Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

SHUT DOWN JOBS OF HRSG 1 & 2

DATE: -----------------------
Sr # Description HRSG Dept
1 HP Feed Water C.V hunting in its feedback. 1 I&C
2 HP steam SORV (11LBA30AA522) is o/o/o. 1 I&C
3 HP steam Injection motorized and C. valve seat are leaking. 1 ME
4 HP drum S/up blow down is o/o/o. 1 I&C
5 HP Super Heater drain valve are on local position (02 Nos) 1 ME
6 IP steam S/up vent valve (11LBA20AA512) is o/o/o. 1 I&C
7 IP Super Heated steam S/up vent valve (11LBB20AA512) is o/o/o. 1 I&C
8 IP steam C.V main & by pass are on Local Position 1 I&C
9 IP Feed Water Pump # 1 leakage in its body 1 ME
10 LP steam drain valve (11LBA10AA412) is o/o/o. 1 I&C
11 HP feed water flow is o/o/o.
12
13
14
15
16
17 HP feed water C.V 12LBA30AA101 needs proper adjustment( seat leaking) 2 I&C
18 HP IBD Valve is not working. 2 I&C
19 Concrete foundation support of R.H steam from RH 1 to 2 is damage. 2 ME
20 IP steam S/up vent valve 12LBB20AA512 is o/o/o. 2 I&C
21 IP feed pump # 1 leakage in RC valve. 2 ME
22 Seat is Leaking in HP economizer # 2 drain line H.W.Valve 2 ME
23 LP Evaporator Lower Header leakage observed 2 ME
24 HP Super Heater drain valve are on local position (02 Nos) 2 I&C
25 R.C valve of HP feed pump #1,2 & 3 seat are leaking 2 ME
26 R.C valve of HP feed pump #1 & 3 flange are leaking 2 ME
27 BWC pumps #1,2 gland are leaking 2 ME
28 IP Feed Water Pumps # 1 & 2 heavy leakage in body. 2 ME
29 HP Super Heater drain valve are on local position (02 Nos) 2 I&C
30 HP feed water C.V 12LBA30AA101 needs proper adjustment( seat leaking) 2 ME
31 HP IBD Valve is not working. 2 I&C
32
33
34 All the parameter of GTs are showing bad in Ovation HMI. 1&2 I&C
35 GTs Temp: control System is o/o/o. 1&2 I&C
36 Greasing required for all H.W valves of both HRSGs. 1&2 ME
37 Plz replace the broken wheels of hand wheel valves of both HRSG. 1&2 ME
38 Diverting Sheets/Plates (inside the HRSG)of both HRSGs are damage plz check 1&2 ME
39 All drain valves of HP,IP and LP system seats are leaking 1&2 ME
40
41
SHUT DOWN JOBS OF G.T 14 & 15

Sr # Description G.T Dept


1 Gas Strainer DP high 14 ME
2 20 PG2 valve is faulty 14 I&C
3 Wheel Space 2nd Stage Forward Thermocouple # TTWS2F0-1 out 14 I&C
4 Off Line water washing due to comp: temp: from diff: GT 15 12c 14 ME
5 CDM can # 15 Amplitude Fault. 14 I&C
6 20 PG3 fan VG3 close Position On Both GTs 14 I&C
7 Lube Oil tank level switch is faulty 14 I&C
8 Gas reducing station Regulation valve are not working properly. 14 I&C
9 Safety relief valve on water to P/Heater in leaking 14 ME
10 88TK and 88BN filters need cleaning. 14 EE
11
12
13
14
15
16 TCC air pressure not working properly. 15 I&C
17 TCC cooling air Temp: not working properly. 15 I&C
18 Generator Rotor fan DP high. 15 EE
19 H2 leakage observed. 15 EE
20 88HQ Hydraulic pump # 1 lift pressure did not maintain 15 I&C
21 CDM can # 10 Implement limits PSI high varied. 15 I&C
22 Exhaust duct pressure sensor disagreement 15 I&C
23 Generator H2 gas pressure high indication is malfunctioning 15 I&C
24 88TK and 88BN filters need cleaning. 15 EE
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41

You might also like