Alüminyum iletken kýsa devre akýmý hesabý

Short-circuit current ratings aluminium conductor

Genel / General

IEC 949’a göre aþaðýdaki formülde izolasyon içindeki


sýcaklýk deðiþimleri hesaba katýlmamýþtýr.

The following formula in accordance with IEC 949 takes


into account an adiabatic heating, i.e. without loss of heat in the insulation.

Kýsa devre akýmý (KA)


Short-circuit current (KA)
1000
0.1 s
0.2 s
0.5 s
1.0 s
2.0 s
3.0 s
100

10

1
100 1000 10000

Alüminyum iletkenin kesiti (mm²)

Cross-sectional area of aluminium conductor (mm²)

I = 148 S Ln 228 + qf veya / or J = 1 = 1 148 Ln 228 + qf = 1 x 94,5


Öt 228 + qi S Öt 228 + qi Öt

I: Ýletken kýsa devre akýmý (A) / Permissible short circuit current (A)
S: Ýletken kesiti (mm²) / Cross-sectional area of the conductor (mm²)
t: Kýsa devre süresi (s) / Short circuit duration time (s)
qf: Kýsa devre iletken sýcaklýðý (250ºC) / Final temperature (250ºC)
qi: Ýletken iþletme sýcaklýðý (90ºC) / Initial temperature (90ºC)
J: Ýletken akým taþýma kapasitesi (A/mm²) / Permissible current density (A/mm²)

t=1 s için / For t=1 s / s için / For t=1


t=1 / s
J0
J=J0= 94,5 A/mm² J=
Öt