This document provides pipe wall thickness calculations for steam pipes as per Indian Boiler Regulation 1950. It lists pipe sizes from 323.850mm to 21.300mm and calculates the minimum required thickness according to the regulation's formula based on design pressure of 41.0 kg/cm2, design temperature of 405°C, material (A106 GR.B), and other factors. The calculated thicknesses are compared to the nominal thicknesses and a selected thickness is chosen at 12.5% above the minimum.
This document provides pipe wall thickness calculations for steam pipes as per Indian Boiler Regulation 1950. It lists pipe sizes from 323.850mm to 21.300mm and calculates the minimum required thickness according to the regulation's formula based on design pressure of 41.0 kg/cm2, design temperature of 405°C, material (A106 GR.B), and other factors. The calculated thicknesses are compared to the nominal thicknesses and a selected thickness is chosen at 12.5% above the minimum.
This document provides pipe wall thickness calculations for steam pipes as per Indian Boiler Regulation 1950. It lists pipe sizes from 323.850mm to 21.300mm and calculates the minimum required thickness according to the regulation's formula based on design pressure of 41.0 kg/cm2, design temperature of 405°C, material (A106 GR.B), and other factors. The calculated thicknesses are compared to the nominal thicknesses and a selected thickness is chosen at 12.5% above the minimum.
Drg. Title : DRG NO 7311-DE-151 Rev.- 0, Dated 12.01.2019 Client : M/S Jindal Urban Waste Management (Guntur) Ltd. Consultant : M/S Korus Engineering Solutions Pvt. Ltd. Service : STEAM Pipe Material : A106 GR.B Pipe Sizes : 323.850, 273.000, 219.100, 168.300, 114.300, 88.900, 60.300, 33.400, 26.670, 21.300, Design Pressure : 41.0 Kg/Cm Square Design Temperature : 405°C Efficiency Factor : 1.00 Corrosion Factor : 0.075 Cm As per IBR Clause 350 For A106GR.B Allowable Stress f : Lowest Value from Et/1.5 or R/2.7 18600.00/1.5 or 60000.00/2.7 12400.00 PSI or 22222.22 PSI 12400.00 PSI or = 871.74 Kg/Cm square
Formula : WP = 2 fe ( T – C ) / [ D – ( T – C ) ] as per IBR Reg. 350
Where WP = Working Pressure f = Allowable Stress as Calculated above e = Efficiency Factor D = Outside Diameter in CM C = Corrosion Allowance T = Calculated Thickness OR T = C + D x WP / (WP+2 fe) T = 0.075 + D x 41.0 /( 41.0 + 2 X 871.74 x 1.00) FOR A106 GR.B T = 0.075 + 0.022975 x D Cm ------------------------------------------------------------------------------------------------------------------------------------ O.D. of Pipe Calculated Thk. Actual Thk. Selected Thk. MM CM / MM NOM. In MM Min. in MM@ 12.5% ----------------------------------------------------------------------------------------------------------------------------------- 323.850 0.819/8.19 21.440 18.760