 10 Output 3 ( Relay )
ANA OP - ANA OP -
Output 2 ( Relay )
Output 1 ( Voltage )
PID500-A-B-09 PID500-A-B-11
L 1 RS485 + 11 6 N L 1 RS485 + 11 6 N
TC+ TC+
NO2 / RTD1 NO2 /
RS485 - 12 RTD1
SSR+ 2 RS485 - 12 7 SSR+ 2 7
COM2 / COM2 /
SSR - 3 13 8 SSR - 3 13 8
TC TC
NO1 / RTD2 NO1 / RTD2
SSR+ CT + SSR+
ANA OP +
4 14 9 ANA OP +
4 M+ 14 9
RTD3 RTD3
COM1 / COM1 /
SSR - 5 CT - 15 10 SSR - 5 M- 15 10
ANA OP - ANA OP -
PID500-A-B-12
PID500-A-B-10 PID500-A-B-13 (without Comm. term.)
L 1 11 6 N L 1 RS485 + 11 6 N
TC+ TC+
NO2 / RTD1 NO2 /
RS485 - 12 RTD1
SSR+ 2 12 7 SSR+ 2 7
COM2 / COM2 /
SSR - 3 13 8 SSR - 3 13 8
TC TC
NO1 / RTD2 NO1 / RTD2
SSR+ SSR+
ANA OP +
4 M+ 14 9 ANA OP +
4 I+ 14 9
RTD3 (ANA IP) RTD3
COM1 / COM1 /
SSR - 5 M- 15 10 SSR - 5 I- 15 10
ANA OP - ANA OP - (ANA IP)
48 45 46