1MRK511192-BEN B en Bay Control REC670 1.1 Pre-Configured Product Guide
1MRK511192-BEN B en Bay Control REC670 1.1 Pre-Configured Product Guide
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes
no responsibility for any errors that may appear in this document.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Pre-configured Revision: B
ABB 3
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
2. Available functions
ANSI Function description Single Breaker Double brekaer 1 1/2 breaker for
(A30) (B30) individual CB
(C30)
Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/
Option Option Option
design) design) design)
Control
25 Synchrocheck, energizing check and synchronizing 1 2 3
(SESRSYN)
79 Autorecloser (SMBRREC) - 1/H04 - 2/H05 - 3/H06
Apparatus control for single bay, max 8 apparatuses 1 - - - - -
incl. interlocking (APC8)
Apparatus control for single bay, max 15 apparatuses - - 1 - - -
incl. interlocking (APC15)
Apparatus control for single bay, max 30 apparatuses - - - - 1 -
incl. interlocking (APC30)
90 Automatic voltage control for tapchanger, single - 1/H11 - 1/H11 - 2/H16
control (TR1ATCC)
90 Automatic voltage control for tapchanger, parallell - 1/H15 - 1/H15 - 2/H18
control (TR8ATCC)
84 Tap changer control and supervision, 6 binary inputs 4 - 4 - 4 -
(TCMYLTC)
84 Tap changer control and supervision, 32 binary 4 - 4 - 4 -
inputs (TCMYLTC)
Logic Rotating Switch for function selection and 15 - 15 - 15 -
LHMI presentation (SLGGIO)
Selector mini switch (VSGGIO) 20 - 20 - 20 -
Differential protection
87 1 phase High impedance differential protection - 3/A02 - 3/A02 - 6/A07
(HZPDIF)
Current protection
50 Instantaneous phase overcurrent protection (PHPIOC) - 1/C21 - 2/C22 - 2/C23
51/67 Four step phase overcurrent protection (OC4PTOC) - 1/C21 - 2/C22 - 2/C23
50N Instantaneous residual overcurrent protection - 1/C31 - 2/C32 - 2/C33
(EFPIOC)
51N/ Four step residual overcurrent protection (EF4PTOC) - 1/C31 - 2/C32 - 2/C33
67N
46I2 Four step directional negative phase sequence - 1/C31 - 2/C32 - 2/C33
overcurrent protection (NS4PTOC)
67N Sensitive directional residual overcurrent and power - 1/C16 - 1/C16 - 1/C16
protection (SDEPSDE)
26 Thermal overload protection one time constant - 1/C31 - 1/C32 - 2/C33
(LPTTR)
49 Thermal overload protection two time constants - 1/C31 - 1/C32 - 2/C33
(TRPTTR)
50BF Breaker failure protection (CCRBRF) - 1/C31 - 2/C32 - 3/C33
52PD Pole-discordance protection (CCRPLD) 1 - 2 - 3 -
37 Directional underpower protection (GUPPDUP) - 1/C17 - 1/C17 - 1/C17
32 Directional overpower protection (GOPPDOP) - 1/C17 - 1/C17 - 1/C17
46 Broken conductor check (BRCPTOC) 1 - 1 - 1 -
Voltage protection
27 Two step undervoltage protection (UV2PTUV) - 2/D02 - 2/D02 - 2/D02
4 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ANSI Function description Single Breaker Double brekaer 1 1/2 breaker for
(A30) (B30) individual CB
(C30)
Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/
Option Option Option
design) design) design)
59 Two step overvoltage protection (OV2PTOV) - 2/D02 - 2/D02 - 2/D02
59N Two step residual overvoltage protection (ROV2PTOV) - 2/D02 - 2/D02 - 2/D02
60 Voltage differential protection (VDCPTOV) 2 - 2 - 2 -
27 Loss of voltage check (LOVPTUV) 1 - 1 - 2 -
Frequency protection
81 Underfrequency function (SAPTUF) - 6/E01 - 6/E01 - 6/E01
81 Overfrequency function (SAPTOF) - 6/E01 - 6/E01 - 6/E01
81 Rate-of-change frequency protection (SAPFRC) - 6/E01 - 6/E01 - 6/E01
Multipurpose protection
General current and voltage protection (CVGAPC) - 4/F01 - 4/F01 - 4/F01
Scheme communication
85 Scheme communication logic for distance or - 1/K01 - 1/K01 - 1/K01
overcurrent protection (ZCPSCH)
85 Current reversal and weak-end infeed logic for - 1/K01 - 1/K01 - 1/K01
distance protection (ZCRWPSCH)
Local acceleration logic (ZCLCPLAL) - 1/K01 - 1/K01 - 1/K01
85 Scheme communication logic for residual overcurrent - 1/C21 - 1/C22 - 1/C23
protection (ECPSCH)
85 Current reversal and weak-end infeed logic for - 1/C21 - 1/C22 - 1/C23
residual overcurrent protection (ECRWPSCH)
Logic
94 Tipping logic (SMPPTRC) 2 - 3 - 3 -
Trip matrix logic (GGIO) 12 - 12 - 12 -
Monitoring
Measurements (CVMMXU) 6/10/6 - 6/10/6 - 6/10/6 -
Event counter (CNTGGIO) 5 - 5 - 5 -
Disturbance report (DRPRDRE) 1 - 1 - 1 -
IEC61850 generic communication I/O functions 64 - 64 - 64 -
(SPGGIO)
Fault locator (LMBRFLO) - 1/M01 - 1/M01 - 1/M01
Measured value expander block (RANGE_XP) 66 - 66 - 66 -
Metering
Pulse counter logic (PCGGIO) 16 - 16 - 16 -
Function for energy calculation and demand handling 6 - 6 - 6 -
(ETPMMTR)
Station communication
IEC61850-8-1 Communication *) 1 - 1 - 1 -
LON communication protocol *) 1 - 1 - 1 -
SPA communication protocol *) 1 - 1 - 1 -
IEC60870-5-103 communication protocol *) 1 - 1 - 1 -
ABB 5
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ANSI Function description Single Breaker Double brekaer 1 1/2 breaker for
(A30) (B30) individual CB
(C30)
Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/
Option Option Option
design) design) design)
DNP3.0 for TCP/IP and EiA-485 communication 1 - 1 - 1 -
protocol
Single command, 16 signals 4 - 4 - 4 -
Multiple command and transmit 60/10 - 60/10 - 60/10 -
Remote communication
Binary signal transfer 6 - 6 - 6 -
*) In order to utilize it, an appropriate optional hardware port must be ordered.
6 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
EF4PTOC can be set directional or non- protection can allow the protected circuit to
directional independently for each of the steps. operate closer to the thermal limits.
A second harmonic blocking can be set The three-phase current measuring protection
individually for each step. has an I2t characteristic with settable time
EF4PTOC can be used as main protection for constant and a thermal memory.
phase-to-earth faults. An alarm level gives early warning to allow
EF4PTOC can also be used to provide a operators to take action well before the line
system back-up for example, in the case of is tripped.
the primary protection being out of service
Thermal overload protection, two time
due to communication or voltage transformer constant TRPTTR
circuit failure.
If the temperature of a power transformer/
Directional operation can be combined generator reaches very high values the
together with corresponding communication equipment might be damaged. The insulation
logic in permissive or blocking teleprotection within the transformer/generator will have
scheme. Current reversal and weak-end forced ageing. As a consequence of this the
infeed functionality are available as well. risk of internal phase-to-phase or phase-to-
EF4PTOC can be configured to measure the earth faults will increase. High temperature
residual current from the three-phase current will degrade the quality of the transformer/
inputs or the current from a separate current generator oil.
input. The thermal overload protection estimates
the internal heat content of the transformer/
Sensitive directional residual overcurrent
generator (temperature) continuously. This
and power protection SDEPSDE
estimation is made by using a thermal model
In isolated networks or in networks with of the transformer/generator with two time
high impedance earthing, the earth fault constants, which is based on current
current is significantly smaller than the short measurement.
circuit currents. In addition to this, the
magnitude of the fault current is almost Two warning levels are available. This
independent on the fault location in the enables actions in the power system to be
network. The protection can be selected to done before dangerous temperatures are
use either the residual current or residual reached. If the temperature continues to
increase to the trip value, the protection
power component 3U0·3I0·cos j, for
initiates trip of the protected transformer/
operating quantity with maintained short
generator.
circuit capacity. There is also available one
nondirectional 3I0 step and one 3U0
Breaker failure protection CCRBRF
overvoltage tripping step.
Breaker failure protection (CCRBRF) ensures
Thermal overload protection, one time fast back-up tripping of surrounding breakers
constant LPTTR in case of own breaker failure to open.
The increasing utilizing of the power system CCRBRF can be current based, contact based,
closer to the thermal limits has generated a or adaptive combination between these two
need of a thermal overload protection also principles.
for power lines. A current check with extremely short reset
A thermal overload will often not be detected time is used as check criteria to achieve a
by other protection functions and the high security against unnecessary operation.
introduction of the thermal overload A contact check criteria can be used where
the fault current through the breaker is small.
ABB 7
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
CCRBRF can be single- or three-phase Each function has two steps with definite
initiated to allow use with single phase time delay. Reset times for every step can be
tripping applications. For the three-phase set as well.
version of CCRBRF the current criteria can be
set to operate only if two out of four for Broken conductor check BRCPTOC
example, two phases or one phase plus the The main purpose of the function Broken
residual current start. This gives a higher conductor check (BRCPTOC) is the detection
security to the back-up trip command. of broken conductors on protected power
CCRBRF function can be programmed to give lines and cables (series faults). Detection can
a single- or three-phase re-trip of the own be used to give alarm only or trip the line
breaker to avoid unnecessary tripping of breaker.
surrounding breakers at an incorrect
Voltage protection
initiation due to mistakes during testing.
Two step undervoltage protection
Pole discordance protection CCRPLD UV2PTUV
Single pole operated circuit breakers can due Undervoltages can occur in the power system
to electrical or mechanical failures end up during faults or abnormal conditions. Two
with the different poles in different positions step undervoltage protection (UV2PTUV)
(close-open). This can cause negative and function can be used to open circuit breakers
zero sequence currents which gives thermal to prepare for system restoration at power
stress on rotating machines and can cause outages or as long-time delayed back-up to
unwanted operation of zero sequence or primary protection.
negative sequence current functions.
UV2PTUV has two voltage steps, each with
Normally the own breaker is tripped to inverse or definite time delay.
correct such a situation. If the situation
persists the surrounding breaker should be Two step overvoltage protection OV2PTOV
tripped to clear the unsymmetrical load Overvoltages may occur in the power system
situation. during abnormal conditions, such as, sudden
The Polediscordance protection function power loss, tap changer regulating failures,
CCRPLD operates based on information from open line ends on long lines.
auxiliary contacts of the circuit breaker for Two step overvoltage protection OV2PTOV
the three phases with additional criteria from can be used as open line end detector,
unsymmetrical phase current when required. normally then combined with directional
reactive over-power function or as system
Directional over/underpower protection
GOPPDOP/GUPPDUP voltage supervision, normally then giving
alarm only or switching in reactors or switch
The directional over-/under-power protection out capacitor banks to control the voltage.
(GOPPDOP/GUPPDUP) can be used
wherever a high/low active, reactive or OV2PTOV has two voltage steps, each of
apparent power protection or alarming is them with inverse or definite time delayed.
required. The functions can alternatively be OV2PTOV has an extremely high reset ratio
used to check the direction of active or to allow setting close to system service voltage.
reactive power flow in the power system.
There are number of applications where such Two step residual overvoltage protection
functionality is needed. Some of them are: ROV2PTOV
• detection of reversed active power flow Residual voltages may occur in the power
• detection of high reactive power flow system during earth faults.
8 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 9
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
CT circuit will mean that the situation will The systems can thus be reconnected after an
remain and extremely high voltages will autoreclose or manual closing, which
stress the secondary circuit. improves the network stability.
Current circuit supervision (CCSRDIF) Synchrocheck, energizing check (SESRSYN)
compares the residual current from a three function checks that the voltages on both
phase set of current transformer cores with sides of the circuit breaker are in
the neutral point current on a separate input synchronism, or with at least one side dead
taken from another set of cores on the to ensure that closing can be done safely.
current transformer.
SESRSYN function includes a built-in voltage
A detection of a difference indicates a fault in selection scheme for double bus and 1½
the circuit and is used as alarm or to block breaker or ring busbar arrangements.
protection functions expected to give
Manual closing as well as automatic reclosing
unwanted tripping.
can be checked by the function and can have
Fuse failure supervision (RFUF) different settings.
Failures in the secondary circuits of the For systems which are running asynchronous
voltage transformer can cause unwanted a synchronizing function is provided. The
operation of distance protection, main purpose of the synchronizing function
undervoltage protection, neutral point voltage is to provide controlled closing of circuit
protection, energizing function (synchronism breakers when two asynchronous systems are
check) etc. The fuse failure supervision going to be connected. It is used for slip
function prevents such unwanted operations. frequencies that are larger than those for
synchrocheck and lower than a set maximum
There are three methods to detect fuse failures. level for the synchronizing function.
The method based on detection of zero
sequence voltage without any zero sequence Autorecloser SMBRREC
current. This is a useful principle in a directly The autorecloser (SMBRREC) function
earthed system and can detect one or two provides high-speed and/or delayed auto-
phase fuse failures. reclosing for single or multi-breaker
applications.
The method based on detection of negative
sequence voltage without any negative Up to five reclosing attempts can be
sequence current. This is a useful principle in programmed. The first attempt can be single-,
a non-directly earthed system and can detect two and/or three phase for single phase or
one or two phase fuse failures. multi-phase faults respectively.
The method based on detection of du/dt-di/ Multiple autoreclosing functions are provided
dt where a change of the voltage is compared for multi-breaker arrangements. A priority
to a change in the current. Only voltage circuit allows one circuit breaker to close first
changes means a voltage transformer fault. and the second will only close if the fault
This principle can detect one, two or three proved to be transient.
phase fuse failures.
Each autoreclosing function can be
Control configured to co-operate with a synchrocheck
function.
Synchronizing, synchrocheck and
energizing check SESRSYN Apparatus control APC
The Synchronizing function allows closing of The apparatus control is a function for
asynchronous networks at the correct control and supervision of circuit breakers,
moment including the breaker closing time. disconnectors and earthing switches within a
10 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
bay. Permission to operate is given after IED and is not dependent on any central
evaluation of conditions from other functions function. For the station-wide interlocking,
such as interlocking, synchrocheck, operator the IEDs communicate via the system-wide
place selection and external or internal interbay bus (IEC 61850-8-1) or by using hard
blockings. wired binary inputs/outputs. The interlocking
conditions depend on the circuit
Features in the apparatus control function:
configuration and apparatus position status at
• Select-Execute principle to give high any given time.
reliability
For easy and safe implementation of the
• Selection function to prevent simultaneous
interlocking function, the IED is delivered
operation
with standardized and tested software
• Selection and supervision of operator place
interlocking modules containing logic for the
• Command supervision
interlocking conditions. The interlocking
• Block/deblock of operation
conditions can be altered, to meet the
• Block/deblock of updating of position
customer’s specific requirements, by adding
indications
configurable logic by means of the graphical
• Substitution of position indications
configuration tool.
• Overriding of interlocking functions
• Overriding of synchrocheck Voltage control TR1ATCC, TR8ATCC,
• Operation counter TCMYLTC and TCLYLTC
• Suppression of Mid position
The voltage control functions, Automatic
Two types of command models can be used: voltage control for tap changer, single control
(TR1ATCC,), Automatic voltage control for
• Direct with normal security tap changer, parallel control (TR8ATCC,) and
• SBO (Select-Before-Operate) with enhanced Tap changer control and supervision, 6
security binary inputs (TCMYLTC,) as well as Tap
changer control and supervision, 32 binary
Normal security means that only the inputs TCLYLTC are used for control of
command is evaluated and the resulting power transformers with a motor driven load
position is not supervised. Enhanced security tap changer. The function provides automatic
means that the command is evaluated with an regulation of the voltage on the secondary
additional supervision of the status value of side of transformers or alternatively on a load
the control object. The command security point further out in the network.
with enhanced security is always terminated
by a CommandTermination service primitive. Control of a single transformer, as well as
control of up to eight transformers in parallel
Control operation can be performed from the is possible. For parallel control of power
local HMI under authority control if so defined. transformers, three alternative methods are
available, the master-follower method, the
Interlocking
circulating current method and the reverse
The interlocking function blocks the reactance method. The two former methods
possibility to operate primary switching require exchange of information between the
devices, for instance when a disconnector is parallel transformers and this is provided for
under load, in order to prevent material within IEC61850-8-1.
damage and/or accidental human injury.
Voltage control includes many extra features
Each apparatus control function has such as possibility of to avoid simultaneous
interlocking modules included for different tapping of parallel transformers, hot stand by
switchyard arrangements, where each regulation of a transformer in a group which
function handles interlocking of one bay. The regulates it to a correct tap position even
interlocking function is distributed to each
ABB 11
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
though the LV CB is open, compensation for such as binary inputs and SPGGIO function
a possible capacitor bank on the LV side bay blocks.
of a transformer, extensive tap changer
monitoring including contact wear and Scheme communication
hunting detection, monitoring of the power
Scheme communication logic for distance
flow in the transformer so that for example, or overcurrent protection ZCPSCH
the voltage control can be blocked if the
power reverses etc. To achieve instantaneous fault clearance for
all line faults, a scheme communication logic
Logic rotating switch for function is provided. All types of communication
selection and LHMI presentation SLGGIO schemes for example, permissive
The logic rotating switch for function underreaching, permissive overreaching,
selection and LHMI presentation function blocking, unblocking, intertrip are available.
(SLGGIO) (or the selector switch function The built-in communication module (LDCM)
block) is used to get a selector switch can be used for scheme communication
functionality similar with the one provided by signaling when included.
a hardware selector switch. Hardware
selector switches are used extensively by Current reversal and weak-end infeed logic
utilities, in order to have different functions for distance protection ZCRWPSCH
operating on pre-set values. Hardware The current reversal function is used to
switches are however sources for prevent unwanted operations due to current
maintenance issues, lower system reliability reversal when using permissive overreach
and extended purchase portfolio. The virtual protection schemes in application with
selector switches eliminate all these problems. parallel lines when the overreach from the
two ends overlap on the parallel line.
Selector mini switch VSGGIO
The weak-end infeed logic is used in cases
Selector mini switch (VSGGIO) function where the apparent power behind the
block is a multipurpose function used in the protection can be too low to activate the
configuration tool in PCM600 for a variety of distance protection function. When activated,
applications, as a general purpose switch. received carrier signal together with local
VSGGIO can be controlled from the menu or under voltage criteria and no reverse zone
from a symbol on the single line diagram operation gives an instantaneous trip. The
(SLD) on the local HMI. received signal is also echoed back to
accelerate the sending end.
Single point generic control 8 signals
SPC8GGIO Three phase or phase segregated scheme
logic is available.
The Single point generic control 8 signals
(SPC8GGIO) function block is a collection of Local acceleration logic ZCLCPLAL
8 single point commands, designed to bring
To achieve fast clearing of faults on the
in commands from REMOTE (SCADA) to
whole line, when no communication channel
those parts of the logic configuration that do
is available, local acceleration logic
not need complicated function blocks that
(ZCLCPLAL) can be used. This logic enables
have the capability to receive commands (for
fast fault clearing during certain conditions,
example, SCSWI). In this way, simple
but naturally, it can not fully replace a
commands can be sent directly to the IED
communication channel.
outputs, without confirmation. Confirmation
(status) of the result of the commands is The logic can be controlled either by the
supposed to be achieved by other means, autorecloser (zone extension) or by the loss-of-
load current (loss-of-load acceleration).
12 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 13
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
• OR function block.
Extension logic package
• INVERTER function blocks that inverts the The logic extension block package includes
input signal. additional trip matrix logic and configurable
logic blocks.
• PULSETIMER function block can be used,
for example, for pulse extensions or Fixed signal function block
limiting of operation of outputs.
The Fixed signals function (FXDSIGN)
• GATE function block is used for controlling generates a number of pre-set (fixed) signals
if a signal should be able to pass from the that can be used in the configuration of an
input to the output or not depending on a IED, either for forcing the unused inputs in
setting. other function blocks to a certain level/value,
or for creating a certain logic.
• XOR function block.
Monitoring
• LOOPDELAY function block used to delay Measurements
the output signal one execution cycle.
The service value function is used to get on-
• TIMERSET function has pick-up and drop- line information from the IED. These service
out delayed outputs related to the input values makes it possible to display on-line
signal. The timer has a settable time delay. information on the local HMI and on the
Substation automation system about:
• AND function block.
• measured voltages, currents, frequency,
active, reactive and apparent power and
• SRMEMORY function block is a flip-flop
power factor
that can set or reset an output from two
• the primary and secondary phasors
inputs respectively. Each block has two
• differential currents, bias currents
outputs where one is inverted. The memory
• positive, negative and zero sequence
setting controls if the block after a power
currents and voltages
interruption should return to the state
• mA, input currents
before the interruption, or be reset. Set
• pulse counters
input has priority.
• event counters
• RSMEMORY function block is a flip-flop • measured values and other information
that can reset or set an output from two of the different parameters for included
inputs respectively. Each block has two functions
outputs where one is inverted. The memory • logical values of all binary in- and
setting controls if the block after a power outputs and
interruption should return to the state • general IED information.
before the interruption, or be reset. Reset
input has priority. Supervision of mA input signals (MVGGIO)
The main purpose of the function is to
measure and process signals from different
measuring transducers. Many devices used in
process control represent various parameters
such as frequency, temperature and DC
battery voltage as low current values, usually
in the range 4-20 mA or 0-20 mA.
14 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Alarm limits can be set and used as triggers, may be uploaded to PCM600 and further
e.g. to generate trip or alarm signals. analysis using the disturbance handling tool.
The function requires that the IED is Event list DRPRDRE
equipped with the mA input module.
Continuous event-logging is useful for
Event counter CNTGGIO monitoring of the system from an overview
perspective and is a complement to specific
Event counter (CNTGGIO) has six counters
disturbance recorder functions.
which are used for storing the number of
times each counter input has been activated. The event list logs all binary input signals
connected to the Disturbance report function.
Disturbance report DRPRDRE The list may contain of up to 1000 time-
Complete and reliable information about tagged events stored in a ring-buffer.
disturbances in the primary and/or in the
secondary system together with continuous Indications DRPRDRE
event-logging is accomplished by the To get fast, condensed and reliable
disturbance report functionality. information about disturbances in the
primary and/or in the secondary system it is
Disturbance report DRPRDRE, always
important to know, for example binary
included in the IED, acquires sampled data of
signals that have changed status during a
all selected analog input and binary signals
disturbance. This information is used in the
connected to the function block that is,
short perspective to get information via the
maximum 40 analog and 96 binary signals.
local HMI in a straightforward way.
Disturbance report functionality is a common
There are three LEDs on the local HMI
name for several functions:
(green, yellow and red), which will display
• Event list status information about the IED and the
• Indications Disturbance report function (trigged).
• Event recorder
The Indication list function shows all selected
• Trip value recorder
binary input signals connected to the
• Disturbance recorder
Disturbance report function that have
• Fault locator
changed status during a disturbance.
Disturbance report function is characterized
Event recorder DRPRDRE
by great flexibility regarding configuration,
starting conditions, recording times and large Quick, complete and reliable information
storage capacity. about disturbances in the primary and/or in
the secondary system is vital, for example,
A disturbance is defined as an activation of
time tagged events logged during
an input in the AxRADR or BxRBDR function
disturbances. This information is used for
blocks, which is set to trigger the disturbance
different purposes in the short term (for
recorder. All signals from start of pre-fault
example corrective actions) and in the long
time to the end of post-fault time will be
term (for example Functional Analysis).
included in the recording.
The event recorder logs all selected binary
Every disturbance report recording is saved
input signals connected to the Disturbance
in the IED in the standard Comtrade format.
report function. Each recording can contain
The same applies to all events, which are
up to 150 time-tagged events.
continuously saved in a ring-buffer. The local
HMI is used to get information about the The event recorder information is available
recordings, but the disturbance report files for the disturbances locally in the IED.
ABB 15
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
16 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Metering
Pulse counter logic PCGGIO
Pulse counter (PCGGIO) function counts
externally generated binary pulses, for
instance pulses coming from an external
energy meter, for calculation of energy
consumption values. The pulses are captured
by the binary input module and then read by
the pulse counter function. A scaled service
value is available over the station bus. The
special Binary input module with enhanced
pulse counting capabilities must be ordered
to achieve this functionality.
ABB 17
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
18 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
The binary input module has 16 optically Optical ethernet module OEM
isolated inputs and is available in two
The optical fast-ethernet module is used to
versions, one standard and one with
connect an IED to the communication buses
enhanced pulse counting capabilities on the
(like the station bus) that use the IEC
inputs to be used with the pulse counter
61850-8-1 protocol (port A, B). The module
function. The binary inputs are freely
has one or two optical ports with ST
programmable and can be used for the input
connectors.
of logical signals to any of the functions.
They can also be included in the disturbance Serial SPA/IEC 60870-5-103 and LON
recording and event-recording functions. This communication module SLM
enables extensive monitoring and evaluation
The optical serial channel and LON channel
of operation of the IED and for all associated
module is used to connect an IED to the
electrical circuits.
communication that use SPA, LON, or
IEC60870–5–103. The module has two optical
ports for plastic/plastic, plastic/glass, or glass/
glass. One port is used for SPA and IEC
60870-5-103 one port is used for LON.
ABB 19
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
B C
D
xx05000003.vsd
IEC05000003 V1 EN
20 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3
(mm)
ABB 21
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
6. Connection diagrams
Table 1. Designations for 1/2 x 19” casing with 1 TRM slot
22 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 23
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
24 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
OEM 2) X311:A, B, C, D
Note!
1)
2) OEM X311:A, B (IEC 61850-8-1). OEM
X311:C, D
ABB 25
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
26 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IEC08000479 BG V1 EN
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-
processing function blocks.
ABB 27
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IEC08000484 BG V1 EN
IEC08000480 BG V1 EN
28 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IEC08000477 BG V1 EN
IEC08000476 BG V1 EN
ABB 29
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IEC08000478 BG V1 EN
IEC08000481 BG V1 EN
Figure 10. Binary output module (BOM). Output contacts named XA corresponds to rear
position X31, X41, and so on, and output contacts named XB to rear position
X32, X42, and so on.
30 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IEC08000482 BG V1 EN
IEC08000483 BG V1 EN
Figure 12. Binary in/out module (IOM). Input contacts named XA corresponds to rear position
X31, X41, and so on, and output contacts named XB to rear position X32, X42,
and so on.
ABB 31
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
BUS WA1
BUS WA2
QB1-OPEN
QB1-CLOSE
QB2-OPEN
QB2-CLOSE
-QB1
OPEN QB1
+
-
-QB2
CLOSE QB1
OPEN QB2
+
- CLOSE QB2
TRM1:10
MCB-OK
TRM1:11
MCB-OK
-QA1
CLOSE QA1
INPUTSSIGNALLING
C
C
CLOSE Reinf
SPARE FAULT
QA1-SPR UNCH
-T1
TRM1:1-4 P1
QB9-OPEN
QB9-CLOSE
OPEN QB9
+
-
CLOSE QB9 -QB9
OPEN QB1
+
-
CLOSE QB1 -QC9
QC9-OPEN
QC9-CLOSE
MCB OR
FUSE
TRM1:7-9
= MCB-OK
=
IRF
- + en05000270.vsd
IEC05000270 V1 EN
32 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
BUS WA1
QB1-OPEN
QB1-CLOSE -QB1
OPEN QB1
+
- CLOSE QB1
-QA1
TRM1:11
C
MCB-OK C
T
CLOSE QA1 C
CLOSE Reinf MAIN 2 TRIP T
TRIP QA1 L1,L2,L3 C
TRIP Reinf
QA1-OPEN
QA1-CLOSE
START AR
QA1-SPR UNCH
INHIBIT AR
-T1 P1
START AR
TRM1:1-3
INHIBIT AR -QB61
MCB OR
FUSE
TRM1:7-9
MCB-OK
FAULT SIGNALLING AND SPARE OUTPUTS
QB61-OPEN -QC9
QB61-CLOSE
OPEN QB61
+
- CLOSE QB61
QC9-OPEN
QC9-CLOSE -QB9
OPEN QC9
+
-
CLOSE QC9
QB9-OPEN
QB9-CLOSE -T2
OPEN QB9
+
- P1
CLOSE QB9
AND SPARE INPUTS
FAULT SIGNALS
TRM1:4-6 -QB62
QB62-OPEN
QB62-CLOSE
OPEN QB62
+
-
CLOSE QB62 -QA2
CLOSE QA2 C
CLOSE Reinf C
1/1 x 19"
1 TRM 6I+6U TRIP QA2 L1,L2,L3 T
2-BIM TRIP Reinf C
2-BOM MAIN 2 TRIP T
QA2-OPEN C
QA2-CLOSE
QA2-SPR UNCH
QB2-OPEN
QB2-CLOSE
+ OPEN QB2
-
CLOSE QB2
-QB2
MCB OR
TRM1:12 FUSE
MCB-OK
=
= BUS WA2
IRF
- + en05000264.vsd
IEC05000264 V1 EN
ABB 33
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Figure 14. Typical connection diagram for a feeder connected to a double breaker arrangement
BUS
WA1
QB1 OPEN =1-BU1
QB1 CLOSE -QB1
OPEN QB1
+
- CLOSE QB1
TRM1:10 =1-QA1
C
MCB-OK C
CLOSE 1-QA1 T
50 C
CLOSE Reinf MAIN 2 TRIP T
TRIP 1-QA1 L1,L2,L3 C
TRIP Reinf
1-QA1 OPEN
1-QA1 CLOSE
1-QA1-SPR UNCH
-BI1 P1
TRM1:1-3
=1-QB6
MCB OR
TRM1:7-9 FUSE
MCB-OK
1-QB6 OPEN
=1-QC9
AR MASTER 1-QB6 CLOSE
AR UNSUCC OPEN 1-QB6
+
- CLOSE 1-QB6
START AR
1-QC9 OPEN
INHIBIT AR 1-QC9 CLOSE =1-QB9
WAIT AR OPEN 1-QC9
+
- CLOSE 1-QC9
SIGNALLING
1-QB9 OPEN
FAULT
TRM1:4-6 -QB61
QB61 OPEN
QB61 CLOSE
=3-QA1
3-QA1 OPEN
3-QA1 CLOSE
QB62 OPEN -QB62
QB62 CLOSE =2-QB9
2-QB9 OPEN
2-QB9 CLOSE
2-QB6 OPEN =2-QB6 =2-QC9
2-QB6 CLOSE
MCB OR
FUSE
TRM1:11
MCB-OK
2-QA1 OPEN =2-QA1
2-QA1 CLOSE
QB2 OPEN
QB2 CLOSE
MCB OR
TRM1:12 FUSE
=2-BU1
-QB2
MCB-OK
=
= BUS WA2
IRF
en05000266.vsd
- +
IEC05000266 V1 EN
Figure 15. Typical connection diagram for a complete one and a half breaker arrangement
34 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
7. Technical data
General
Definitions
Reference The specified value of an influencing factor to which are referred the
value characteristics of the equipment
Nominal The range of values of an influencing quantity (factor) within which, under
range specified conditions, the equipment meets the specified requirements
Operative The range of values of a given energizing quantity for which the equipment,
range under specified conditions, is able to perform its intended functions
according to the specified requirements
Analog inputs
ABB 35
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Auxiliary DC voltage
36 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 11. BIM - Binary input module with enhanced pulse counting capabilities
ABB 37
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 13. IOM - Binary input/output module contact data (reference standard: IEC
61810-2)
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
38 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 14. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary
outputs
ABB 39
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 15. SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Table 16. BOM - Binary output module contact data (reference standard: IEC 61810-2)
40 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Influencing factors
ABB 41
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
42 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Test According to
Immunity EN 50263
Emissivity EN 50263
Low voltage directive EN 50178
ABB 43
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Differential protection
Table 25. High impedance differential protection (PDIF, 87)
Current protection
Table 26. Instantaneous phase overcurrent protection PHPIOC
44 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 45
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
46 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 47
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 30. Sensitive directional residual overcurrent and power protection SDEPSDE
48 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 30. Sensitive directional residual overcurrent and power protection SDEPSDE ,
continued
Function Range or value Accuracy
Operate time, non 60 ms typically at 0 to 2 x Iset -
directional residual over
current
Reset time, non 60 ms typically at 2 to 0 x Iset -
directional residual over
current
Operate time, start 150 ms typically at 0 to 2 x Iset -
function
Reset time, start function 50 ms typically at 2 to 0 x Iset -
I = actual measured
current
Ip = load current before
overload occurs
Ib = base current, IBase
ABB 49
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content ± 2.0% of heat content trip
trip value
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content ± 2.0% of heat content trip
trip
50 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 51
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Voltage protection
Table 38. Two step undervoltage protection UV2PTUV
52 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 53
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Frequency protection
Table 42. Underfrequency protection SAPTUF
54 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Multipurpose protection
Table 45. General current and voltage protection (GAPC)
See table 88 and table 89 Parameter ranges for customer See table 88 and table 89
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
ABB 55
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
High and low voltage limit, (1.0 - 200.0)% of Ubase ± 1.0% of Ur for U<Ur
voltage dependent operation ± 1.0% of U for U>Ur
56 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 57
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Control
Table 48. Synchronizing, synchrocheck and energizing check SESRSYN
58 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 59
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
60 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 50. Voltage control TR1ATCC, TR8ATCC, TCMYLTC and TLCYLTC, continued
Function Range or value Accuracy
Alarm level of active power in (-9999.99–9999.99) MW ± 1.0% of Sr
forward and reverse direction
Alarm level of reactive power in (-9999.99–9999.99) MVAr ± 1.0% of Sr
forward and reverse direction
Time delay for alarms from power (1–6000) s ± 0.5% ± 10 ms
supervision
Tap position for lowest and highest (1–63) -
voltage
mA for lowest and highest voltage (0.000–25.000) mA -
tap position
Type of code conversion BIN, BCD, GRAY, SINGLE, mA -
Time after position change before (1–60) s ± 0.5% ± 10 ms
the value is accepted
Tap changer constant time-out (1–120) s ± 0.5% ± 10 ms
Raise/lower command output pulse (0.5–10.0) s ± 0.5% ± 10 ms
duration
Scheme communication
Table 51. Scheme communication logic for distance or overcurrent protection ZCPSCH
ABB 61
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 52. Current reversal and weak-end infeed logic for distance protection
ZCRWPSCH
Table 53. Scheme communication logic for residual overcurrent protection ECPSCH
Table 54. Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH
62 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Logic
Table 55. Tripping logic SMPPTRC
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicPulseTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicTimerSet 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicLoopDelay 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicXOR - - 49 - -
LogicSRMemory - - 49 - -
LogicTimer - - 49 (0.000– ± 0.5% ± 10 ms
90000.000) s
LogicPulseTimer - - 49 (0.000– ± 0.5% ± 10 ms
90000.000) s
Trip matrix logic - - 12 - -
ABB 63
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Monitoring
Table 58. Measurements CVMMXN
64 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 65
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Function Value
Buffer capacity Maximum number of events in 1000
the list
Resolution 1 ms
Accuracy Depending on time
synchronizing
Function Value
Buffer capacity Maximum number of indications presented 96
for single disturbance
Maximum number of recorded disturbances 100
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on
time
synchronizing
Function Value
Buffer capacity Maximum number of analog inputs 30
Maximum number of disturbance reports 100
66 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and 340 seconds (100 recordings)
maximum number of channels, typical value) at 50 Hz
280 seconds (80 recordings) at
60 Hz
Metering
Table 68. Pulse counter PCGGIO
Station communication
Table 70. IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
ABB 67
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
68 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Remote communication
Hardware
ABB 69
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
IED
Table 79. Water and dust protection level according to IEC 60529
Connection system
70 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out
Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled ± 1.0 ms typically
measurement values
Function Value
Max antenna cable attenuation 26 db @ 1.6 GHz
Antenna cable impedance 50 ohm
Lightning protection Must be provided externally
Antenna cable connector SMA in receiver end
TNC in antenna end
ABB 71
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Inverse characteristic
Table 88. ANSI Inverse time characteristics
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
72 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
ABB 73
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
74 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 91. Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
ABB 75
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 92. Inverse time characteristics for Two step overvoltage protection (POVM, 59)
U> = Uset
U = Umeasured
76 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Table 93. Inverse time characteristics for Two step residual overvoltage protection
(POVM, 59N)
U> = Uset
U = Umeasured
ABB 77
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
8. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Exemple code: REC670*1.1-A30-C01D02F01H04-X0-D-C-B-B-A6X0-DAXR-X-XD. Using the code of each position #1-12 specified as
REC670*1-2 2-3 3 3 3 3 3 3 3-4 4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REC670* - - - - - . - -
- 10 - 11 - 12
- . -
SOFTWARE Position
#1 Notes and Rules
Version number
Version no 1.1
Selection for position #1.
78 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
ABB 79
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules
Compression terminals K
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.
80 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
Slot position (rear view) Note: Max 3 positions in 1/2
rack, 8 in 3/4 rack with 1 TRM,
5 in 3/4 rack with 2 TRM, 14 in
1/1 rack with 1 TRM and 11 in
1/1 rack with 2 TRM
1/2 Case with 1 TRM
3/4 Case with 1 TRM
3/4 Case with 2 TRM
1/1 Case with 1 TRM
1/1 Case with 2 TRM
No board in slot X X X X X X X X X X X X
Binary output module 24 A A A A A A A A A A A A A Note: Maximum 4 (BOM+SOM
output relays (BOM) +MIM) boards.
BIM 16 inputs, RL24-30 VDC, B B B B B B B B B B B B B
30 mA
BIM 16 inputs, RL48-60 VDC, C C C C C C C C C C C C C
30 mA
BIM 16 inputs, RL110-125 D D D D D D D D D D F F F
VDC, 30 mA
BIM 16 inputs, RL220-250 E E E E E E E E E E E E E
VDC, 30 mA
BIMp 16 inputs, RL24-30 VDC F F F F F F F F F F F F
for pulse counting
BIMp 16 inputs, RL48-60 VDC G G G G G G G G G G G G
for pulse counting
BIMp 16 inputs, RL110-125 H H H H H H H H H H H H
VDC for pulse counting
BIMp 16 inputs, RL220-250 K K K K K K K K K K K K
VDC for pulse counting
IOM 8 inputs, 10+2 output, L L L L L L L L L L L L
RL24-30 VDC
IOM 8 inputs, 10+2 output, M M M M M M M M M M M M
RL48-60 VDC
IOM 8 inputs, 10+2 output, N N N N N N N N N N N N
RL110-125 VDC
IOM 8 inputs, 10+2 output, P P P P P P P P P P P P
RL220-250 VDC
IOM with MOV 8 inputs, 10-2 U U U U U U U U U U U U
output, 24-30 VDC
IOM with MOV 8 inputs, 10-2 V V V V V V V V V V V V
output, 48-60 VDC
IOM with MOV 8 inputs, 10-2 W W W W W W W W W W W W
output, 110-125 VDC
IOM with MOV 8 inputs, 10-2 Y Y Y Y Y Y Y Y Y Y Y Y
output, 220-250 VDC
mA input module MIM 6 R R R R R R R R R R R Note: Max 4 (BOM+SOM+MIM)
channels board in 1/1 case. Max 1 MIM+3
BOM in 3/4 case. No MIM board
in 1/2 case
GPS time synchronization S S S S S
module (in last slot)
SOM static outputs module, 12 T T T T T T T T T T T T
outputs, 48-60 VDC 1 1 1 1 1 1 1 1 1 1 1 1
SOM static outputs module, 12 T T T T T T T T T T T T
outputs, 110-250 VDC 2 2 2 2 2 2 2 2 2 2 2 2
Selection for position #10.
ABB 81
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Remote end communication, DNP serial comm. #11 Notes and Rules
and time synchronization modules
X312
X313
X302
X303
X322
X323
Slot position (rear view)
Available slots in 1/2 case with 1TRM Note: Max 1 LDCM in 1/2 case
Available slots in 3/4 & 1/1 case with 2 TRM Note: Max 2 LDCM in 3/4 and
1/1 case
Available slots in 3/4 & 1/1 case with 2 TRM slots
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Not in A21
Note: Max 2 LDCM (same or
Optical medium range, LDCM 1310 nm B B B B B B
different type) can be selected
IRIG-B Time synchronization module, with PPS F
Galvanic RS485 communication module G G G G
Selection for position #11.
Serial communication unit for station communication #12 Notes and Rules
X301
X311
Slot position (rear view)
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain
functions can only be ordered in combination with other functions and that some functions require specific
hardware selections.
82 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Hardware
Accessories
GPS antenna and mounting details
ABB 83
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
External interface converter from C37.94 to G703 including Quantity: 1MRK 002 245-AA
1U 19” rack mounting accessories
External interface converter from C37.94 to G703.E1 Quantity: 1MRK 002 245-BA
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of IED, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of IED, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of IED, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
84 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
High impedance resistor unit 1-ph with resistor 1.8 kOhms and Quantity: 1 2 3 RK795101-MA
voltage dependent resistor for 20-100V operating voltage
High impedance resistor unit 3-ph with resistor 1.8 kOhms and Quantity: RK795101-MB
voltage dependent resistor for 20-100V operating voltage
High impedance resistor unit 1-ph with resistor 6.8 kOhms and Quantity: 1 2 3 RK795101-CB
voltage dependent resistor for 100-400V operating voltage
High impedance resistor unit 3-ph with resistor 6.8 kOhms and Quantity: RK795101-DC
voltage dependent resistor for 100-400V operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
ABB 85
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
User documentation
Rule: Specify the number of printed manuals requested IEC Quantity: 1MRK 511 188-UEN
Operator’s manual
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
86 ABB
Bay control REC670 1MRK 511 192-BEN B
Pre-configured
Product version: 1.1 Issued: June 2010
Related documents
ABB 87
88