City of Aurora Public Works Department

FIRE WATCH REQUIREMENTS


Building Division • 15151 E. Alameda Parkway, Ste 2400 • Aurora, CO 80012 • 303-739-7420 • Fax: 303-739-7551

Until a valid Certificate of Occupancy is issued by the Building Division, all buildings are considered construction sites and any
occupancy, including stocking of furniture, materials and merchandise is prohibited. However, in an effort to accommodate the
building owner, exceptions to the requirements of the building code may be considered if the following criteria are followed:
■ Written permission must be obtained from the City of Aurora Building Division prior to installing any furniture, merchandise or
materials within a building under construction.
■ Upon receiving a request for stocking this Division will conduct inspections to determine the safety and suitability of the request.
■ Stocking of furniture or materials must not hinder or impact the performance of any remaining building inspections.
■ Fire sprinkler and alarm systems must be operational and must be inspected and approved by the Building Division. Bringing
merchandise and furniture into a building loads the building with combustibles and the building must have systems in place to
extinguish a fire and occupants and emergency personnel.
■ Proper exiting for the building must be in place. This includes all required exit signs, exit doors, panic hardware, etc. Stocking
operations typically involve large numbers of people and it is necessary to ensure that in the event of an emergency, safe egress from
the building can be accomplished.
■ No safety hazards can exist in the building. We will inspect to make sure that all electrical boxes are closed, no live wires are present,
guardrails and signs are in place and no other hazards to occupants exist.
■ If racks are needed, all permits and inspections must be complete prior to loading of the racks.
■ Failure to meet these conditions will result in the denial of stocking.

Written approval will be granted by the supervisory staff and appropriate forms (orange in color) must be posted on the construction site
with the building permit card. The approval form will indicate the areas of the building that may be stocked and must be signed by the
job site contractor. Without this form stocking will not be permitted.

What is a fire watch? system. A fire watch cannot be used as a simultaneously—fire watch personnel
technique to avoid or delay the installation shall have the sole responsibility of
A fire watch is a temporary measure for of a required fire sprinkler, fire alarm, or performing fire watch duties.
the purposes of ensuring the fire-safety other life safety system. Hot work requires
of a building or premises in the event that a fire watch last throughout the What are the duties of fire watch
of any act or situation which creates an duration of the operation and at least 30 personnel?
increased risk to persons or property. The minutes after the conclusion of work. The
term fire watch is also used to describe a 30 minute time period may be extended Fire watch personnel shall:
dedicated person or persons whose sole by the fire code official depending on the ■ Have access to one approved means
responsibility is to look for fires and other nature of work or hazards present. of communication; know the exact
hazards within a building, specific area, or address of the property, and how
premises. Who can be assigned to fire to report a fire or other emergency
watch? condition by calling 9-1-1.
What is the purpose of a fire Persons assigned to fire watch should ■ Be familiar with the buildings and
watch? be familiar with the building or premises property and have an accepted written
The purpose of a fire watch is provide and have access to all areas to sufficiently plan for patrolling the property.
temporary surveillance in a building or perform their patrol duties. Assigned ■ Be trained in the use of fire
premises for the purposes of identifying persons should also be well-versed in any extinguishers shall have access to all
and controlling fire hazards, detecting and all emergency evacuation procedures, facility fire extinguishers and know
early signs of unwanted fire, initiating safety plans, alarm activation procedures, their location.
alarms or evacuation procedures, and and have formal training in the proper use ■ Have knowledge of and be trained
notifying the fire department. of fire extinguishers or other emergency in the facility’s evacuation plan in
safety equipment. Persons assigned to fire the event of a fire. They shall be able
How long can a fire watch watch must have no other responsibilities to communicate with non-English
remain in effect? but to perform the fire watch. In other speaking residents well enough to give
words, an employee who is normally
an evacuation order.
In general, a fire watch is to be used only assigned to perform maintenance duties
as a temporary means to provide either in a school cannot be assigned to a fire ■ Not be permitted, while on duty, to
an extra level of safety (in the case of a watch while cleaning floors; nor can a perform any other duties.
special event or hot work operation) or security guard at a public event perform ■ Not be impaired and shall remain
to supplant an out of service life safety door security and fire watch duties awake and alert at all times.

Fire Watch Requirements (Revised 2/2013)


■ Keep a log of fire watch related “approved” means shall be determined by Who do I send the completed fire
activities. The log shall include; the local fire code official. Examples watch logs too?
address of the facility, time of each include a hard-wired telephone,
patrol, name of the fire watch person, cellular phone (with no dead-coverage Daily notification of the completion of each
notes for other related activities fire watch must provided to the Building
areas), manual central station fire
performed. The log shall be faxed to Division prior to 9:00 AM on the morning
alarm, or radio.
after each scheduled fire watch the log
(303-739-7551) or emailed to mdean@ ■ Fire watch personnel shall also be shall be emailed or faxed to the contact
auroragov.org. provided access to fire extinguishing shown below:
■ Keep a constant watch for fires, be equipment (i.e., portable extinguishers)
on the lookout for any obstructions to and have received adequate training Attn: Mike Dean
exits, and be alert to any other hazards City of Aurora Building Division
on its safe use.
during the time when the building or Email: mdean@auroragov.org (subject
■ During hot work operations, fire watch line: Fire Watch Log for (name and
premises is open to the public, the
personnel shall be supplied a minimum address of building)
hazardous activity is taking place,
of one portable fire extinguisher with Fax: 303-739-7551 (Attn: Mike Dean)
or throughout the duration of the fire
a minimum 2A:20BC rating. This
alarm/sprinkler system being out of Who do I notify when I complete a fire
extinguisher shall be within 30 feet
service. watch?
of the location where the hot work is
■ Are expected to correct any hazards performed. Fire watch and hot work A fire watch can only be removed
found, extinguish small fires, contact personnel shall be trained on the where the Building Division has granted
the fire department, activate fire proper use of fire extinguishers before approval. Approval is typically based
alarms, and assist with emergency performing these duties. upon the issuance of a temporary or a
evacuation procedures of the public. full Certificate of Occupancy. Contact the
■ Patrol their areas at a minimum of How do you request a fire watch? Field Inspectors Supervisors Office by
30-minute intervals. calling 303-739-7420.
If a fire watch is deemed necessary while
Are there any specific tools or an active building permit is in place then
equipment fire watch personnel need the Aurora Building Division will authorize
Key Life Safety Plan Review Staff:
to perform their duties? the fire watch through the Field Inspectors • Mike Dean, Life Safety Plans
Supervisors Office (303-739-7420). The Examiner Supervisor (303) 739-7447.
■ Fire watch personnel need to be
provided with a minimum of one Aurora Fire Department (303-326-8999) • Neil Wiegert, Life Safety Plans
(1), approved and reliable means of is responsible for approving any request Examiner (303)-739-7613.
notification to the local fire department for a fire watch where there is NOT a valid • Jean Pardue, Life Safety Plans
or fire alarm monitoring company. The building permit in place. Examiner (303) 739-7410.

Finally, it is a requirement that all fire watch personnel record a log of their activity.
The log shall have the following information:
Name/Address of Building: _______________________________________________________________________________________________

Reason for Fire Watch:___________________________________________________________________________________________________

Person Performing Fire Watch: ____________________________________________________________________________________________

Date: _________ /_________ Time: _________ /_________ a.m. p.m. Area patrolled:___________________ Status: ____________________

Date: _________ /_________ Time: _________ /_________ a.m. p.m. Area patrolled:___________________ Status: ____________________

Date: _________ /_________ Time: _________ /_________ a.m. p.m. Area patrolled:___________________ Status: ____________________

Date: _________ /_________ Time: _________ /_________ a.m. p.m. Area patrolled:___________________ Status: ____________________

BOARD OF APPEALS: The City of Aurora has created a Building Code and Contractors Appeals and Standards Board. Applicants
have the right to have the board hear appeals of orders, decisions or determinations made by the building official relative to the
application and interpretation of the building code. Any application for appeal to the board shall be based on a claim that the true
intent of the code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of the building cod do not
fully apply or an equally good or better form of construction is proposed.