Cooling and Dehumidifying Heat Load Esti

Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 380.4 15.0 0.36
Ceiling 156.9 15.0 0.36
Floor 156.9 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 60 20.0 1.08 0.10
Internal Heat
People 12 255 0
Lights 157 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 60 73.5 0.68 0.10
People 12 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 314 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 60 20.0 1.08 0.90
hum diff const
Latent 60 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 2.3364884303
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

256.02
288.12

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 203.4 GLASS
SOUTH 177.0 ALL GLASS
- WEST PARTITION
- EAST M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 380.4
- AREA 156.88 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 12 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
2,054 CFM/PERSON 10
847 EXHAUST 0
998 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
130 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 157 (1 if Mod.Ceiling Panels exists else 0)
3,060 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
803 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.73 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.87 REV. TR
- Dehumd. CFM 479 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
11,305
789 FRESH AIR REQUIREMENT
12,094 NOS CFM/PER ACH NET (CFM)
PEOPLE 12 5 60
- EXHAUST 0
300 NO. OF A/CHANGES 0
3,060 TOTAL FRESH AIR
- Ventilation cfm/ft2 157 0.2 60
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
669 INSIDE 69.0 58.9 1 25.6
4,029
403 DIFF. -13.0 -1.8
4,432
16,525 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 54.21
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
1,166 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 77.23
2,699 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
20,391 3. ENTERING AIR MOISTURE CONTENT 90.38
2,039 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.30
22,430 ( Tadp + (BF(Tedb - T adp)))
1.87 5. SUPPLY AIR CFM 538.55
0.73 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
479 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
0.00
0.00
47.46
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 33.9 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 154.4 12.0 0.37
South 0.0 26.0 0.37
West 116.7 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 33.9 20.0 1.13
Partition 180.8 15.0 0.36
Ceiling 172.1 15.0 0.36
Floor 172.1 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 360 20.0 1.08 0.10
Internal Heat
People 12 255 0
Lights 172 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 360 73.5 0.68 0.10
People 12 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 461 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 360 20.0 1.08 0.90
hum diff const
Latent 360 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 5.5420150789
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

167.31
248.51

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 154.4 GLASS
SOUTH 86.6 ALL GLASS
- WEST 33.9 116.7 PARTITION
- EAST 94.2 M.PARTN
2,999 NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 180.8
- AREA 172.05 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
686 FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
1,771 NO. OF PEOPLE 12 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
766 BPF 0.1
976 CFM/PERSON 10
929 EXHAUST 0
1,094 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
778 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 172 (1 if Mod.Ceiling Panels exists else 0)
3,060 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
881 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.74 REV. ESHR
ADP 49.00 REV. ADP
- TR 4.43 REV. TR
- Dehumd. CFM 742 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
17,352
1,394 FRESH AIR REQUIREMENT
18,746 NOS CFM/PER ACH NET (CFM)
PEOPLE 12 30 360
- EXHAUST 0
1,800 NO. OF A/CHANGES 0
3,060 TOTAL FRESH AIR
- Ventilation cfm/ft2 172 0.2 360
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
982 INSIDE 69.0 58.9 1 25.6
5,842
584 DIFF. -13.0 -1.8
6,426
25,173 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 59.25
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
6,998 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 81.53
16,196 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
48,367 3. ENTERING AIR MOISTURE CONTENT 163.55
4,837 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.23
53,203 ( Tadp + (BF(Tedb - T adp)))
4.43 5. SUPPLY AIR CFM 1101.79
0.74 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
742 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
0.00
48.24
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 700.5 15.0 0.36
Ceiling 56.5 15.0 0.36
Floor 56.5 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 20 20.0 1.08 0.10
Internal Heat
People 4 255 0
Lights 56 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 20 73.5 0.68 0.10
People 4 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 113 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 20 20.0 1.08 0.90
hum diff const
Latent 20 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 1.4411937201
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

336.07
353.42

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 56.5 GLASS
SOUTH 56.5 ALL GLASS
- WEST 293.7 PARTITION
- EAST 293.7 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 700.5
- AREA 56.49 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 4 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
3,783 CFM/PERSON 10
305 EXHAUST 0
359 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
43 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 56 (1 if Mod.Ceiling Panels exists else 0)
1,020 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
289 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.15 REV. TR
- Dehumd. CFM 387 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
9,212
580 FRESH AIR REQUIREMENT
9,792 NOS CFM/PER ACH NET (CFM)
PEOPLE 4 5 20
- EXHAUST 0
100 NO. OF A/CHANGES 0
1,020 TOTAL FRESH AIR
- Ventilation cfm/ft2 56 0.2 20
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
241 INSIDE 69.0 58.9 1 25.6
1,361
136 DIFF. -13.0 -1.8
1,497
11,289 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.75
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
389 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 75.98
900 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
12,578 3. ENTERING AIR MOISTURE CONTENT 75.38
1,258 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.32
13,835 ( Tadp + (BF(Tedb - T adp)))
1.15 5. SUPPLY AIR CFM 407.47
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
387 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
52.69
0.00
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 1028.1 15.0 0.36
Ceiling 88.6 15.0 0.36
Floor 88.6 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 20 20.0 1.08 0.10
Internal Heat
People 4 255 0
Lights 89 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 20 73.5 0.68 0.10
People 4 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 177 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 20 20.0 1.08 0.90
hum diff const
Latent 20 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 1.7497882039
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

348.67
362.96

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 165.7 GLASS
SOUTH 274.9 ALL GLASS
- WEST 293.7 PARTITION
- EAST 293.7 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 1028.1
- AREA 88.61 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 4 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
5,552 CFM/PERSON 10
478 EXHAUST 0
564 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
43 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 89 (1 if Mod.Ceiling Panels exists else 0)
1,020 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
454 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.88 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.40 REV. TR
- Dehumd. CFM 488 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
11,524
811 FRESH AIR REQUIREMENT
12,335 NOS CFM/PER ACH NET (CFM)
PEOPLE 4 5 20
- EXHAUST 0
100 NO. OF A/CHANGES 0
1,020 TOTAL FRESH AIR
- Ventilation cfm/ft2 89 0.2 20
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
378 INSIDE 69.0 58.9 1 25.6
1,498
150 DIFF. -13.0 -1.8
1,648
13,982 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.52
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
389 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 75.79
900 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
15,271 3. ENTERING AIR MOISTURE CONTENT 73.22
1,527 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.33
16,798 ( Tadp + (BF(Tedb - T adp)))
1.40 5. SUPPLY AIR CFM 508.08
0.88 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
488 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
53.05
0.00
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 538.5 15.0 0.36
Ceiling 101.7 15.0 0.36
Floor 101.7 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 20 20.0 1.08 0.10
Internal Heat
People 4 255 0
Lights 102 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 20 73.5 0.68 0.10
People 4 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 203 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 20 20.0 1.08 0.90
hum diff const
Latent 20 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 1.4514072383
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

329.52
346.74

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 50.8 GLASS
SOUTH 50.8 ALL GLASS
- WEST 195.8 PARTITION
- EAST 241.0 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 538.5
- AREA 101.68 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 4 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
2,908 CFM/PERSON 10
549 EXHAUST 0
647 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
43 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 102 (1 if Mod.Ceiling Panels exists else 0)
1,020 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
521 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.85 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.16 REV. TR
- Dehumd. CFM 383 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
9,101
569 FRESH AIR REQUIREMENT
9,669 NOS CFM/PER ACH NET (CFM)
PEOPLE 4 5 20
- EXHAUST 0
100 NO. OF A/CHANGES 0
1,020 TOTAL FRESH AIR
- Ventilation cfm/ft2 102 0.2 20
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
434 INSIDE 69.0 58.9 1 25.6
1,554
155 DIFF. -13.0 -1.8
1,709
11,378 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.76
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
389 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 75.99
900 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
12,667 3. ENTERING AIR MOISTURE CONTENT 75.52
1,267 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.32
13,934 ( Tadp + (BF(Tedb - T adp)))
1.16 5. SUPPLY AIR CFM 402.61
0.85 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
383 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
52.25
0.00
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
CARDINAL SANTOS SPORTS INSTITUTE
Load Calculation
Ground Floor RULE OF THU TONS CHECK
SQFT SQM BTU/SQM TONS HP SQM/TON TON
Hallway to CR 156.88 14.58 800 1.0 1.2 15.0 18 0.81 1.01
Reception 172.05 15.99 800 1.1 1.3 15.0 16 1.00 1.25
A North 56.49 5.25 800 0.4 0.4 15.0 16 0.33 0.41
AW 101.68 9.45 800 0.6 0.8 15.0 16 0.59 0.74
AE 164.14 15.26 800 1.0 1.3 15.0 20 0.76 0.95
Consult89 126.21 11.73 800 0.8 1.0 15.0 16 0.73 0.92
Treat 57 190.56 17.71 800 1.2 1.5 15.0 16 1.11 1.38
Treat 14 252.43 23.46 800 1.6 2.0 15.0 16 1.47 1.83
Consult 14 327.10 30.40 800 2.0 2.5 15.0 16 1.90 2.38
Consult 58 397.04 36.90 800 2.5 3.1 15.0 16 2.31 2.88
Lounge 113.41 10.54 800 0.7 0.9 15.0 16 0.66 0.82
12.8 15.9
CALCULATED ACH CFM No Rooms TR/RM Model
TR
1.87 60.00 1.00 1.87 2.34 65 63
4.43 4.43 1.00 4.43 5.54 155
1.15 20.00 1.00 1.15 1.44 40 45
1.16 20.00 1.00 1.16 1.45 41 45
1.21 20.00 1.00 1.21 1.52 42 45
2.05 20.00 2.00 1.03 1.28 36 36
1.97 40.00 2.00 0.98 1.23 34 36
2.24 40.00 4.00 0.56 0.70 20 22
2.25 40.00 4.00 0.56 0.70 20 22
2.88 80.00 4.00 0.72 0.90 25 28
2.95 2.95 1.00 2.95 3.68 103
24.16 344.43
- 195.57
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 964.1 15.0 0.36
Ceiling 164.1 15.0 0.36
Floor 164.1 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 20 20.0 1.08 0.10
Internal Heat
People 4 255 0
Lights 164 1.5 3.413
Equipment 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 20 73.5 0.68 0.10
People 4 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 328 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 20 20.0 1.08 0.90
hum diff const
Latent 20 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 1.5164347509
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

324.34
340.83

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 50.8 GLASS
SOUTH 50.8 ALL GLASS
- WEST 380.4 PARTITION
- EAST 482.0 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 964.1
- AREA 164.14 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 4 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
5,206 CFM/PERSON 10
886 EXHAUST 0
1,044 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
43 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 164 (1 if Mod.Ceiling Panels exists else 0)
1,020 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
840 ADP&SHR 0 (1 if ADP & SHR revised else 0)
- Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.83 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.21 REV. TR
- Dehumd. CFM 393 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
9,040
904 FRESH AIR REQUIREMENT
9,944 NOS CFM/PER ACH NET (CFM)
PEOPLE 4 5 20
- EXHAUST 0
100 NO. OF A/CHANGES 0
1,020 TOTAL FRESH AIR
- Ventilation cfm/ft2 164 0.2 20
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
700 INSIDE 69.0 58.9 1 25.6
1,820
182 DIFF. -13.0 -1.8
2,002
11,946 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.73
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
389 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 75.97
900 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
13,234 3. ENTERING AIR MOISTURE CONTENT 75.22
1,323 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.32
14,558 ( Tadp + (BF(Tedb - T adp)))
1.21 5. SUPPLY AIR CFM 413.48
0.83 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
393 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
51.75
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 43.0 0.48
Roof -Sun-Insulated 43.0 0.20
Roof -Shaded 20.0 0.48
Transmission gain-except walls & roof
All glass 0.0 23.0 1.13
Partition 557.4 18.0 0.36
Ceiling 126.2 18.0 0.36
Floor 126.2 18.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 20 23.0 1.08 0.10
Internal Heat
People 4 255 0
Lights 126 1.5 3.413
Equipment 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 20 79.6 0.68 0.10
People 4 255
Appilances 3.00 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 252 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 20 23.0 1.08 0.90
hum diff const
Latent 20 79.6 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 2.565060433
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

170.45
180.20

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 72.0 50%
DIFFERENCE 23.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 86.6 GLASS
SOUTH 86.6 ALL GLASS
- WEST 192.1 PARTITION
- EAST 192.1 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 557.4
- AREA 126.21 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 4 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
3,612 CFM/PERSON 10
818 EXHAUST 0
963 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
50 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 126 (1 if Mod.Ceiling Panels exists else 0)
1,020 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
646 ADP&SHR 0 (1 if ADP & SHR revised else 0)
- Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.37 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.05 REV. TR
- Dehumd. CFM 350 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
7,109
711 FRESH AIR REQUIREMENT
7,820 NOS CFM/PER ACH NET (CFM)
PEOPLE 4 5 20
- EXHAUST 0
108 NO. OF A/CHANGES 0
1,020 TOTAL FRESH AIR
10,239 Ventilation cfm/ft2 126 0.2 20
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
583 INSIDE 69.0 58.9 1 25.6
11,950
1,195 DIFF. -13.0 -1.8
13,145
20,965 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.42
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 20.70
* If above is too high. Determine supply CFM
447 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 73.24
974 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
22,386 3. ENTERING AIR MOISTURE CONTENT 70.08
2,239 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.08
24,625 ( Tadp + (BF(Tedb - T adp)))
2.05 5. SUPPLY AIR CFM 369.78
0.37 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
21 # when bypassing a mixture of OA & RA use supply CFM, when
350 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
58.8 0.0084 7000
79.6

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
0.00
0.00
0.00
0.00
0.00
0.00
19.82

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 43.0 0.48
Roof -Sun-Insulated 43.0 0.20
Roof -Shaded 20.0 0.48
Transmission gain-except walls & roof
All glass 0.0 23.0 1.13
Partition 753.2 18.0 0.36
Ceiling 190.6 18.0 0.36
Floor 190.6 18.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 40 23.0 1.08 0.10
Internal Heat
People 8 255 0
Lights 191 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 40 79.6 0.68 0.10
People 8 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 381 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 40 23.0 1.08 0.90
hum diff const
Latent 40 79.6 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 2.4588542412
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

344.88
365.21

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 72.0 50%
DIFFERENCE 23.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 86.6 GLASS
SOUTH 86.6 ALL GLASS
- WEST 290.0 PARTITION
- EAST 290.0 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 753.2
- AREA 190.56 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 8 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
4,881 CFM/PERSON 10
1,235 EXHAUST 0
1,454 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
99 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 191 (1 if Mod.Ceiling Panels exists else 0)
2,040 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
976 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.81 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.97 REV. TR
- Dehumd. CFM 678 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
14,098
1,068 FRESH AIR REQUIREMENT
15,166 NOS CFM/PER ACH NET (CFM)
PEOPLE 8 5 40
- EXHAUST 0
217 NO. OF A/CHANGES 0
2,040 TOTAL FRESH AIR
- Ventilation cfm/ft2 191 0.2 40
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
880 INSIDE 69.0 58.9 1 25.6
3,136
314 DIFF. -13.0 -1.8
3,450
18,616 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.45
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 20.70
* If above is too high. Determine supply CFM
894 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 73.28
1,949 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
21,459 3. ENTERING AIR MOISTURE CONTENT 70.43
2,146 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.08
23,605 ( Tadp + (BF(Tedb - T adp)))
1.97 5. SUPPLY AIR CFM 718.40
0.81 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
21 # when bypassing a mixture of OA & RA use supply CFM, when
678 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
58.8 0.0084 7000
79.6

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
51.16
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 43.0 0.48
Roof -Sun-Insulated 43.0 0.20
Roof -Shaded 20.0 0.48
Transmission gain-except walls & roof
All glass 0.0 23.0 1.13
Partition 941.5 18.0 0.36
Ceiling 252.4 18.0 0.36
Floor 252.4 18.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 40 23.0 1.08 0.10
Internal Heat
People 8 255 0
Lights 252 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 40 79.6 0.68 0.10
People 8 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 505 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 40 23.0 1.08 0.90
hum diff const
Latent 40 79.6 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 2.7986220296
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

355.97
373.84

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 72.0 50%
DIFFERENCE 23.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 86.6 GLASS
SOUTH 86.6 ALL GLASS
- WEST 384.1 PARTITION
- EAST 384.1 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 941.5
- AREA 252.43 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
- NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 8 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
6,101 CFM/PERSON 10
1,636 EXHAUST 0
1,927 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
99 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 252 (1 if Mod.Ceiling Panels exists else 0)
2,040 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
1,292 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.83 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.24 REV. TR
- Dehumd. CFM 797 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
16,508
1,309 FRESH AIR REQUIREMENT
17,817 NOS CFM/PER ACH NET (CFM)
PEOPLE 8 5 40
- EXHAUST 0
217 NO. OF A/CHANGES 0
2,040 TOTAL FRESH AIR
- Ventilation cfm/ft2 252 0.2 40
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
1,165 INSIDE 69.0 58.9 1 25.6
3,422
342 DIFF. -13.0 -1.8
3,764
21,581 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.29
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 20.70
* If above is too high. Determine supply CFM
894 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 73.10
1,949 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
24,424 3. ENTERING AIR MOISTURE CONTENT 68.70
2,442 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.08
26,867 ( Tadp + (BF(Tedb - T adp)))
2.24 5. SUPPLY AIR CFM 836.98
0.83 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
21 # when bypassing a mixture of OA & RA use supply CFM, when
797 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
58.8 0.0084 7000
79.6

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
51.52
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 120.5 12.0 0.37
South 120.5 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 715.5 15.0 0.36
Ceiling 327.1 15.0 0.36
Floor 327.1 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 40 20.0 1.08 0.10
Internal Heat
People 8 255 0
Lights 327 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 40 73.5 0.68 0.10
People 8 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 654 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 40 20.0 1.08 0.90
hum diff const
Latent 40 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 2.8089918033
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

315.89
333.69

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 120.5 GLASS
SOUTH 120.5 ALL GLASS
- WEST 357.8 PARTITION
- EAST 357.8 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 715.5
- AREA 327.10 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
535 FALSE CEILING HT. 13 ft SHR ADP
1,159 NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 8 0.03 0.92 54
- Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
3,864 CFM/PERSON 10
1,766 EXHAUST 0
2,080 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
86 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 327 (1 if Mod.Ceiling Panels exists else 0)
2,040 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
1,675 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.82 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.25 REV. TR
- Dehumd. CFM 710 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
16,619
1,321 FRESH AIR REQUIREMENT
17,940 NOS CFM/PER ACH NET (CFM)
PEOPLE 8 5 40
- EXHAUST 0
200 NO. OF A/CHANGES 0
2,040 TOTAL FRESH AIR
- Ventilation cfm/ft2 327 0.2 40
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
1,395 INSIDE 69.0 58.9 1 25.6
3,635
363 DIFF. -13.0 -1.8
3,998
21,938 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 52.85
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
778 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 76.07
1,800 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
24,515 3. ENTERING AIR MOISTURE CONTENT 76.35
2,451 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.32
26,966 ( Tadp + (BF(Tedb - T adp)))
2.25 5. SUPPLY AIR CFM 749.86
0.82 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
710 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
51.26
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 116.7 26.0 0.37
West 0.0 41.0 0.37
East 154.4 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 229.7 15.0 0.36
Ceiling 113.4 15.0 0.36
Floor 113.4 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 80 20.0 1.08 0.10
Internal Heat
People 8 255 0
Lights 113 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 80 73.5 0.68 0.10
People 8 255
Appilances 3.00 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 227 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 80 20.0 1.08 0.90
hum diff const
Latent 80 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 3.6820050472
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

167.93
195.09

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 116.7 GLASS
SOUTH 116.7 ALL GLASS
- WEST 113.0 PARTITION
- EAST 154.4 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 229.7
- AREA 113.41 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
1,123 NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 8 0.03 0.92 54
1,771 Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
1,241 CFM/PERSON 10
612 EXHAUST 0
721 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
173 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 113 (1 if Mod.Ceiling Panels exists else 0)
2,040 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
581 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.46 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.95 REV. TR
- Dehumd. CFM 495 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
11,675
826 FRESH AIR REQUIREMENT
12,501 NOS CFM/PER ACH NET (CFM)
PEOPLE 8 10 80
- EXHAUST 0
400 NO. OF A/CHANGES 0
2,040 TOTAL FRESH AIR
10,239 Ventilation cfm/ft2 113 0.2 80
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
484 INSIDE 69.0 58.9 1 25.6
13,162
1,316 DIFF. -13.0 -1.8
14,479
26,980 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 54.86
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
1,555 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 77.78
3,599 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
32,134 3. ENTERING AIR MOISTURE CONTENT 97.77
3,213 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.29
35,347 ( Tadp + (BF(Tedb - T adp)))
2.95 5. SUPPLY AIR CFM 574.66
0.46 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
495 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
0.00
0.00
0.00
0.00
0.00
0.00
24.62

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
Cooling and Dehumidifying Heat Load Esti
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 338.9 26.0 0.37
West 0.0 41.0 0.37
East 154.4 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 493.3 15.0 0.36
Ceiling 397.0 15.0 0.36
Floor 397.0 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 80 20.0 1.08 0.10
Internal Heat
People 8 255 0
Lights 397 1.5 3.413
Equipment 1.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 80 73.5 0.68 0.10
People 8 255
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 794 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 80 20.0 1.08 0.90
hum diff const
Latent 80 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 3.5961633839
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)

298.25
326.06

14.0
144
fying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH TH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0 0.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS
GLASS WALLS PARTNS WALL
Btu/hr NORTH 338.9 GLASS
SOUTH 338.9 ALL GLASS
- WEST 154.4 PARTITION
- EAST 154.4 M.PARTN
- NW CEILING
- NE M.CLG.PANL
- SW FLOOR
- SE ROOF
- OTHER DATA TO BE FILLED 493.3
- AREA 397.04 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR ADP
3,261 NO OF F.A.CHANGES 5 PER HR. 1 55.2
- NO. OF PEOPLE 8 0.03 0.92 54
1,771 Steam 0 0.84 52
- Brewer 0 0.78 50
- 0 0.74 48
- 0 0.71 46
- LIGHTING LOAD 1.5 W/S. FT 0.69 44
- EQUIPMENT LOAD 1.0 KW 0.66 40
- DIVERSITY FACTOR 1 0.64 34
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
2,664 CFM/PERSON 10
2,144 EXHAUST 0
2,525 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
173 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 397 (1 if Mod.Ceiling Panels exists else 0)
2,040 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
2,033 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,413 Motor bkw IF ADP & SHR REVISED,CONSIDER FOLWG
- SHR 0.83 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.88 REV. TR
- Dehumd. CFM 858 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
20,023
1,661 FRESH AIR REQUIREMENT
21,684 NOS CFM/PER ACH NET (CFM)
PEOPLE 8 10 80
- EXHAUST 0
400 NO. OF A/CHANGES 0
2,040 TOTAL FRESH AIR
- Ventilation cfm/ft2 397 0.2 80
PRE-COOLING COIL
- DB 'F WB 'F RH TH
- LEV. COND 56.0 55.9 99.5 23.8
1,693 INSIDE 69.0 58.9 1 25.6
4,133
413 DIFF. -13.0 -1.8
4,546
26,230 1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 53.60
Trm-( RSH/(1.08 x (De. CFM+CFMoa)) 23.40
* If above is too high. Determine supply CFM
1,555 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE 76.71
3,599 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
31,385 3. ENTERING AIR MOISTURE CONTENT 83.84
3,138 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE 51.31
34,523 ( Tadp + (BF(Tedb - T adp)))
2.88 5. SUPPLY AIR CFM 938.04
0.83 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
858 bypassing RA only, use deh. CFM

10.3
GR/LB
138.4
64.9
73.5

U' FACTORS
0.360 11.4 34.2
0.560 15.96 13.68
1.130 27.36 47.88
0.360
0.150
0.424
0.150
0.424
0.510

e ADP Table 32.56


75.0 & 50%RH 9
6.375
0.00 47.935
0.00
51.56
0.00
0.00
0.00
0.00
0.00
0.00

ONSIDER FOLWG
0.97
50
0.00
0
0.00

GR/LB
66.7
58.2

8.5

F
0

F
0

Gr./lb

F
0

F
0

F
0

F
0
R Value of Concrete Wall

Outside Air 0.25


Plastering 3/4inch 0.15
CHB 6 0.91
Plastering 3/4inch 0.15
Inside Air 0.61
1.639344 0.61