DRAINAGE DESIGN CALCULATIONS

Project : CADANGAN PROJEK PEMBANGUNAN HARTANAH MAIS DI LOT 44697 SEKSYEN 9, PN 96172 JALAN PADANG TEMBAK, BANDAR KAJANG, DAERAH HULU
LANGAT, SELANGOR DARUL EHSAN

Owner : MAJLIS AGAMA ISLAM SELANGOR (MAIS) Date : 11/03/2016


Prepared by: Narvell De Abrill A. Gabil
Location Design Flow (5 years ARI)
1 2 3 4 5 6 8 9 10 11 12.00
Remarks
Drain Line Catchment Runoff Rainfall Design Cumul. Type of Drain Gradient Depth Capacity Velocity
Area (A) Coeff. (C) intensity Flow (Q) Flow (Q) Prov.
Ha mm/hr m3/s m3/s 1:X m m3/s m/s
a1 - a2 0.013 0.80 281.66 0.008 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18 -
a2 - a3 0.013 0.80 281.66 0.008 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a3 - a4 0.013 0.80 281.66 0.008 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a4 - a5 0.023 0.80 281.66 0.014 0.022 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a5 - a6 0.005 0.80 281.66 0.003 0.025 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a6 - a7 0.002 0.80 281.66 0.001 0.026 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a7 - a8 0.006 0.80 281.66 0.004 0.030 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a8 - a9 0.001 0.80 281.66 0.001 0.031 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
b1 - b2 0.086 0.80 281.66 0.054 0.054 V SHAPE (W=300) 1:225 0.300 0.09 0.996
b2 - b3 0.006 0.80 281.66 0.004 0.057 V SHAPE (W=300) 1:225 0.300 0.09 0.996
b4 - b5 0.008 0.80 281.66 0.005 0.005 V SHAPE (W=300) 1:225 0.300 0.09 0.996
b5 - b6 0.008 0.80 281.66 0.005 0.010 V SHAPE (W=300) 1:225 0.300 0.09 0.996
b6 - b3 0.008 0.80 281.66 0.005 0.010 V SHAPE (W=300) 1:225 0.300 0.09 0.996
b3 - a9 0.004 0.80 281.66 0.002 0.101 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a9 - a10 0.082 0.80 281.66 0.051 0.152 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a10 - a11 - 0.80 281.66 - 0.152 750mm Dia RCPC CLASS Y 1:300 - 0.76 1.72 CULVERT
a11 - a12 0.036 0.80 281.66 0.023 0.174 225mm PC HR (W=450) 1:225 0.600 0.31 1.28
a12 - OSD 0.035 0.80 281.66 0.022 0.197 225mm PC HR (W=450) 1:225 0.600 0.31 1.28

Page 1 of 63
a13 - a14 0.077 0.80 281.66 0.048 0.048 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a14 - a15 0.157 0.80 281.66 0.098 0.147 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a15 - a16 0.052 0.80 281.66 0.033 0.179 225mm PC HR (W=450) 1:225 0.600 0.31 1.28
a16 - a17 0.008 0.80 281.66 0.005 0.184 225mm PC HR (W=450) 1:225 0.600 0.31 1.28
a18 - a19 0.136 0.80 281.66 0.085 0.085 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a19 - a17 0.073 0.80 281.66 0.046 0.131 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a17 - OSD - 0.80 281.66 - 0.315 225mm PC HR (W=600) 1:225 0.600 0.45 1.43

a1 - a20 0.006 0.80 281.66 0.004 0.004 750mm Dia RCPC CLASS Y 1:300 - 0.76 1.72 CULVERT
a20 - a21 0.006 0.80 281.66 0.004 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a21 - a22 - 0.80 281.66 - 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a22 - a23 - 0.80 281.66 - 0.008 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a4 - a24 0.008 0.80 281.66 0.005 0.005 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a24 - a23 0.014 0.80 281.66 0.009 0.014 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a23 - a25 - 0.80 281.66 - 0.021 750mm Dia RCPC CLASS Y 1:300 - 0.76 1.72 CULVERT
a25 - a26 0.083 0.80 281.66 0.052 0.073 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a26 - a27 - 0.80 281.66 - 0.073 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a27 - a28 - 0.80 281.66 - 0.073 750mm Dia RCPC CLASS Y 1:225 - 0.76 1.72 CULVERT
a28 - a29 0.060 0.80 281.66 0.038 0.111 225mm PC HR (W=450) 1:225 0.450 0.20 1.18
a29 - OSD - 0.80 281.66 - 0.111 225mm PC HR (W=450) 1:225 0.450 0.20 1.18

Page 2 of 63
RATIONAL METHOD CALCULATION

(a) Determine I and C

Assume :-
Time of concentration tc = 5.0 minutes .

For ARI of 10 years, from Table 2.B1 using Eqn. 2.2 ;


(Pintu Kaw Tg Agas, ID: 2025001)
Fitting constants : λ = 80.936
κ = 0.1870
θ = 0.2580
η = 0.8900

Rainfall Intensity and Rainfall Depth for 30 and 60minutes :

From Eqn. 2.2;


i= λTκ
(
d + θ)η

i= 80.936 x 10^(0.187)
( 0.0833 + 0.258 )^(0.89)

i = 324.05 mm/hr

Table 2.5; C= 0.90 [ Commercial and Business Centres ]

(b) Determine Peak Flow, Q

From Equation 2.3,

Design peak flow, Q10 = C.i.A


360
0.810 A.(m3 /s)

Note : ' A ' is subcatchment area.


DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS


Owner : - Date : 28/09/2018
Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI

Ground Level:
Minimum Depth: 0.45 m

Location Design Flow (10 years ARI)


1 2 3 4 5 6 8 9 10 11
Catchment Runoff Rainfall Design Cumul.
Drain Line Type of Drain Capacity Velocity Design Remark
Area (A) Coeff. (C) intensity Flow (Q) Flow (Q)
Ha mm/hr m3/s m3/s m3/s m/s
A1 - A1.1 0.042 0.90 324.05 0.034 0.034 300mm PC HR (W=750) 0.38 1.45 PASSED
A1.1 - A1.2 0.077 0.90 324.05 0.062 0.096 300mm PC HR (W=750) 0.38 1.45 PASSED
A1.2 - A1.3 0.061 0.90 324.05 0.049 0.225 300mm PC HR (W=750) 0.38 1.45 PASSED
A1.3 - A1.4 0.041 0.90 324.05 0.033 0.338 300mm PC HR (W=750) 0.38 1.45 PASSED
A1.4 - A1.5 0.052 0.90 324.05 0.042 0.408 300mm PC HR (W=750) 0.38 1.45 FAILED
A1.5 - A1.6 0.092 0.90 324.05 0.075 0.483 300mm PC HR (W=750) 0.38 1.45 FAILED
A1.6 - A1.7 0.051 0.90 324.05 0.041 0.656 300mm PC HR (W=750) 0.38 1.45 FAILED
A1.7 - A1.8 0.038 0.90 324.05 0.030 1.154 300mm PC HR (W=750) 0.38 1.45 FAILED
A1.8 - OSD 1 0.074 0.90 324.05 0.060 1.290 PC PIPE 225mm DIA FAILED

A2 - A2.1 0.030 0.90 324.05 0.024 0.024 300mm PC HR (W=750) 0.20 1.17 PASSED
A2.1 - A1.3 0.070 0.90 324.05 0.056 0.080 300mm PC HR (W=750) 0.20 1.17 PASSED

A3 - A3.1 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.38 1.45 PASSED
A3.1 - A3.2 0.051 0.90 324.05 0.041 0.072 300mm PC HR (W=750) 0.38 1.45 PASSED
A3.2 - A3.3 0.032 0.90 324.05 0.026 0.098 300mm PC HR (W=750) 0.38 1.45 PASSED
A3.3 - A3.4 0.032 0.90 324.05 0.026 0.318 300mm PC HR (W=750) 0.38 1.45 PASSED
A3.4 - A7.2 0.050 0.90 324.05 0.040 0.390 300mm PC HR (W=750) 0.38 1.45 FAILED
A4 - A4.1 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.42 1.48 PASSED
A4.1 - A4.2 0.048 0.90 324.05 0.039 0.076 300mm PC HR (W=750) 0.42 1.48 PASSED
A4.2 - A5.2 0.026 0.90 324.05 0.021 0.097 300mm PC HR (W=750) 0.11 1.02 PASSED

A5 - A5.1 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.42 1.48 PASSED
A5.1 - A5.2 0.048 0.90 324.05 0.039 0.076 300mm PC HR (W=750) 0.42 1.48 PASSED
A5.2 - A3.3 0.026 0.90 324.05 0.021 0.194 300mm PC HR (W=750) 0.42 1.48 PASSED

A6 - A3.4 0.039 0.90 324.05 0.032 0.032 300mm PC HR (W=750) 0.11 1.02 PASSED

A7 - A7.1 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.42 1.48 PASSED
A7.1 - A7.2 0.039 0.90 324.05 0.031 0.452 300mm PC HR (W=750) 0.42 1.48 FAILED
A7.2 - A1.7 0.020 0.90 324.05 0.016 0.468 300mm PC HR (W=750) 0.42 1.48 FAILED

A8 - A8.1 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.42 1.48 PASSED
A8.1 - A1.8 0.059 0.90 324.05 0.048 0.076 300mm PC HR (W=750) 0.42 1.48 PASSED

A9 - A9.1 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.20 1.17 PASSED
A9.1 - A9.2 0.039 0.90 324.05 0.031 0.050 300mm PC HR (W=300) 0.20 1.17 PASSED
A9.2 - PT.EX1 0.056 0.90 324.05 0.045 0.095 PC PIPE 225mm DIA FAILED

A10 - A1.4 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.42 1.48 PASSED
A10 - A10.1 0.034 0.90 324.05 0.028 0.056 300mm PC HR (W=750) 0.42 1.48 PASSED
A10.1 - A10.2 0.061 0.90 324.05 0.049 0.105 300mm PC HR (W=750) 0.42 1.48 PASSED
A10.2 - A1.6 0.033 0.90 324.05 0.027 0.132 300mm PC HR (W=750) 0.42 1.48 PASSED
B1 - B1.1 0.042 0.90 324.05 0.034 0.034 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.1 - B1.2 0.021 0.90 324.05 0.017 0.051 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.2 - B1.3 0.021 0.90 324.05 0.017 0.068 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.3 - B1.4 0.019 0.90 324.05 0.015 0.107 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.4 - B1.5 0.022 0.90 324.05 0.018 0.156 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.5 - B1.6 0.035 0.90 324.05 0.028 0.221 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.6 - B1.7 0.032 0.90 324.05 0.026 0.286 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.7 - B1.8 0.033 0.90 324.05 0.027 0.332 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.8 - B1.9 0.035 0.90 324.05 0.028 0.351 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.9 -B1.10 0.022 0.90 324.05 0.018 0.401 300mm PC HR (W=750) 0.42 1.48 PASSED
B1.10 -B1.11 0.019 0.90 324.05 0.015 0.447 300mm PC HR (W=750) 0.42 1.48 FAILED
B1.11 -B1.12 0.018 0.90 324.05 0.015 0.462 300mm PC HR (W=750) 0.42 1.48 FAILED
B1.12 - OSD 2 0.023 0.90 324.05 0.018 0.508 300mm PC HR (W=750) 0.42 1.48 FAILED

B2 - B1.3 0.030 0.90 324.05 0.024 0.024 300mm PC HR (W=750) 0.42 1.48 PASSED

B3 - B1.4 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.42 1.48 PASSED

B4 - B1.5 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.42 1.48 PASSED

B5 - B5.1 0.014 0.90 324.05 0.012 0.012 300mm PC HR (W=300) 0.20 1.17 PASSED
B5.1 - B1.6 0.033 0.90 324.05 0.027 0.039 300mm PC HR (W=300) 0.20 1.17 PASSED

B6 - B1.7 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.20 1.17 PASSED

B7 - B1.8 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.42 1.48 PASSED

B8 - B1.9 0.039 0.90 324.05 0.032 0.032 300mm PC HR (W=300) 0.20 1.17 PASSED

B9 - B1.10 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=300) 0.20 1.17 PASSED

B10 - B1.12 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.42 1.48 PASSED
B11 - B12 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.20 1.17 PASSED
B12 - PT.EX2 0.021 0.90 324.05 0.017 0.036 PC PIPE 225mm DIA FAILED

C1 - C2 0.030 0.90 324.05 0.025 0.025 300mm PC HR (W=300) 0.20 1.17 PASSED
C2 - C3 0.046 0.90 324.05 0.037 0.062 300mm PC HR (W=300) 0.20 1.17 PASSED
C3 - C4 0.046 0.90 324.05 0.037 0.099 300mm PC HR (W=300) 0.20 1.17 PASSED
C4 - C5 0.046 0.90 324.05 0.037 0.136 300mm PC HR (W=300) 0.20 1.17 PASSED
C5 - C6 0.027 0.90 324.05 0.022 0.158 300mm PC HR (W=300) 0.20 1.17 PASSED
C6 - OSD 1 0.037 0.90 324.05 0.030 0.188 PC PIPE 225mm DIA FAILED
Invert Level
12 13 14 15
Remarks
Ground
Length Gradient Invert Level
Level
m m 1: X m
12.28 26.374 1: 200 11.830
46.967 1: 200 11.698
21.349 1: 200 11.463
5.720 1: 200 11.357
46.471 1: 200 11.328
45.247 1: 200 11.096
5.720 1: 200 10.869
21.336 1: 200 10.841
5.926 1: 200 10.734

13.22 26.369 1: 200 12.770


46.966 1: 200 12.638

13.22 43.266 1: 200 12.770


43.266 1: 200 12.554
4.287 1: 200 12.337
43.266 1: 200 12.316
4.296 1: 200 12.100
12.80 22.550 1: 200 12.350
22.550 1: 200 12.237
4.301 1: 200 12.125

12.30 22.549 1: 200 11.850


22.545 1: 200 11.737
19.812 1: 200 11.625

12.44 43.266 1: 200 11.990

12.44 26.374 1: 200 11.990


17.282 1: 200 11.858
28.784 1: 200 11.772

11.90 26.374 1: 200 11.450


46.966 1: 200 11.318

11.68 7.491 1: 200 11.230


36.850 1: 200 11.193
1.131 1: 200 11.008

12.86 19.812 1: 200 12.410


46.472 1: 200 12.311
45.248 1: 200 12.079
19.812 1: 200 11.852
12.28 13.601 1: 200 11.830
8.122 1: 200 11.762
16.914 1: 200 11.721
4.296 1: 200 11.637
19.812 1: 200 11.615
18.659 1: 200 11.516
12.736 1: 200 11.423
18.000 1: 200 11.359
19.812 1: 200 11.269
4.296 1: 200 11.170
16.914 1: 200 11.149
8.100 1: 200 11.064
5.426 1: 200 11.024

13.22 20.597 1: 200 12.770

13.22 21.882 1: 200 12.770

12.80 21.887 1: 200 12.350

12.36 8.320 1: 200 11.910


27.286 1: 200 11.868

12.36 31.083 1: 200 11.910

12.30 21.887 1: 200 11.850

12.44 21.882 1: 200 11.990

12.44 20.592 1: 200 11.990

11.90 13.601 1: 200 11.450


11.68 19.906 1: 200 11.230
1.166 1: 200 0.000

12.28 45.610 1: 200 11.830


45.610 1: 200 11.602
45.610 1: 200 11.374
45.610 1: 200 11.146
14.065 1: 200 10.918
6.105 1: 200 10.847
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS


Owner : - Date : 28/09/2018
Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI

Ground Level:
Minimum Depth: 0.6 m

Location Design Flow (10 years ARI)


1 2 3 4 5 6 8 9 9 10 11 12
Catchment Runoff Rainfall Design Cumul. Depth of
Drain Line Type of Drain Min. Depth Capacity Velocity Design Remark
Area (A) Coeff. (C) intensity Flow (Q) Flow (Q) HR
Ha mm/hr m3/s m3/s m m m3/s m/s
A1
0.042 0.90 324.05 0.034 0.034 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.1
0.077 0.90 324.05 0.062 0.096 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.2
0.061 0.90 324.05 0.049 0.145 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.3
0.041 0.90 324.05 0.033 0.258 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.4
0.052 0.90 324.05 0.042 0.328 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.5
0.092 0.90 324.05 0.075 0.403 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.6
0.051 0.90 324.05 0.041 0.548 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.7
0.038 0.90 324.05 0.030 1.046 300mm PC HR (W=750) 0.375 0.90 1.11 1.86 PASSED
A1/8
0.074 0.90 324.05 0.060 1.182 PC PIPE 300mm DIA 0.375 FAILED
OSD 1
A2 - A2.1 0.030 0.90 324.05 0.024 0.024 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A2.1 - A1.3 0.070 0.90 324.05 0.056 0.080 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.3

A3 - A3.1 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.1 - A3.2 0.051 0.90 324.05 0.041 0.072 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.2 - A3.3 0.032 0.90 324.05 0.026 0.098 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.3 - A3.4 0.032 0.90 324.05 0.026 0.318 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.4 - A7.2 0.050 0.90 324.05 0.040 0.390 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A7.2
A4 - A4.1 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A4.1 - A4.2 0.048 0.90 324.05 0.039 0.076 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A4.2 - A5.2 0.026 0.90 324.05 0.021 0.097 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A5.2

A5 - A5.1 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A5.1 - A5.2 0.048 0.90 324.05 0.039 0.076 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A5.2 - A3.3 0.026 0.90 324.05 0.021 0.194 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.3

A6 - A3.4 0.039 0.90 324.05 0.032 0.032 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A3.4

A7 - A7.1 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A7.1 - A7.2 0.039 0.90 324.05 0.031 0.062 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A7.2 - A1.7 0.020 0.90 324.05 0.016 0.468 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.7

A8 - A8.1 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A8.1 - A1.8 0.059 0.90 324.05 0.048 0.076 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.8

A9 - A9.1 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
A9.1 - A9.2 0.039 0.90 324.05 0.031 0.050 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
A9.2 - PT.EX1 0.056 0.90 324.05 0.045 0.095 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
PT.EX1

A10 - A1.4 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A10 - A10.1 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A10.1 - A10.2 0.061 0.90 324.05 0.049 0.077 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A10.2 - A1.6 0.033 0.90 324.05 0.027 0.104 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
A1.6
B1 - B1.1 0.042 0.90 324.05 0.034 0.034 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.1 - B1.2 0.021 0.90 324.05 0.017 0.051 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.2 - B1.3 0.021 0.90 324.05 0.017 0.068 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.3 - B1.4 0.019 0.90 324.05 0.015 0.107 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.4 - B1.5 0.022 0.90 324.05 0.018 0.156 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.5 - B1.6 0.035 0.90 324.05 0.028 0.221 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.6 - B1.7 0.032 0.90 324.05 0.026 0.286 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.7 - B1.8 0.033 0.90 324.05 0.027 0.332 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.8 - B1.9 0.035 0.90 324.05 0.028 0.351 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.9 -B1.10 0.022 0.90 324.05 0.018 0.401 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.10 -B1.11 0.019 0.90 324.05 0.015 0.447 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.11 -B1.12 0.018 0.90 324.05 0.015 0.462 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.12 - OSD 2 0.023 0.90 324.05 0.018 0.508 PC PIPE 300mm DIA 0.375 FAILED
OSD 2

B2 - B1.3 0.030 0.90 324.05 0.024 0.024 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.3

B3 - B1.4 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.4

B4 - B1.5 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.5

B5 - B5.1 0.014 0.90 324.05 0.012 0.012 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B5.1 - B1.6 0.033 0.90 324.05 0.027 0.039 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B1.6

B6 - B1.7 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B1.7

B7 - B1.8 0.046 0.90 324.05 0.037 0.037 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.8
B8 - B1.9 0.039 0.90 324.05 0.032 0.032 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B1.9

B9 - B1.10 0.038 0.90 324.05 0.031 0.031 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B1.10

B10 - B1.12 0.034 0.90 324.05 0.028 0.028 300mm PC HR (W=750) 0.375 0.60 0.61 1.64 PASSED
B1.12

B11 - B12 0.023 0.90 324.05 0.019 0.019 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
B12 - PT.EX2 0.021 0.90 324.05 0.017 0.036 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
PT.EX2

C1 - C2 0.030 0.90 324.05 0.025 0.025 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
C2 - C3 0.046 0.90 324.05 0.037 0.062 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
C3 - C4 0.046 0.90 324.05 0.037 0.099 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
C4 - C5 0.046 0.90 324.05 0.037 0.136 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
C5 - C6 0.027 0.90 324.05 0.022 0.158 300mm PC HR (W=300) 0.150 0.60 0.20 1.17 PASSED
C6 - OSD 1 0.037 0.90 324.05 0.030 0.188 PC PIPE 225mm DIA FAILED
OSD 1

OSD 1
Invert Level
12 12 12 13 14 15 15
Remarks
Ground Dropped Drop From
Length Gradient Invert Level Sump Level
Level Level Ground
m m m m 1: X m m

13.90 0.000 0.600 26.374 1: 200 13.300 -

13.90 0.132 0.732 46.967 1: 200 13.168 12.793

13.40 0.235 0.467 21.349 1: 200 12.933 12.558

12.70 0.107 -0.127 5.720 1: 200 12.827 12.452

12.70 0.029 -0.098 46.471 1: 200 12.798 12.423

12.28 0.232 -0.286 45.247 1: 200 12.566 12.191

11.71 0.226 -0.629 5.720 1: 200 12.339 11.964

11.71 0.029 -0.601 21.336 1: 200 12.311 11.936

11.40 0.107 -0.804 5.926 1: 200 12.204 11.829


11.30 0.030 -0.874 12.174 -

13.22 0.000 0.600 26.369 1: 200 12.620 -


13.06 0.132 0.572 46.966 1: 200 12.488 12.113
12.70 0.235 0.447 12.253 -

13.22 0.000 0.600 43.266 1: 200 12.620 -


12.86 0.216 0.456 43.266 1: 200 12.404 12.029
12.43 0.216 0.243 4.287 1: 200 12.187 11.812
12.43 0.021 0.264 43.266 1: 200 12.166 11.791
12.00 0.216 0.050 4.296 1: 200 11.950 11.575
12.00 0.021 0.072 11.928 -
12.80 0.000 0.600 22.550 1: 200 12.200 -
12.80 0.113 0.713 22.550 1: 200 12.087 11.712
12.26 0.113 0.285 4.301 1: 200 11.975 11.600
12.26 0.022 0.307 11.953 -

12.30 0.000 0.600 22.549 1: 200 11.700 -


12.30 0.113 0.713 22.545 1: 200 11.587 11.212
12.26 0.113 0.785 19.812 1: 200 11.475 11.100
12.43 0.099 1.055 11.375 -

12.44 0.000 0.600 43.266 1: 200 11.840 -


12.00 0.216 0.376 11.624 -

12.44 0.000 0.600 26.374 1: 200 11.840 -


12.18 0.132 0.472 17.282 1: 200 11.708 11.333
12.00 0.086 0.378 28.784 1: 200 11.622 11.247
11.71 0.144 0.232 11.478 -

11.90 0.000 0.600 26.374 1: 200 11.300 -


11.90 0.132 0.732 46.966 1: 200 11.168 10.793
11.40 0.235 0.467 10.933 -

11.68 0.000 0.600 7.491 1: 200 11.080 -


11.68 0.037 0.637 36.850 1: 200 11.043 10.893
11.48 0.184 0.622 1.131 1: 200 10.858 10.708
11.48 0.006 0.627 10.853 -

12.86 0.000 0.600 19.812 1: 200 12.260 -


12.86 0.099 0.699 46.472 1: 200 12.161 11.786
12.43 0.232 0.501 45.248 1: 200 11.929 11.554
12.60 0.226 0.898 19.812 1: 200 11.702 11.327
11.71 0.099 0.107 11.603 -
12.28 0.000 0.600 13.601 1: 200 11.680 -
13.90 0.068 2.288 8.122 1: 200 11.612 11.237
13.90 0.041 2.329 16.914 1: 200 11.571 11.196
13.17 0.085 1.683 4.296 1: 200 11.487 11.112
13.17 0.021 1.705 19.812 1: 200 11.465 11.090
12.80 0.099 1.434 18.659 1: 200 11.366 10.991
12.80 0.093 1.527 12.736 1: 200 11.273 10.898
12.80 0.064 1.591 18.000 1: 200 11.209 10.834
12.30 0.090 1.181 19.812 1: 200 11.119 10.744
12.67 0.099 1.650 4.296 1: 200 11.020 10.645
12.67 0.021 1.671 16.914 1: 200 10.999 10.624
11.90 0.085 0.986 8.100 1: 200 10.914 10.539
11.90 0.125 1.111 5.426 1: 200 10.874 10.499
11.70 0.027 0.938 10.762 -

13.22 0.000 0.600 20.597 1: 200 12.620 -


13.17 0.103 0.653 12.517 -

13.22 0.000 0.600 21.882 1: 200 12.620 -


13.17 0.109 0.659 12.511 -

12.80 0.000 0.600 21.887 1: 200 12.200 -


12.80 0.109 0.709 12.091 -

12.36 0.000 0.600 8.320 1: 200 11.760 -


12.35 0.042 0.632 27.286 1: 200 11.718 11.568
12.80 0.136 1.218 11.582 -

12.36 0.000 0.600 31.083 1: 200 11.760 -


12.80 0.155 1.195 11.605 -

12.30 0.000 0.600 21.887 1: 200 11.700 -


12.30 0.109 0.709 11.591 -
12.44 0.000 0.600 21.882 1: 200 11.840 -
12.67 0.109 0.939 11.731 -

12.44 0.000 0.600 20.592 1: 200 11.840 -


12.67 0.103 0.933 11.737 -

11.90 0.000 0.600 13.601 1: 200 11.300 -


11.90 0.068 0.668 11.232 -

11.68 0.000 0.600 19.906 1: 200 11.080 -


11.68 0.100 0.700 1.166 1: 200 10.980 10.830
11.97 0.006 0.990 - - - 10.975 -

12.28 0.000 0.600 45.610 1: 200 11.680 11.680


12.28 0.228 0.828 45.610 1: 200 11.452 11.302
12.28 0.228 1.056 45.610 1: 200 11.224 11.074
12.28 0.228 1.284 45.610 1: 200 10.996 10.846
12.28 0.228 1.512 14.065 1: 200 10.768 10.618
12.28 0.070 1.583 6.105 1: 200 10.697 10.697
11.40 0.031 0.733 10.667 -
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A1 0.042 0.90 324.05 0.034 0.034
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.1 0.077 0.90 324.05 0.062 0.096
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.2 0.061 0.90 324.05 0.049 0.145
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A1.3 0.041 0.90 324.05 0.033 0.258
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A1.4 0.052 0.90 324.05 0.042 0.328
A1 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.5 0.092 0.90 324.05 0.075 0.403
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.6 0.051 0.90 324.05 0.041 0.548
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A1.7 0.038 0.90 324.05 0.030 1.046
300mm PC HR (W=750) 0.075 0.75 1.21 2.49 PASSED
A1.8 0.074 0.90 324.05 0.060 1.182

A2 0.030 0.90 324.05 0.024 0.024


300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A2.1 0.070 0.90 324.05 0.056 0.080
A2
^ 300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.3 To A1.3

A3 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.1 0.051 0.90 324.05 0.041 0.072
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.2 0.032 0.90 324.05 0.026 0.098
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
A3
A3.3 0.032 0.90 324.05 0.026 0.318
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
A3.4 0.050 0.90 324.05 0.040 0.390
^ 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A7.2 To A7.2
CONTINUE HERE
A4 0.046 0.90 324.05 0.037 0.037
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A4.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A4
A4.2 0.026 0.90 324.05 0.021 0.097
^ 300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A5.2 To A5.2

A5 0.046 0.90 324.05 0.037 0.037


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5
A5.2 0.026 0.90 324.05 0.021 0.194
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.3 To A3.3

A6 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A6
A3.4 To A3.4

A7 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A7.1 0.039 0.90 324.05 0.031 0.062
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A7
A7.2 0.020 0.90 324.05 0.016 0.468
^ 300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
A1.7 To A1.7
CONTINUE HERE
A8 0.034 0.90 324.05 0.028 0.028
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A8.1 0.059 0.90 324.05 0.048 0.076
A8
^ 300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.8 To A1.8

A9 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A9.1 0.039 0.90 324.05 0.031 0.558
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A9
A9.2 0.056 0.90 324.05 0.045 1.973
^ 300mm PC HR (W=750) 0.075 0.90 2.22 3.71 PASSED
PT.EX1 To PT.EX1
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10-1
A1.4 To A1.4

A10 0.034 0.90 324.05 0.028 0.028


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10.1 0.061 0.90 324.05 0.049 0.077
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10-2
A10.2 0.033 0.90 324.05 0.027 0.104
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.6 To A1.6
CONTINUE HERE
B1 0.042 0.90 324.05 0.034 0.034
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
B1.1 0.021 0.90 324.05 0.017 0.051
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
B1.2 0.021 0.90 324.05 0.017 0.068
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
B1.3 0.019 0.90 324.05 0.015 0.107
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
B1.4 0.022 0.90 324.05 0.018 0.156
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
B1.5 0.035 0.90 324.05 0.028 0.221
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.6 0.032 0.90 324.05 0.026 0.286
B1 300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.7 0.033 0.90 324.05 0.027 0.332
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.8 0.035 0.90 324.05 0.028 0.351
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.9 0.022 0.90 324.05 0.018 0.401
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
B1.10 0.019 0.90 324.05 0.015 0.447
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.11 0.018 0.90 324.05 0.015 0.462
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.12 0.023 0.90 324.05 0.018 0.508

B2 0.030 0.90 324.05 0.024 0.024


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B2
B1.3 To B1.3

B3 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B3
B1.4 To B1.4

B4 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B4
B1.5 To B1.5

B5 0.014 0.90 324.05 0.012 0.012


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B5.1 0.033 0.90 324.05 0.027 0.039
B5
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.6 To B1.6

B6 0.023 0.90 324.05 0.019 0.019


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B6
B1.7 To B1.7

B7 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B7
B1.8 To B1.8

B8 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B8
B1.9 To B1.9

B9 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B9
B1.10 To B1.10
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
B10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B10
B1.12 To B1.12

B11 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B12 0.021 0.90 324.05 0.017 0.036
B11
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
PT.EX2 To PT.EX2

C1 0.030 0.90 324.05 0.025 0.025


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C2 0.046 0.90 324.05 0.037 0.062
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C3 0.046 0.90 324.05 0.037 0.099
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C
C4 0.046 0.90 324.05 0.037 0.136
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C5 0.027 0.90 324.05 0.022 0.158
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
C6 0.037 0.90 324.05 0.030 0.188

INLET OUTLET
Drain Cumulative Flow Drain Sump Cumulative Flow m3/s
Sump m3/s
A1.8 1.182
OSD 1 A9.2 1.370
C6 0.188

OSD 2 B1.12 0.508 A9.1 0.508


DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
A1 13.90 13.450 13.450 0.450 0.000
26.374 150 0.176
A1.1 13.90 13.274 13.199 0.626 26.374
46.967 100 0.470
A1.2 13.40 12.730 12.655 0.670 73.341
21.349 50 0.427
A1.3 12.70 12.228 12.131 0.472 94.690
5.720 50 0.114
A1.4 12.70 12.017 11.942 0.683 100.410
A1 46.471 150 0.310
A1.5 12.28 11.632 11.557 0.648 146.881
45.247 150 0.302
A1.6 11.71 11.255 11.070 0.455 192.129
5.720 50 0.114
A1.7 11.71 10.955 10.444 0.755 197.848
21.336 100 0.213
A1.8 11.40 10.230 10.155 1.170 219.184

A2 13.22 12.770 12.770 0.450 0.000


26.369 150 0.176
A2.1 13.06 12.594 12.519 0.466 26.369
A2
46.966 150 0.313
A1.3 12.70 12.206 12.131 0.494 73.335

A3 13.22 12.770 12.770 0.450 0.000


43.266 100 0.433
A3.1 12.86 12.337 12.262 0.523 43.266
43.266 100 0.433
A3.2 12.43 11.830 11.755 0.600 86.532
4.287 200 0.021
A3
A3.3 12.43 11.733 11.201 0.697 90.819
43.266 200 0.216
A3.4 12.00 10.985 10.910 1.015 134.085
4.296 150 0.029
A7.2 12.00 10.881 10.806 1.119 138.381

A4 12.80 12.350 12.350 0.450 0.000


22.550 200 0.113
A4.1 12.80 12.237 12.162 0.563 22.550
22.550 50 0.451
A4
A4.2 12.26 11.711 11.636 0.549 45.099
4.301 50 0.086
A5.2 12.26 11.550 11.475 0.710 49.400

A5 12.30 11.850 11.850 0.450 0.000


22.549 200 0.113
A5.1 12.30 11.737 11.662 0.563 22.549
22.545 200 0.113
A5
A5.2 12.26 11.550 11.475 0.710 45.094
19.812 100 0.198
A3.3 12.43 11.276 11.201 1.154 64.906

A6 12.44 11.990 11.990 0.450 0.000


43.266 50 0.865
A6
A3.4 12.00 11.125 10.910 0.875 43.266

A7 12.44 11.990 11.990 0.450 0.000


26.374 100 0.264
A7.1 12.18 11.726 11.651 0.454 26.374
17.282 150 0.115
A7
A7.2 12.00 11.536 10.806 0.464 43.656
28.784 100 0.288
A1.7 11.71 10.519 10.444 1.191 72.440

A8 11.90 11.450 11.450 0.450 0.000


26.374 200 0.132
A8.1 11.90 11.318 11.243 0.582 26.374
A8
46.966 150 0.313
A1.8 11.40 10.930 10.155 0.470 73.340

A9 11.68 11.230 11.230 0.450 0.000


7.491 200 0.037
A9.1 11.68 11.193 11.118 0.487 7.491
36.850 50 0.737
A9
A9.2 11.48 10.381 10.306 1.099 44.341
1.131 50 0.023
PT.EX1 11.48 10.283 10.208 1.197 45.471
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
A10 12.86 12.410 12.410 0.450 0.000
19.812 100 0.198
A10-1
A1.4 12.70 12.212 11.942 0.488 19.812

A10 12.86 12.410 12.410 0.450 0.000


46.472 100 0.465
A10.1 12.43 11.945 11.870 0.485 46.472
45.248 100 0.452
A10-2
A10.2 12.60 11.418 11.343 1.182 91.720
19.812 100 0.198
A1.6 11.71 11.145 11.070 0.565 111.532

B1 13.90 13.450 13.450 0.450 0.000


13.601 50 0.272
B1.1 13.90 13.178 13.103 0.722 13.601
8.122 50 0.162
B1.2 13.90 12.941 12.866 0.959 21.723
16.914 100 0.169
B1.3 13.17 12.696 12.592 0.474 38.637
4.296 100 0.043
B1.4 13.17 12.549 12.474 0.621 42.933
19.812 150 0.132
B1.5 12.80 12.342 12.166 0.458 62.745
18.659 200 0.093
B1.6 12.80 12.072 11.582 0.728 81.405
B1 12.736 200 0.064
B1.7 12.80 11.518 11.443 1.282 94.141
18.000 200 0.090
B1.8 12.30 11.353 11.278 0.947 112.140
19.812 200 0.099
B1.9 12.67 11.179 11.104 1.491 131.953
4.296 150 0.029
B1.10 12.67 11.076 11.001 1.594 136.249
16.914 100 0.169
B1.11 11.90 10.831 10.756 1.069 153.163
8.100 100 0.081
B1.12 11.90 10.675 10.600 1.225 161.263

B2 13.22 12.770 12.770 0.450 0.000


20.597 200 0.103
B2
B1.3 13.17 12.667 12.592 0.503 20.597

B3 13.22 12.770 12.770 0.450 0.000


21.882 200 0.109
B3
B1.4 13.17 12.661 12.474 0.509 21.882

B4 12.80 12.350 12.350 0.450 0.000


21.887 200 0.109
B4
B1.5 12.80 12.241 12.166 0.559 21.887

B5 12.36 11.910 11.910 0.450 0.000


8.320 200 0.042
B5.1 12.35 11.868 11.793 0.482 8.320
B5
27.286 200 0.136
B1.6 12.80 11.657 11.582 1.143 35.606

B6 12.36 11.910 11.910 0.450 0.000


31.083 200 0.155
B6
B1.7 12.80 11.755 11.443 1.045 31.083

B7 12.30 11.850 11.850 0.450 0.000


21.887 200 0.109
B7
B1.8 12.30 11.741 11.278 0.559 21.887

B8 12.44 11.990 11.990 0.450 0.000


21.882 200 0.109
B8
B1.9 12.67 11.881 11.104 0.789 21.882

B9 12.44 11.990 11.990 0.450 0.000


20.592 200 0.103
B9
B1.10 12.67 11.887 11.001 0.783 20.592
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
B10 11.90 11.450 11.450 0.450 0.000
13.601 200 0.068
B10
B1.12 11.90 11.382 10.600 0.518 13.601

B11 11.68 11.230 11.230 0.450 0.000


19.906 200 0.100
B12 11.68 11.130 11.055 0.550 19.906
B11
1.166 200 0.006
PT.EX2 11.97 11.050 10.975 0.915 21.072

C1 12.28 11.830 11.830 0.450 0.000


45.610 200 0.228
C2 12.28 11.602 11.527 0.678 45.610
45.610 200 0.228
C3 12.28 11.299 11.224 0.981 91.220
45.610 200 0.228
C
C4 12.28 10.996 10.921 1.284 136.830
45.610 200 0.228
C5 12.28 10.693 10.618 1.587 182.440
14.065 150 0.094
C6 12.28 10.524 10.449 1.756 196.505
Drainage Profile A1
14.500

14.000
13.90 13.90

13.500 13.450 13.40


13.274
13.199
13.000
12.730
12.655 12.70
12.70
12.500
12.228 12.28
Level (m)

12.131 Ground Level


12.000 12.017
11.942 Invert Level
11.71
11.71 Sump Level
11.632
11.557
11.500
11.40
11.255
11.000 11.070
10.955

10.500 10.444
10.230
10.155
10.000

9.500
0.000 50.000 100.000 150.000 200.000 250.000

Length (m)

Drainage Profile A2
14.000

13.500

13.22
13.06
13.000

12.770
12.70
12.594 Ground Level
Level (m)

12.500 12.519
Invert Level
Sump Level
12.206
12.131
12.000

11.500

11.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000

Length (m)

Drainage Profile A3
14.000

13.500

13.22
13.000
12.86
12.770

12.500
12.43
12.43
12.337
12.262
Ground Level
Level (m)

12.000 12.00
12.00 Invert Level
11.830 Sump Level
11.755
11.733
11.500

11.201
11.000 10.985
10.910
10.881
10.806

10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000

Length (m)
Drainage Profile A4
14.000

13.500

13.000
12.80 12.80

12.500
12.350
12.237 12.26 12.26
12.162 Ground Level
Level (m)

12.000 Invert Level


Sump Level
11.711
11.636
11.500 11.550
11.475

11.000

10.500

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000

Length (m)

14.000 Drainage Profile A5

13.500

13.000

12.500
12.43
12.30 12.30 12.26
Level (m)

12.000
11.850
11.737
11.662
11.500 11.550
11.475
11.276
11.201
11.000
Ground Level
Invert Level
Sump Level
10.500

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000

Length (m)

Drainage Profile A6
13.000

12.500
12.44

12.000 11.990 12.00

Ground Level
Level (m)

11.500 Invert Level


Sump Level

11.125
11.000
10.910

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)
11.500

Level (
Invert Level
Sump Level

11.125
11.000
10.910

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)

Drainage Profile A7
13.000

12.500
12.44

12.18

12.000 11.990 12.00

11.726 11.71
11.651
Ground Level
Level (m)

11.500 11.536
Invert Level
Sump Level

11.000

10.806

10.500 10.519
10.444

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000

Length (m)

Drainage Profile A8
13.000

12.500

12.000
11.90 11.90

11.500 11.450 11.40


11.318
11.243
Ground Level
Level (m)

11.000 Invert Level


10.930
Sump Level

10.500

10.155
10.000

9.500

9.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000

Length (m)

Drainage Profile A9
12.000

11.800

11.68 11.68
11.600

11.48
11.48
11.400

11.230
11.200 11.193
11.118
Ground Level
Level (m)

11.000 Invert Level


Sump Level
10.800

10.600

10.400 10.381
10.306
10.283
10.200 10.208

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)
Sump Level

L
10.800

10.600

10.400 10.381
10.306
10.283
10.200 10.208

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)

Drainage Profile A10-1

12.900
12.86

12.700 12.70

12.500

12.410

12.300 Ground Level


Level (m)

12.212 Invert Level


Sump Level
12.100

11.942
11.900

11.700

11.500
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile A10-2


13.000
12.86

12.60
12.500
12.410 12.43

12.000
11.945
11.870
11.71
Ground Level
Level (m)

11.500 Invert Level


11.418
11.343 Sump Level
11.145
11.070
11.000

10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000

Length (m)
Drainage Profile B1
14.500

14.000
13.90 13.90 13.90

13.500 13.450

13.178 13.17
13.17
13.103
13.000 12.941
12.866 12.80 12.80 12.80
12.696 12.67
12.67
12.592
12.549
12.500 12.474
Ground Level
Level (m)

12.342 12.30
12.166 Invert Level
12.072 Sump Level
12.000
11.90 11.90

11.582 11.518
11.500 11.443
11.353
11.278
11.179
11.104
11.076
11.000 11.001
10.831
10.756
10.675
10.600
10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000 180.000

Length (m)

Drainage Profile B2
13.400

13.200 13.22
13.17

13.000

12.800
12.770
Ground Level
Level (m)

12.667 Invert Level


12.600 Sump Level
12.592

12.400

12.200

12.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile B3
13.400

13.200 13.22
13.17

13.000

12.800
12.770
Ground Level
Level (m)

Invert Level
12.661
Sump Level
12.600

12.474
12.400

12.200

12.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)
Drainage Profile B4
13.000

12.800 12.80 12.80

12.600

12.400
12.350
Level (m)

Ground Level
Invert Level
12.241
12.200 Sump Level
12.166

12.000

11.800

11.600
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile B5
13.000

12.800 12.80

12.600

12.400
12.36 12.35

12.200

Ground Level
Level (m)

12.000 Invert Level


11.910 Sump Level
11.868
11.800 11.793

11.657
11.600 11.582

11.400

11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000

Length (m)

Drainage Profile B6
13.000

12.800 12.80

12.600

12.400
12.36

12.200

Ground Level
Level (m)

12.000 Invert Level


11.910 Sump Level
11.800
11.755

11.600

11.443
11.400

11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000

Length (m)
L
11.800
11.755

11.600

11.443
11.400

11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000

Length (m)

Drainage Profile B7

12.400

12.30 12.30

12.200

12.000

11.850
11.800 Ground Level
Level (m)

11.741
Invert Level
Sump Level
11.600

11.400

11.278
11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile B8
13.000

12.67
12.500
12.44

12.000 11.990
11.881

Ground Level
Level (m)

11.500 Invert Level


Sump Level

11.104
11.000

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile B9
13.000

12.67
12.500
12.44

12.000 11.990
11.887

Ground Level
Level (m)

11.500 Invert Level


Sump Level

11.000 11.001

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)
12.000 11.990
11.887

Ground Level

Level (m)
11.500 Invert Level
Sump Level

11.000 11.001

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile B10


12.500

12.000
11.90 11.90

11.500
11.450
11.382
Ground Level
Level (m)

Invert Level
Sump Level
11.000

10.600
10.500

10.000
0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000

Length (m)

Drainage Profile B11


12.200

12.000
11.97

11.800

11.68 11.68

11.600
Ground Level
Level (m)

Invert Level
Sump Level
11.400

11.230
11.200
11.130
11.055 11.050
11.000
10.975

10.800
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile C
12.500

12.28 12.28 12.28 12.28 12.28 12.28

12.000

11.830

11.602
11.500 11.527

Ground Level
Level (m)

11.299
11.224 Invert Level
Sump Level
11.000 10.996
10.921

10.693
10.618
10.500 10.524
10.449
12.500

12.28 12.28 12.28 12.28 12.28 12.28

12.000

11.830

11.602
11.500 11.527

Ground Level

Level (m)
11.299
11.224 Invert Level
Sump Level
11.000 10.996
10.921

10.693
10.618
10.500 10.524
10.449

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000 180.000 200.000

Length (m)
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A1 0.042 0.90 324.05 0.034 0.034
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.1 0.077 0.90 324.05 0.062 0.096
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.2 0.061 0.90 324.05 0.049 0.145
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A1.3 0.041 0.90 324.05 0.033 0.258
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A1.4 0.052 0.90 324.05 0.042 0.328
A1 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.5 0.092 0.90 324.05 0.075 0.403
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.6 0.051 0.90 324.05 0.041 0.548
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A1.7 0.038 0.90 324.05 0.030 1.046
300mm PC HR (W=750) 0.075 0.75 1.21 2.49 PASSED
A1.8 0.074 0.90 324.05 0.060 1.182

A2 0.030 0.90 324.05 0.024 0.024


300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A2.1 0.070 0.90 324.05 0.056 0.080
A2
^ 300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.3 To A1.3

A3 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.1 0.051 0.90 324.05 0.041 0.072
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.2 0.032 0.90 324.05 0.026 0.098
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
A3
A3.3 0.032 0.90 324.05 0.026 0.318
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
A3.4 0.050 0.90 324.05 0.040 0.390
^ 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A7.2 To A7.2

A4 0.046 0.90 324.05 0.037 0.037


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A4.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A4
A4.2 0.026 0.90 324.05 0.021 0.097
^ 300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A5.2 To A5.2

A5 0.046 0.90 324.05 0.037 0.037


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5
A5.2 0.026 0.90 324.05 0.021 0.194
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.3 To A3.3

A6 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A6
A3.4 To A3.4

A7 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A7.1 0.039 0.90 324.05 0.031 0.062
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A7
A7.2 0.020 0.90 324.05 0.016 0.468
^ 300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
A1.7 To A1.7

A8 0.034 0.90 324.05 0.028 0.028


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A8.1 0.059 0.90 324.05 0.048 0.076
A8
^ 300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.8 To A1.8

A9 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A9.1 0.039 0.90 324.05 0.031 0.558
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A9
A9.2 0.056 0.90 324.05 0.045 1.973
^ 300mm PC HR (W=750) 0.075 0.90 2.22 3.71 PASSED
PT.EX1 To PT.EX1
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10-1
A1.4 To A1.4

A10 0.034 0.90 324.05 0.028 0.028


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10.1 0.061 0.90 324.05 0.049 0.077
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10-2
A10.2 0.033 0.90 324.05 0.027 0.104
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.6 To A1.6

B1 0.042 0.90 324.05 0.034 0.034


300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
B1.1 0.021 0.90 324.05 0.017 0.051
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
B1.2 0.021 0.90 324.05 0.017 0.068
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
B1.3 0.019 0.90 324.05 0.015 0.107
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
B1.4 0.022 0.90 324.05 0.018 0.156
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
B1.5 0.035 0.90 324.05 0.028 0.221
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.6 0.032 0.90 324.05 0.026 0.286
B1 300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.7 0.033 0.90 324.05 0.027 0.332
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.8 0.035 0.90 324.05 0.028 0.351
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.9 0.022 0.90 324.05 0.018 0.401
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
B1.10 0.019 0.90 324.05 0.015 0.447
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.11 0.018 0.90 324.05 0.015 0.462
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.12 0.023 0.90 324.05 0.018 0.508

B2 0.030 0.90 324.05 0.024 0.024


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B2
B1.3 To B1.3

B3 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B3
B1.4 To B1.4

B4 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B4
B1.5 To B1.5

B5 0.014 0.90 324.05 0.012 0.012


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B5.1 0.033 0.90 324.05 0.027 0.039
B5
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.6 To B1.6

B6 0.023 0.90 324.05 0.019 0.019


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B6
B1.7 To B1.7

B7 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B7
B1.8 To B1.8

B8 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B8
B1.9 To B1.9

B9 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B9
B1.10 To B1.10
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
B10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B10
B1.12 To B1.12

B11 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B12 0.021 0.90 324.05 0.017 0.036
B11
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
PT.EX2 To PT.EX2

C1 0.030 0.90 324.05 0.025 0.025


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C2 0.046 0.90 324.05 0.037 0.062
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C3 0.046 0.90 324.05 0.037 0.099
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C
C4 0.046 0.90 324.05 0.037 0.136
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C5 0.027 0.90 324.05 0.022 0.158
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
C6 0.037 0.90 324.05 0.030 0.188

INLET OUTLET
Drain Cumulative Flow Drain Sump Cumulative Flow m3/s
Sump m3/s
A1.8 1.182
OSD 1 A9.2 1.370
C6 0.188

OSD 2 B1.12 0.508 A9.1 0.508


DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
A1 13.90 13.450 13.450 0.450 0.000
26.374 150 0.176
A1.1 13.90 13.274 13.199 0.626 26.374
46.967 100 0.470
A1.2 13.40 12.730 12.655 0.670 73.341
21.349 50 0.427
A1.3 12.70 12.228 12.131 0.472 94.690
5.720 50 0.114
A1.4 12.70 12.017 11.942 0.683 100.410
A1 46.471 150 0.310
A1.5 12.28 11.632 11.557 0.648 146.881
45.247 150 0.302
A1.6 11.71 11.255 11.070 0.455 192.129
5.720 50 0.114
A1.7 11.71 10.955 10.444 0.755 197.848
21.336 100 0.213
A1.8 11.40 10.230 10.155 1.170 219.184

A2 13.22 12.770 12.770 0.450 0.000


26.369 150 0.176
A2.1 13.06 12.594 12.519 0.466 26.369
A2
46.966 150 0.313
A1.3 12.70 12.206 12.131 0.494 73.335

A3 13.22 12.770 12.770 0.450 0.000


43.266 100 0.433
A3.1 12.86 12.337 12.262 0.523 43.266
43.266 100 0.433
A3.2 12.43 11.830 11.755 0.600 86.532
4.287 200 0.021
A3
A3.3 12.43 11.733 11.201 0.697 90.819
43.266 200 0.216
A3.4 12.00 10.985 10.910 1.015 134.085
4.296 150 0.029
A7.2 12.00 10.881 10.806 1.119 138.381

A4 12.80 12.350 12.350 0.450 0.000


22.550 200 0.113
A4.1 12.80 12.237 12.162 0.563 22.550
22.550 50 0.451
A4
A4.2 12.26 11.711 11.636 0.549 45.099
4.301 50 0.086
A5.2 12.26 11.550 11.475 0.710 49.400

A5 12.30 11.850 11.850 0.450 0.000


22.549 200 0.113
A5.1 12.30 11.737 11.662 0.563 22.549
22.545 200 0.113
A5
A5.2 12.26 11.550 11.475 0.710 45.094
19.812 100 0.198
A3.3 12.43 11.276 11.201 1.154 64.906

A6 12.44 11.990 11.990 0.450 0.000


43.266 50 0.865
A6
A3.4 12.00 11.125 10.910 0.875 43.266

A7 12.44 11.990 11.990 0.450 0.000


26.374 100 0.264
A7.1 12.18 11.726 11.651 0.454 26.374
17.282 150 0.115
A7
A7.2 12.00 11.536 10.806 0.464 43.656
28.784 100 0.288
A1.7 11.71 10.519 10.444 1.191 72.440

A8 11.90 11.450 11.450 0.450 0.000


26.374 200 0.132
A8.1 11.90 11.318 11.243 0.582 26.374
A8
46.966 150 0.313
A1.8 11.40 10.930 10.155 0.470 73.340

A9 11.68 11.230 11.230 0.450 0.000


7.491 200 0.037
A9.1 11.68 11.193 11.118 0.487 7.491
36.850 50 0.737
A9
A9.2 11.48 10.381 10.306 1.099 44.341
1.131 50 0.023
PT.EX1 11.48 10.283 10.208 1.197 45.471
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
A10 12.86 12.410 12.410 0.450 0.000
19.812 100 0.198
A10-1
A1.4 12.70 12.212 11.942 0.488 19.812

A10 12.86 12.410 12.410 0.450 0.000


46.472 100 0.465
A10.1 12.43 11.945 11.870 0.485 46.472
45.248 100 0.452
A10-2
A10.2 12.60 11.418 11.343 1.182 91.720
19.812 100 0.198
A1.6 11.71 11.145 11.070 0.565 111.532

B1 13.90 13.450 13.450 0.450 0.000


13.601 50 0.272
B1.1 13.90 13.178 13.103 0.722 13.601
8.122 50 0.162
B1.2 13.90 12.941 12.866 0.959 21.723
16.914 100 0.169
B1.3 13.17 12.696 12.592 0.474 38.637
4.296 100 0.043
B1.4 13.17 12.549 12.474 0.621 42.933
19.812 150 0.132
B1.5 12.80 12.342 12.166 0.458 62.745
18.659 200 0.093
B1.6 12.80 12.072 11.582 0.728 81.405
B1 12.736 200 0.064
B1.7 12.80 11.518 11.443 1.282 94.141
18.000 200 0.090
B1.8 12.30 11.353 11.278 0.947 112.140
19.812 200 0.099
B1.9 12.67 11.179 11.104 1.491 131.953
4.296 150 0.029
B1.10 12.67 11.076 11.001 1.594 136.249
16.914 100 0.169
B1.11 11.90 10.831 10.756 1.069 153.163
8.100 100 0.081
B1.12 11.90 10.675 10.600 1.225 161.263

B2 13.22 12.770 12.770 0.450 0.000


20.597 200 0.103
B2
B1.3 13.17 12.667 12.592 0.503 20.597

B3 13.22 12.770 12.770 0.450 0.000


21.882 200 0.109
B3
B1.4 13.17 12.661 12.474 0.509 21.882

B4 12.80 12.350 12.350 0.450 0.000


21.887 200 0.109
B4
B1.5 12.80 12.241 12.166 0.559 21.887

B5 12.36 11.910 11.910 0.450 0.000


8.320 200 0.042
B5.1 12.35 11.868 11.793 0.482 8.320
B5
27.286 200 0.136
B1.6 12.80 11.657 11.582 1.143 35.606

B6 12.36 11.910 11.910 0.450 0.000


31.083 200 0.155
B6
B1.7 12.80 11.755 11.443 1.045 31.083

B7 12.30 11.850 11.850 0.450 0.000


21.887 200 0.109
B7
B1.8 12.30 11.741 11.278 0.559 21.887

B8 12.44 11.990 11.990 0.450 0.000


21.882 200 0.109
B8
B1.9 12.67 11.881 11.104 0.789 21.882

B9 12.44 11.990 11.990 0.450 0.000


20.592 200 0.103
B9
B1.10 12.67 11.887 11.001 0.783 20.592
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Invert Level Design


1 13 14 15 16 17 18 19 20

Drain Sump Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
PROFILE Level (1:X) Drop Level Length
m m X m m m m m
B10 11.90 11.450 11.450 0.450 0.000
13.601 200 0.068
B10
B1.12 11.90 11.382 10.600 0.518 13.601

B11 11.68 11.230 11.230 0.450 0.000


19.906 200 0.100
B12 11.68 11.130 11.055 0.550 19.906
B11
1.166 200 0.006
PT.EX2 11.97 11.050 10.975 0.915 21.072

C1 12.28 11.830 11.830 0.450 0.000


45.610 200 0.228
C2 12.28 11.602 11.527 0.678 45.610
45.610 200 0.228
C3 12.28 11.299 11.224 0.981 91.220
45.610 200 0.228
C
C4 12.28 10.996 10.921 1.284 136.830
45.610 200 0.228
C5 12.28 10.693 10.618 1.587 182.440
14.065 150 0.094
C6 12.28 10.524 10.449 1.756 196.505

Gradient Ranges = Steepest = 1: 50


Gentle = 1: 200

Deepest Sump Level = 10.155 m


13.450

Deepest Invert Level Drop = 1.756 m


Drainage Profile A1
14.500

14.000 13.90 13.90


13.500 13.450 13.40
13.274
13.199
13.000
12.730
12.655 12.70
12.70
12.500
12.228 12.28
Level (m)

12.131 Ground Level


12.000 12.017
11.942 Invert Level
11.632 11.71
11.71
11.500 11.557 Sump Level
11.40
11.255
11.000 11.070
10.955
10.500 10.444
10.230
10.155
10.000

9.500
0.000 50.000 100.000 150.000 200.000 250.000
Length (m)

Drainage Profile A2

14.000

13.500

13.22
13.06
13.000
12.770
12.70
12.594
Level (m)

Ground Level
12.500 12.519
Invert Level
Sump Level
12.206
12.131
12.000

11.500

11.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000

Length (m)

Drainage Profile A3

14.000

13.500
13.22
13.000
12.86
12.770
12.500 12.43
12.43
12.337
12.262
Level (m)

Ground Level
12.000 12.00
12.00
Invert Level
11.830
11.755
11.733 Sump Level
11.500

11.201
11.000 10.985
10.910
10.881
10.806

10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000

Length (m)
Drainage Profile A4
14.000

13.500

13.000
12.80 12.80
12.500
12.350
12.237 12.26 12.26
12.162
Level (m)

Ground Level
12.000
Invert Level
11.711
11.636 Sump Level
11.500 11.550
11.475

11.000

10.500

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000
Length (m)

14.000 Drainage Profile A5

13.500

13.000

12.500 12.43
12.30 12.30 12.26
Level (m)

12.000
11.850
11.737
11.662
11.500 11.550
11.475
11.276
11.201
11.000 Ground Level
Invert Level
Sump Level
10.500

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000
Length (m)

Drainage Profile A6
13.000

12.500
12.44

12.000 11.990 12.00


Level (m)

Ground Level
11.500
Invert Level
Sump Level
11.125
11.000
10.910

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000
Length (m)
11.000
10.910

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)

Drainage Profile A7
13.000

12.500 12.44
12.18
12.000 11.990 12.00

11.726 11.71
11.651
Level (m)

11.536 Ground Level


11.500
Invert Level
Sump Level
11.000
10.806

10.500 10.519
10.444

10.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000
Length (m)

Drainage Profile A8
13.000

12.500

12.000
11.90 11.90

11.500 11.450
11.318 11.40
11.243
Level (m)

Ground Level
11.000 10.930 Invert Level
Sump Level
10.500
10.155
10.000

9.500

9.000
0.000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000
Length (m)

Drainage Profile A9

12.000

11.800
11.68 11.68
11.600
11.48
11.48
11.400

11.200 11.230 11.193


11.118
Level (m)

Ground Level
11.000
Invert Level
Sump Level
10.800

10.600

10.400 10.381
10.306
10.283
10.200 10.208

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)
10.800

10.600

10.400 10.381
10.306
10.283
10.200 10.208

10.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000

Length (m)

Drainage Profile A10-1

12.900
12.86

12.700 12.70

12.500
12.410

12.300
Level (m)

Ground Level
12.212 Invert Level
Sump Level
12.100

11.942
11.900

11.700

11.500
0.000 5.000 10.000 15.000 20.000 25.000

Length (m)

Drainage Profile A10-2

13.000
12.86

12.60
12.500
12.410 12.43

12.000
11.945
11.870
11.71
Level (m)

Ground Level
11.500
11.418 Invert Level
11.343 Sump Level
11.145
11.070
11.000

10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000

Length (m)
Drainage Profile B1

14.500

14.000
13.90 13.9013.90

13.500 13.450
13.178
13.103 13.17
13.17
13.000 12.941
12.866 12.80 12.80 12.80
12.696 12.67
12.67
12.592
12.549
12.500 12.474
Level (m)

12.342 12.30 Ground Level


12.166 Invert Level
12.000 12.072
11.9011.90 Sump Level

11.500 11.582 11.518


11.443 11.353
11.278
11.179
11.104
11.000 11.076
11.001
10.831
10.756
10.675
10.600
10.500

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000 180.000

Length (m)

Drainage Profile B2
13.400

13.200 13.22
13.17

13.000

12.800 12.770
Level (m)

Ground Level
12.667 Invert Level
12.600 12.592 Sump Level

12.400

12.200

12.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile B3
13.400

13.200 13.22
13.17

13.000

12.800
12.770
Level (m)

Ground Level
12.661 Invert Level
12.600 Sump Level
12.474
12.400

12.200

12.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)
Drainage Profile B4
13.000

12.800 12.80 12.80

12.600

12.400
12.350
Level (m)

Ground Level
12.241 Invert Level
12.200 Sump Level
12.166

12.000

11.800

11.600
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile B5
13.000

12.800 12.80

12.600

12.400 12.36 12.35


12.200
Level (m)

Ground Level
12.000
11.910 Invert Level
11.868 Sump Level
11.800 11.793
11.657
11.600 11.582
11.400

11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000
Length (m)

Drainage Profile B6
13.000

12.800 12.80

12.600

12.400 12.36
12.200
Level (m)

Ground Level
12.000
11.910 Invert Level
11.800 Sump Level
11.755
11.600
11.443
11.400

11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000 30.000 35.000
Length (m)
Drainage Profile B7

12.400
12.30 12.30
12.200

12.000

11.850
11.800
Level (m)

11.741 Ground Level


Invert Level
11.600 Sump Level

11.400
11.278
11.200

11.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile B8
13.000

12.67
12.500 12.44

12.000 11.990
11.881
Level (m)

Ground Level
11.500
Invert Level
Sump Level
11.104
11.000

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile B9
13.000

12.67
12.500 12.44

12.000 11.990
11.887
Level (m)

Ground Level
11.500
Invert Level
Sump Level
11.000 11.001

10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)
10.500

10.000
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile B10


12.500

12.000
11.90 11.90

11.500 11.450
11.382
Level (m)

Ground Level
Invert Level
11.000 Sump Level

10.600
10.500

10.000
0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000
Length (m)

Drainage Profile B11


12.200

12.000
11.97

11.800

11.68 11.68
11.600
Level (m)

Ground Level
Invert Level
11.400 Sump Level

11.230
11.200
11.130
11.055
11.050
11.000 10.975

10.800
0.000 5.000 10.000 15.000 20.000 25.000
Length (m)

Drainage Profile C
12.500
12.28 12.28 12.28 12.28 12.28 12.28

12.000
11.830
11.602
11.500 11.527
Level (m)

11.299 Ground Level


11.224 Invert Level
11.000 10.996 Sump Level
10.921
10.693
10.618
10.500 10.524
10.449

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000 180.000 200.000
Length (m)
11.224 Invert Level

Level
11.000 10.996 Sump Level
10.921
10.693
10.618
10.500 10.524
10.449

10.000
0.000 20.000 40.000 60.000 80.000 100.000 120.000 140.000 160.000 180.000 200.000
Length (m)
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A1 0.042 0.90 324.05 0.034 0.034
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.1 0.077 0.90 324.05 0.062 0.096
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.2 0.061 0.90 324.05 0.049 0.145
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A1.3 0.041 0.90 324.05 0.033 0.258
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A1.4 0.052 0.90 324.05 0.042 0.328
A1 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.5 0.092 0.90 324.05 0.075 0.403
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A1.6 0.051 0.90 324.05 0.041 0.548
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A1.7 0.038 0.90 324.05 0.030 1.046
300mm PC HR (W=750) 0.075 0.75 1.21 2.49 PASSED
A1.8 0.074 0.90 324.05 0.060 1.182

A2 0.030 0.90 324.05 0.024 0.024


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A2.1 0.070 0.90 324.05 0.056 0.080
A2
^ 300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
A1.3 To A1.3

A3 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
A3.1 0.051 0.90 324.05 0.041 0.072
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A3.2 0.032 0.90 324.05 0.026 0.098
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A3
A3.3 0.032 0.90 324.05 0.026 0.318
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
A3.4 0.050 0.90 324.05 0.040 0.390
^ 300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
A7.2 To A7.2

A4 0.046 0.90 324.05 0.037 0.037


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A4.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A4
A4.2 0.026 0.90 324.05 0.021 0.097
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5.2 To A5.2

A5 0.046 0.90 324.05 0.037 0.037


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5.1 0.048 0.90 324.05 0.039 0.076
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A5
A5.2 0.026 0.90 324.05 0.021 0.194
^ 300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A3.3 To A3.3

A6 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A6
A3.4 To A3.4

A7 0.038 0.90 324.05 0.031 0.031


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A7.1 0.039 0.90 324.05 0.031 0.062
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A7
A7.2 0.020 0.90 324.05 0.016 0.468
^ 300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
A1.7 To A1.7

A8 0.034 0.90 324.05 0.028 0.028


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A8.1 0.059 0.90 324.05 0.048 0.076
A8
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A1.8 To A1.8

A9 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A9.1 0.039 0.90 324.05 0.031 0.558
300mm PC HR (W=750) 0.075 0.45 0.76 2.91 PASSED
A9
A9.2 0.056 0.90 324.05 0.045 1.973
^ 900mm Dia PC Pipe Culvert 0.075 - 2.14 3.36 PASSED
PT.EX1 To PT.EX1
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12
A9
Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
A10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A10-1
A1.4 To A1.4

A10 0.034 0.90 324.05 0.028 0.028


300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10.1 0.061 0.90 324.05 0.049 0.077
300mm PC HR (W=300) 0.075 0.45 0.20 1.59 PASSED
A10-2
A10.2 0.033 0.90 324.05 0.027 0.104
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
A1.6 To A1.6

B1 0.042 0.90 324.05 0.034 0.034


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.1 0.021 0.90 324.05 0.017 0.051
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.2 0.021 0.90 324.05 0.017 0.068
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.3 0.019 0.90 324.05 0.015 0.107
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.4 0.022 0.90 324.05 0.018 0.156
300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
B1.5 0.035 0.90 324.05 0.028 0.221
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.6 0.032 0.90 324.05 0.026 0.286
B1 300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.7 0.033 0.90 324.05 0.027 0.332
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.8 0.035 0.90 324.05 0.028 0.351
300mm PC HR (W=750) 0.075 0.45 0.38 1.45 PASSED
B1.9 0.022 0.90 324.05 0.018 0.401
300mm PC HR (W=750) 0.075 0.45 0.44 1.68 PASSED
B1.10 0.019 0.90 324.05 0.015 0.447
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.11 0.018 0.90 324.05 0.015 0.462
300mm PC HR (W=750) 0.075 0.45 0.53 2.05 PASSED
B1.12 0.023 0.90 324.05 0.018 0.508

B2 0.030 0.90 324.05 0.024 0.024


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B2
B1.3 To B1.3

B3 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B3
B1.4 To B1.4

B4 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B4
B1.5 To B1.5

B5 0.014 0.90 324.05 0.012 0.012


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B5.1 0.033 0.90 324.05 0.027 0.039
B5
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B1.6 To B1.6

B6 0.023 0.90 324.05 0.019 0.019


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B6
B1.7 To B1.7

B7 0.046 0.90 324.05 0.037 0.037


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B7
B1.8 To B1.8

B8 0.039 0.90 324.05 0.032 0.032


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B8
B1.9 To B1.9

B9 0.038 0.90 324.05 0.031 0.031


^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B9
B1.10 To B1.10
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Location Design Flow (10 years ARI) Design Capacity


1 2 3 4 5 6 7 8 9 10 11 12

Drain Sump Catchment Runoff Rainfall Design Cumul. Flow Type of Drain Drop from Invert Min. Depth Capacity Velocity Capacity
PROFILE Area (A) Coeff. (C) intensity Flow (Q) (Q) to Sump Remark
Ha mm/hr m3/s m3/s m m m3/s m/s
B10 0.034 0.90 324.05 0.028 0.028
^ 300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B10
B1.12 To B1.12

B11 0.023 0.90 324.05 0.019 0.019


300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
B12 0.021 0.90 324.05 0.017 0.036
B11
^ 300mm Dia PC Pipe Culvert 0.075 - 0.07 0.93 PASSED
PT.EX2 To PT.EX2

C1 0.030 0.90 324.05 0.025 0.025


300mm PC HR (W=300) 0.075 0.45 0.28 2.26 PASSED
C2 0.046 0.90 324.05 0.037 0.062
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C3 0.046 0.90 324.05 0.037 0.099
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C
C4 0.046 0.90 324.05 0.037 0.136
300mm PC HR (W=300) 0.075 0.45 0.14 1.13 PASSED
C5 0.027 0.90 324.05 0.022 0.158
300mm PC HR (W=300) 0.075 0.45 0.16 1.30 PASSED
C6 0.037 0.90 324.05 0.030 0.188

INLET OUTLET
Drain Cumulative Flow Drain Sump Cumulative Flow m3/s
Sump m3/s
A1.8 1.182
OSD 1 A9.2 1.370
C6 0.188

OSD 2 B1.12 0.508 A9.1 0.508


DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Invert Level Design


13 14 15 16 17 18 19 20
Proposed Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
Level (1:X) Drop Level Length
m m X m m m m m
13.70 13.250 13.250 0.450 0.000
26.169174 150 0.174
13.55 13.076 13.001 0.474 26.169
46.49412 100 0.465
13.25 12.536 12.461 0.714 72.663
21.636 100 0.216
12.70 12.244 12.127 0.456 94.299
5.848 50 0.117
12.70 12.010 11.935 0.690 100.148
45.830 150 0.306
12.30 11.630 11.555 0.670 145.978
45.416 150 0.303
11.80 11.252 11.064 0.548 191.395
5.818 50 0.116
11.80 10.948 10.400 0.852 197.213
21.136 100 0.211
11.35 10.189 10.114 1.161 218.349

13.30 12.850 12.850 0.450 0.000


26.167 100 0.262
13.10 12.588 12.513 0.512 26.167
46.694 150 0.311
12.70 12.202 12.127 0.498 72.861

13.30 12.850 12.850 0.450 0.000


42.928 50 0.859
12.75 11.991 11.916 0.759 42.928
43.261 200 0.216
12.30 11.700 11.625 0.600 86.190
4.247 200 0.021
12.30 11.604 11.155 0.696 90.437
43.260 200 0.216
11.85 10.939 10.864 0.911 133.697
4.446 150 0.030
11.85 10.834 10.759 1.016 138.143

12.75 12.300 12.300 0.450 0.000


22.216 100 0.222
12.75 12.078 12.003 0.672 22.216
22.550 100 0.225
12.30 11.777 11.702 0.523 44.766
4.296 200 0.021
12.30 11.681 11.426 0.619 49.062

12.25 11.800 11.800 0.450 0.000


22.216 200 0.111
12.30 11.689 11.614 0.611 22.216
22.549 200 0.113
12.30 11.501 11.426 0.799 44.766
19.582 100 0.196
12.30 11.230 11.155 1.070 64.348

11.95 11.500 11.500 0.450 0.000


43.033 200 0.215
11.85 11.285 10.864 0.565 43.033

11.95 11.500 11.500 0.450 0.000


26.172 200 0.131
11.90 11.369 11.294 0.531 26.172
17.282 200 0.086
11.85 11.208 10.759 0.642 43.454
28.452 100 0.285
11.80 10.475 10.400 1.325 71.906

11.65 11.200 11.200 0.450 0.000


26.172 100 0.262
11.40 10.938 10.863 0.462 26.172
46.494 200 0.232
11.35 10.631 10.114 0.719 72.666

11.65 11.200 11.200 0.450 0.000


6.536 200 0.033
11.65 11.167 11.092 0.483 6.536
37.500 50 0.750
11.20 10.342 10.267 0.858 44.036
0.423 100 0.004
11.20 10.263 - 0.937 44.459
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Invert Level Design


13 14 15 16 17 18 19 20
Proposed Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
Level (1:X) Drop Level Length
m m X m m m m m
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Invert Level Design


13 14 15 16 17 18 19 20
Proposed Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
Level (1:X) Drop Level Length
m m X m m m m m
12.75 12.300 12.300 0.450 0.000
19.812 200 0.099
12.70 12.201 11.935 0.499 19.812

12.75 12.300 12.300 0.450 0.000


45.830 100 0.458
12.30 11.842 11.767 0.458 45.830
45.316 100 0.453
11.85 11.314 11.239 0.536 91.147
19.812 200 0.099
11.80 11.139 11.064 0.661 110.959

13.70 13.250 13.250 0.450 0.000


13.806 200 0.069
13.75 13.181 13.106 0.569 13.806
7.916 200 0.040
13.80 13.066 12.991 0.734 21.722
16.764 200 0.084
13.55 12.908 12.671 0.642 38.486
4.296 200 0.021
13.55 12.649 12.574 0.901 42.782
19.612 50 0.392
12.75 12.182 12.107 0.568 62.394
18.650 200 0.093
12.75 12.014 11.569 0.736 81.044
12.945 200 0.065
12.75 11.504 11.429 1.246 93.989
18.203 200 0.091
12.25 11.338 11.263 0.912 112.192
19.609 200 0.098
12.00 11.165 11.090 0.835 131.801
4.296 150 0.029
12.00 11.062 10.987 0.938 136.097
16.764 100 0.168
11.75 10.819 10.744 0.931 152.861
7.705 100 0.077
11.75 10.667 10.592 1.083 160.566

13.30 12.850 12.850 0.450 0.000


20.816 200 0.104
13.55 12.746 12.671 0.804 20.816

13.30 12.850 12.850 0.450 0.000


22.084 200 0.110
13.55 12.740 12.574 0.810 22.084

12.75 12.300 12.300 0.450 0.000


21.884 200 0.109
12.75 12.191 12.107 0.559 21.884

12.35 11.900 11.900 0.450 0.000


9.103 200 0.046
12.35 11.854 11.779 0.496 9.103
27.100 200 0.136
12.75 11.644 11.569 1.106 36.203

12.35 11.900 11.900 0.450 0.000


30.550 200 0.153
12.75 11.747 11.429 1.003 30.550

12.25 11.800 11.800 0.450 0.000


21.884 200 0.109
12.25 11.691 11.263 0.559 21.884

11.95 11.500 11.500 0.450 0.000


22.084 200 0.110
12.00 11.390 11.090 0.610 22.084

11.95 11.500 11.500 0.450 0.000


20.794 200 0.104
12.00 11.396 10.987 0.604 20.794
DRAINAGE DESIGN CALCULATIONS
Project : NURI PAGOH

Company: WANZA CONSULTING ENGINEERS

Owner : Date : 11/04/2020

Prepared by: MUHAMMAD AMIER THAQIF BIN ZUHAIMI Approved By:

Invert Level Design


13 14 15 16 17 18 19 20
Proposed Ground Length Gradient Invert Level Invert Level Sump Level IL from Ground Cumulative
Level (1:X) Drop Level Length
m m X m m m m m
11.65 11.200 11.200 0.450 0.000
14.014 200 0.070
11.75 11.130 10.592 0.620 14.014

11.65 11.200 11.200 0.450 0.000


18.181 200 0.091
11.75 11.109 11.034 0.641 18.181
0.422 300 0.001
12.00 11.033 - 0.967 18.603

13.25 12.800 12.800 0.450 0.000


45.760 50 0.915
12.75 11.885 11.810 0.865 45.760
45.610 150 0.304
12.35 11.506 11.431 0.844 91.370
45.610 200 0.228
11.85 11.203 11.128 0.647 136.980
45.492 200 0.227
11.35 10.900 10.825 0.450 182.472
14.623 150 0.097
11.35 10.728 10.653 0.622 197.095

Gradient Ranges = Steepest = 1: 50


Gentle = 1: 300

Deepest Sump Level = 10.114 m


Highest Sump Level = 13.250 m
Deepest Invert Level Drop = 1.325 m
Cumulative Ground Level Invert Level Depth of Sump
PROFILE Sump Distance (m) Sump Level (m)
Distance (m) (m) (m) (m)

A1 26.169 0.000 13.70 13.250 13.250 0.450

A1.1 46.494 26.169 13.55 13.076 13.001 0.549

A1.2 21.636 72.663 13.25 12.536 12.461 0.789

A1.3 5.848 94.299 12.70 12.244 12.127 0.573

A1 A1.4 45.830 100.148 12.70 12.010 11.935 0.765

A1.5 45.416 145.978 12.30 11.630 11.555 0.745

A1.6 5.818 191.395 11.80 11.252 11.064 0.736

A1.7 21.136 197.213 11.80 10.948 10.400 1.400

A1.8 0.000 218.349 11.35 10.189 10.114 1.236

A2 26.167 0.000 13.30 12.850 12.850 0.450

A2 A2.1 46.694 26.167 13.10 12.588 12.513 0.587

A1.3 0.000 72.861 12.70 12.202 12.127 0.573

A3 42.928 0.000 13.30 12.850 12.850 0.450

A3.1 43.261 42.928 12.75 11.991 11.916 0.834

A3.2 4.247 86.190 12.30 11.700 11.625 0.675


A3
A3.3 43.260 90.437 12.30 11.604 11.155 1.145

A3.4 4.446 133.697 11.85 10.939 10.864 0.986

A7.2 0.000 138.143 11.85 10.834 10.759 1.091

A4 22.216 0.000 12.75 12.300 12.300 0.450

A4.1 22.550 22.216 12.75 12.078 12.003 0.747


A4
A4.2 4.296 44.766 12.30 11.777 11.702 0.598

A5.2 0.000 49.062 12.30 11.681 11.426 0.874

A5 22.216 0.000 12.25 11.800 11.800 0.450

A5.1 22.549 22.216 12.30 11.689 11.614 0.686


A5
A5.2 19.582 44.766 12.30 11.501 11.426 0.874

A3.3 0.000 64.348 12.30 11.230 11.155 1.145

A6 43.033 0.000 11.95 11.500 11.500 0.450


A6
A3.4 0.000 43.033 11.85 11.285 10.864 0.986

A7 26.172 0.000 11.95 11.500 11.500 0.450

A7.1 17.282 26.172 11.90 11.369 11.294 0.606


A7
A7.2 28.452 43.454 11.85 11.208 10.759 1.091

A1.7 0.000 71.906 11.80 10.475 10.400 1.400

A8 26.172 0.000 11.65 11.200 11.200 0.450

A8 A8.1 46.494 26.172 11.40 10.938 10.863 0.537

A1.8 0.000 72.666 11.35 10.631 10.114 1.236

A9 6.536 0.000 11.65 11.200 11.200 0.450

A9.1 37.500 6.536 11.65 11.167 11.092 0.558


A9
A9.2 0.423 44.036 11.20 10.342 10.267 0.933

PT.EX1 0.000 44.459 11.20 10.263 - -


A9
Cumulative Ground Level Invert Level Depth of Sump
PROFILE Sump Distance (m) Sump Level (m)
Distance (m) (m) (m) (m)
PT.EX1 0.000 44.459 11.20 10.263 - -
Cumulative Ground Level Invert Level Depth of Sump
PROFILE Sump Distance (m) Sump Level (m)
Distance (m) (m) (m) (m)

A10 19.812 0.000 12.75 12.300 12.300 0.450


A10-1
A1.4 0.000 19.812 12.70 12.201 11.935 0.765

A10 45.830 0.000 12.75 12.300 12.300 0.450

A10.1 45.316 45.830 12.30 11.842 11.767 0.533


A10-2
A10.2 19.812 91.147 11.85 11.314 11.239 0.611

A1.6 0.000 110.959 11.80 11.139 11.064 0.736

B1 13.806 0.000 13.70 13.250 13.250 0.450

B1.1 7.916 13.806 13.75 13.181 13.106 0.644

B1.2 16.764 21.722 13.80 13.066 12.991 0.809

B1.3 4.296 38.486 13.55 12.908 12.671 0.879

B1.4 19.612 42.782 13.55 12.649 12.574 0.976

B1.5 18.650 62.394 12.75 12.182 12.107 0.643

B1 B1.6 12.945 81.044 12.75 12.014 11.569 1.181

B1.7 18.203 93.989 12.75 11.504 11.429 1.321

B1.8 19.609 112.192 12.25 11.338 11.263 0.987

B1.9 4.296 131.801 12.00 11.165 11.090 0.910

B1.10 16.764 136.097 12.00 11.062 10.987 1.013

B1.11 7.705 152.861 11.75 10.819 10.744 1.006

B1.12 0.000 160.566 11.75 10.667 10.592 1.158

B2 20.816 0.000 13.30 12.850 12.850 0.450


B2
B1.3 0.000 20.816 13.55 12.746 12.671 0.879

B3 22.084 0.000 13.30 12.850 12.850 0.450


B3
B1.4 0.000 22.084 13.55 12.740 12.574 0.976

B4 21.884 0.000 12.75 12.300 12.300 0.450


B4
B1.5 0.000 21.884 12.75 12.191 12.107 0.643

B5 9.103 0.000 12.35 11.900 11.900 0.450

B5 B5.1 27.100 9.103 12.35 11.854 11.779 0.571

B1.6 0.000 36.203 12.75 11.644 11.569 1.181

B6 30.550 0.000 12.35 11.900 11.900 0.450


B6
B1.7 0.000 30.550 12.75 11.747 11.429 1.321

B7 21.884 0.000 12.25 11.800 11.800 0.450


B7
B1.8 0.000 21.884 12.25 11.691 11.263 0.987

B8 22.084 0.000 11.95 11.500 11.500 0.450


B8
B1.9 0.000 22.084 12.00 11.390 11.090 0.910

B9 20.794 0.000 11.95 11.500 11.500 0.450


B9
B1.10 0.000 20.794 12.00 11.396 10.987 1.013
Cumulative Ground Level Invert Level Depth of Sump
PROFILE Sump Distance (m) Sump Level (m)
Distance (m) (m) (m) (m)

B10 14.014 0.000 11.65 11.200 11.200 0.450


B10
B1.12 0.000 14.014 11.75 11.130 10.592 1.158

B11 18.181 0.000 11.65 11.200 11.200 0.450

B11 B12 0.422 18.181 11.75 11.109 11.034 0.716

PT.EX2 0.000 18.603 12.00 11.033 - -

C1 45.760 0.000 13.25 12.800 12.800 0.450

C2 45.610 45.760 12.75 11.885 11.810 0.940

C3 45.610 91.370 12.35 11.506 11.431 0.919


C
C4 45.492 136.980 11.85 11.203 11.128 0.722

C5 14.623 182.472 11.35 10.900 10.825 0.525

C6 0.000 197.095 11.35 10.728 10.653 0.697