Protection Against Electric Shock
Protection Against Electric Shock
3
IS 14772: 2000
connection, to the earthing circuit during fixing of when fitted with conduit or with sheathed cable.
the cover or cover-plate itself.
Compliance is checked by inspection and by the test
The use of fixing screws, or other means, is allowed. of 12.4.
Compliance is checked by inspection and by the test 11.4 Surface and semi-flush mounting enclosures with
of 10.2. IP Xl to IP X6 shall be designed to allow opening a
drain-hole at least 5 mm in diameter or 20 mm2 in
10 PROVISION FOR EARTHING area with a minimum width or length of 3 mm.
10.1Metallic enclosures, which may become live in Drain-holes shall be so located and available in such
the event of an insulation fault, shall be provided with a number that one of the holes can always become
a facility for permanent and reliable connection to an effective in any intended position of the enclosure.
earthing means.
Compliance is checked by inspection, measurement
Compliance is checked by inspection. and the use of probes.
10.2 The correction between an earthing terminal and 11.5Enclosures suitable for mounting in hollow walls
accessible metal parts to be connected thereto shall be shall have at least IP20.
of low resistance.
They shall be provided with suitable means for fixing
Compliance is checked by the following test: accessories, covers or cover-plates.
A current derived from an a.c. source having a no- Compliance is checked by inspection and by a test
load voltage not exceeding 12V and equal to 25A is under consideration.
passed between the earthing terminal and each of the
11.6 Enclosures shall have provisions for their attach-
accessible metal parts in turn. The voltage drop
ment into or onto a wall or ceiling.
between the earthing terminal and the accessible metal
parts is measured, and the-resistance calculated from Enclosures of insulating material shall be constructed
the current and this voltage drop. in such a way that, when mounted using the fixing
means intended, any metal parts of an internal fixing
In no case shall the resistance exceed 0.05 SZ.
means is surrounded by insulation which projects
NOTES above the top of the fixing means by an amount of at
1 Care should be taken that the contact resistance between the least 10 percent of the maximum width of the fixing
tip of the measuring probe and the metal part under test does not means recess.
influence the test results.
2 In insulating enclosures with IP > XOprovision may be made Compliance is checked by inspection and by measure-
for the addition of means for the effective continuity of the earth- ments.
ing conductor, when more than one inlet is provided.
11.7 Inlet openings, if any, shall allow either the
11 CONSTRUCTIONAL REQUIREMENTS introduction of the conduit or a suitable fitting
11.1 Enclosures shall have adequate mechanical terminating the conduit at the enclosure or the
strength. protective covering of the cable so as to provide
mechanical protection.
Compliance is checked by inspection and by the tests
of 13. Inlet opening for conduit entries, or at least two of
them if there are more than one, shall be capable of
11.1 Covers or cover-plates which are intended to accepting either conduits of sizes, or a combination
ensure safety against electric shock shall be reliably of sizes in accordance with the requirements given in
held in place by two or more independent means, at IS 14763.
least one of which requires the use of a tool.
Compliance is checked by inspection and by tests using
One means only, requiring the use of a tool, is allowed the appropriate~cables or conduits.
if it acts centrally, provided that it holds the covers or
NOTES
the cover-plate reliably in place.
1 Inlet openings forrable entries are under consideration.
Compliance is checked by inspection. 2 Inlet openings of adequate size may also be obtained by the use
bf knock-outs or suitable insertion pieces or by means of an
The tests for snap-on fixing means are under appropriate cutting tool.
consideration.
11.8Screw fixing means for covers, accessories, etc,
11.3 Enclosures with IP>XO fitted with appropriate shall be so designed that these means withstand the
glands or membranes if any, shall provide the required mechanical stress occurring during installations and
degree of protection against harmful ingress of water normal use.
4