Building Information Owned/Rented

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 59

Name of the Factory: XXX XXX XXX FFC ID: XXXXX

Initial Assessment
Factory Address: XXXX XXXX XXXXX, Bangladesh DD-MM-YY
Date:

Visit Date: DD-MM-YY CCVV Date: DD-MM-YY


Building Information Owned/Rented

TABLE 1: BUILDING INFORMATION

Height of
the
Building Floor Area (Floor- Occupancy Type Type of Building Construction
SL highest
Name Designation wise) (Floor-wise) Constcution Height History
occupied
level

1 Building-1 GF A H Type 1, RCC p' q' 2009


1 B E
2 C G2
TABLE 2: BUILDING INFORMATION

Immediate
SL Building Floor Slab Thickness Surrounding Building Information (Occupancy type)
Action
Name Designation (Floor-wise) with Proximity Distance as per BNBC Table 3.2.2
Required

1 Building-1 GF mm " " Occupancy withing " " ft


1 mm " " Occupancy withing " " ft
2 mm " " Occupancy withing " " ft

TABLE 3: MEANS OF EGRESS

Location Location
Floor Location & Location & Location & Location & Location & Location &
Building Number of & Width & Width
Designati Width of Exit Width of Exit Width of Exit Width of Width of Exit Width of Exit
Name Exit Stair of Exit of Exit
on Stair-1 Stair-2 Stair-3 Exit Stair-4 Stair-6 Stair-7
Stair-5 Stair-8

Building-1 GF 3 NE, 41 mm
1 3 NE, 41 mm
2 2 NE, 41 mm

TABLE 4: MEANS OF EGRESS


Floor
Building Width of Exit- Width of Exit- Width of Width of Width of Exit-
Designati Width of Exit-2 Width of Exit-3 Width of Exit-7
Name 1 4 Exit-5 Exit-6 8
on
Building-1 GF a b c a b c a b
1 d e f d e f d e
2 l NA n l NA n l NA
TABLE 5: MEANS OF EGRESS
Number of
Floor Required total Measured total Required total Measured
Building Existing
Designati width of exit width of exit width of exit total width
Name Occupants
on doors doors stairs of exit tairs
(Floor-wise)
Building-1 GF x
1 y
2 z

FACTORY REPRESENTATIVE:
I hereby declare that the above mentioned information are correct. On behalf of factory management, I have agreed to ensure all above
recommendations properly in future.
Seal & Signature: Signature:

Factory Factory Responsible Name QAF Name


Fire Assessor
Representative : Designation Designation

Date 30-Dec-99 Date 30-Dec-99


Name of the Factory: XXX XXX XXX FFC ID: XXXXX

Initial
Factory Address: XXXX XXXX XXXXX, Bangladesh Assessment DD-MM-YY
Date:
Visit Date: DD-MM-YY CCVV Date: DD-MM-YY

Safety Monitoring Inspection Checklist

Fire: Status Remarks


All openings and penetrations through rated walls and assemblies are
1 protected with fire rated construction/or certified fire rated opening Yes
protectives.

Exit enclosures are provided with fire- resistive rated construction barrier.
2 Yes

All occupied roofs are provided with parapets or guards with a minimum
3 height as per standard. Yes

Travel distance to reach an exit does not exceed the maximum distance
4 allowed by Occupancy Type. Yes

Exit access corridors serving an occupant load exceeding 30 are separated


5 by walls having a fire-resistance rating of 1 hr. Yes

All paths of egress are provided with compliant means of illumination.


6 Yes

Doors are not locked in the direction of egress under any conditions. All
7 hasps, locks, slide bolts, and other locking devices have been removed Yes
where required.

All doors in a means of egress are of the side-hinged swinging type.


8 Yes

Illuminated exit signs are provided with battery backup or emergency power
9 and are continuously illuminated. Yes

Walking surfaces along the path of egress are uniformly slip resistant.
10 Yes

Landings are provided on both sides of doors used along the path of egress.
11 Doors do not swing out over stairs. N/A

Ramps do not have a running slope greater than 1 in 8 (12.5 percent) and
12 have handrails on both sides of the ramp. N/A

A Fire Safety Director position has been filled with proper training from the
13 appropriate authority. N/A

Storage areas underneath the cutting tables are clear of combustibles.


14 N/A

Fire protection system has been found functional during the verification and
15 updated inspection, testing and maintenance documents as per NFPA 25 are N/A
available at the factory.

Fire alarm and detection system has been found functional during the
verification and updated inspection, testing and maintenance documents as
per NFPA 72 are available at the factory.
16 N/A

Exit discharge is directly to the exterior of the building, unless the


17 requirements of of egress court has been adopted, at grade or provides N/A
direct access to grade. Exit discharge shall not reenter a building.

Means of egress are free from impediments, obstructions, and stored


18 materials. N/A

Compliant guards are provided on the open sides of egress components


19 where the elevation exceeds 760 mm (30 in) above the ground or floor N/A
below.
Stair treads are of nominal uniformity.
20 N/A

Stairwells are free from stored materials and electrical appliances?


21 N/A

Emergency egress maps are posted at the entrance to each exit stair or
22 main point of egress. N/A

Are the required number of people trained and certified in fire fighting, first
23 aid, and rescue training by the appropriate authority. N/A

All applicable permits are up to date including Fire License & Boiler License.
24 N/A

Approval documents are available for fire proof hybrid separation if


25 constructed. N/A

AHJ (Authorities Having Jurisdiction) approval documents are available if


26 applicable for a certain condition. Yes

Occupant loads on each level (floor) do not exceed the capacity of the
27 available means of egress. N/A

Fire Department pre-planning has been completed.


28 N/A

Chemicals and other flammable materials are stored within approved


29 enclosures. N/A

Fire extinguishers are in good condition and inspection, testing,


30 maintenance documents as per NFPA 10 are available at the factory. N/A

Fire doors are in good condition and inspection, testing, maintenance


31 documents as per NFPA 80 are available at the factory. N/A

Hotwork has been conducted as per NFPA 51B and permission documents
32 are available at the factory. Yes

Housekeeping policy and procedures have been implemented.


33 Yes

Factory is conducting fire drill under the appropriate authority and all
34 records are documented. Yes

Maintenance & testing documents for emergency lights and Exit Signages
35 are available at the factory. Yes

Are all approved proposed and as- built design of fire protection system,
36 detection system and fire door checklists available at the factory? Yes

Flammable gas connections or gas cylinders are existed within the factory
37 premises. Yes

Signature: Signature:

Name & Position Name

Date DD-MM-YY Date DD-MM-YY


Safety Monitoring Inspection (Action Needed) Fire Report
Factory Information
ID: XXXXX
Name of The Factory: XXX XXX XXX
Openings & penetrations through
Address: XXXX XXXX XXXXX, Bangladesh Wall: Visit Date: DD-MM-YY
BNBC Part 3 Table 3.2.3-
Requirements for Opening
Protection Assembly Rating of
Exterior Walls Priority Status on Visit
SI No Question Description References Due Date Recommendation
Level Date
BNBC Part 4 Section 2.5-
OPENINGS IN SEPARATING WALL
1 Are openings and penetrations through 6 weeks In-progress
rated walls and/or assemblies protected? NFPA 101 (Edition 2012) Chapter
8 Section 8.3.5 (Penetrations)
NFPA 101 (Edition 2018) Chapter
8 Section 8.3.4 (Penetrations)
Doors:
NFPA 80 & NFPA 252 High
BNBC Part 4 Section 1.5.4-The fire
door assemblies shall conform to
the test requirements of ASTM E
152

Windows:
BNBC Part 4 Section 1.5.5-The fire
windows and fire shutters shall
meet the test requirements of
ACKNOWLEDGED ASTM E 163
I hereby declare that the above mentioned information are correct. On behalf of factory NFPA 257
management, I have agreed to ensure all above recommendations properly in future. Ducts & Fire Damper:

NFPA 90 A
Signature Signature

Factory Representative : Factory Responsible Name Fire Assessor QAF Name


Designation Designation

Date: DD-MM-YY Date: DD-MM-YY


COMPRESSED GAS CYLINDERS SAFETY CHECKLIST
Item Yes No

Are cylinders stored in upright positions and immobilized by chains or other means to
prevent them from being knocked over?

Are cylinders stored away from highly flammable substances such as oil, gasoline, or
waste?

Are cylinders stored away from electrical connections, gas flames or other sources of
ignition, and substances such as flammable solvents and combustible waste material?

Are flammable gases separated from oxidizing gases in storage areas? Note: Acetylene
and propane cylinders should be separated from oxygen cylinders when not in use

Are oxygen and fuel gas cylinders separated by a minimum of 20 feet when in storage?
Note: A fire-resistant partition between the cylinders can also be used.

Are storage rooms for cylinders dry, cool, and well- ventilated? Note: Storage rooms
should be fire resistant and the storage should not be in subsurface locations. Cylinders
should be stored in secure areas at temperatures below 125ºF, away from radiators or
other sources of heat.

Are cylinders stored away from incompatibles, excessive heat, continuous dampness, salt
or other corrosive chemicals, and any areas that may subject them to damage?

Is the storage area permanently posted with the names of the gases stored in the
cylinders?

Do all compressed gas cylinders have their contents and precautionary labeling clearly
marked on their exteriors?

Are all compressed gas cylinder valve covers in place when cylinders are not in use?

Are all compressed gas cylinders stored so they do not interfere with exit paths?

Are all compressed gas cylinders subject to periodic hydrostatic testing and interior
inspection? Note: This is normally done by the supplier
Do all compressed gas cylinders have safety pressure relief valves?

Are cylinders always maintained at temperatures below 125ºF? Note: A flame should
never come in contact with any part of a compressed gas cylinder.

Are safety relief devices in the valve or on the cylinder free from any indication of
tampering?

Is repair or alteration to the cylinder, valve, or safety relief devices prohibited? Note: All
alterations and repairs to the cylinder and valve must be made by the compressed gas
vendor. Modification of safety relief devices beyond the tank or regulator should only be
made by a competent person appointed by management.

Is painting cylinders without authorization by the owner prohibited? Note: Often color
codes are used to help designate cylinders. Arbitrary paint is not recommended.

Are charged or full cylinders labeled and stored away from empty cylinders?

Is the bottom of the cylinder protected from the ground to prevent rusting?

Are all compressed gas cylinders regularly inspected for corrosion, pitting, cuts, gouges,
digs, bulges, neck defects and general distortion?

Are cylinder valves closed at all times, except when the valve is in use? Note: Regulator
diaphragms have failed, and unwanted gas was delivered to an area or apparatus, causing
safety and health problems.

Are compressed gas cylinders always moved, even short distances, by a suitable hand
truck? Note: Cylinders must never be dragged across the floor.

Is using wrenches or other tools for opening and closing valves prohibited? Note:
Hammering on valve wheels to open them should be strictly prohibited. For valves that
are hard to open, contact the supplier for instruction

Are suitable pressure regulating devices in use whenever the gas is emitted to systems
with pressure-rated limitations lower than the cylinder pressure?

Are all compressed gas cylinder connections such as pressure regulators, manifolds, hoses,
gauges, and relief valves checked for integrity and tightness?
Are all compressed gas cylinders regularly subjected to leak detection using an approved
leak detecting liquid? Note: Ordinary soap solution may contain oils that are unsafe when
used with oxygen cylinders. Leak detection liquids are available from commercial welding
supply houses.

Is an approved leak-detection liquid used to detect flammable gas leaks? Note: A flame
should never be used.

Are procedures established for when a compressed gas cylinder leak cannot be remedied
by simply tightening the valve?

Do the above procedures include the following:


·         Attach tag to the cylinder stating it is unserviceable
·         Remove cylinder to a well-ventilated out of doors location
·         If the gas is flammable or toxic, place an appropriate sign at the cylinder warning of
these hazards
·         Notify the gas supplier and follow his/her instructions as to the return of the
cylinder.

Are workers prohibited from using compressed gases (air) to clean clothing or work
surfaces?

Are compressed gases only handled by experienced and properly trained people?

Annual Gas Appliance Inspection Checklist


BTU/ALTITUDE ADJUSTMENT (GREEN STICKER)
APPLIANCE Yes No
Manufacturer’s recommended settings

Proper orifice sizing

Proper gas pressure

Proper flue-gas emissions


Apply sticker

APPLIANCE SAFETY INSPECTION


ACCESS Yes No

Safe location

Accessible

APPLIANCE

Proper clearance to combustibles

Proper operation clearance

Safe duct work

Proper ignition and burning

Btu/altitude adjustment

Operational safety checks

Visual heat exchanger inspection

GAS PIPING

Proper piping & fitting

Leak check

Sizing

Gas pressure verification

COMBUSTION AIR
Verify air supply

VENTING
Size

Clearances

Unobstructed

Proper vent cap

CARBON MONOXIDE (CO)


Perform CO test
ECKLIST
Comments
cklist

Comments
Comments
SL No. Question Reference Priority Level Weightage Severity Factor

All openings and penetrations through rated Please see the references against individual
walls and assemblies are protected with fire sub-question.
rated construction/or certified fire rated
opening protectives.

1 High 5

Doors are not locked in the direction of egress BNBC Part 3 Table 3.3.1-Enclosure of fire Exits
under any conditions. All hasps, locks, slide
bolts, and other locking devices have been
removed where required. Fire barriers shall be constructed of materials
meeting the testing requirements of ASTM E
2 119 High 5

All occupied roofs are provided with parapets BNBC Part 3 Section 1.12.14
or guards with a minimum height as per
standard.

3 Medium 3
Travel distance to reach an exit does not exceed BNBC Part 4 Section 3.15.1
the maximum distance allowed by Occupancy NFPA 101 Edition 2018 Section 7.5.4 (Accessible
Type. Means of Egress)
NFPA 101 Table 40.2.6 (Maximum Travel Distance
to Exits)
NFPA 101 Edition 2018 Table 40.2.6.1 (Maximum
4 Travel Distance to Exits) High 5
NFPA 101 Edition 2018 Table 42.2.6 (Maximum
Travel Distance to Exits)

Exit access corridors serving an occupant load NFPA 101 Edition 2018 Section 7.1.3.1 (Exit Access
exceeding 30 are separated by walls having a fire- Corridors)
resistance rating of 1 hr.

5 High 5

All paths of egress are provided with compliant BNBC Part 4 Section 3.16 (MEANS OF EXIT SIGNS
means of illumination. AND ILLUMINATION)

BNBC Part 8 Section 1.5 (ILLUMINATION OF EXIT


SIGNS AND MEANS OF ESCAPE)

6 Medium 3
Doors are not locked in the direction of egress BNBC Part 4 Section 3.9.8
under any conditions. All hasps, locks, slide bolts,
and other locking devices have been removed
where required.

7 High 5

All doors in a means of egress are of the side- BNBC Part 4 Section 3.9.5
hinged swinging type.

8 High 5

Illuminated exit signs are provided with battery NFPA 101 Edition 2018 Section 7.10.5.2
backup or emergency power and are continuously (Continuous Illumination)
illuminated.

9 High 5
Walking surfaces along the path of egress are NFPA 101 Edition 2018 Section 7.1.6 (Walking Surface
uniformly slip resistant. in the Means of Egress)

10 Medium 3

Landings are provided on both sides of doors used IBC Edition 2015 Section 1010.1.5 (Floor
along the path of egress. Doors do not swing out Elevation)
over stairs.

11 High 5

Ramps do not have a running slope greater than 1 BNBC Part 4 Section 3.11 RAMPS
in 8 (12.5 percent) and have handrails on both NFPA 101 Edition 2018 Section 7.2.2.4 (Guard and
sides of the ramp. Handrails)

12 Medium 3
A Fire Safety Director position has been filled with BNBC Part 4 A 4.8 (Fire Safety Plan)
proper training from the appropriate authority.

13 Low 1

Storage areas underneath the cutting tables are As per requirement


clear of combustibles.

14 Medium 3

Fire protection system has been found Please see the references against individual
functional during the verification and updated sub-question.
inspection, testing and maintenance
documents as per NFPA 25 are available at
the factory.
15 High 5
Fire alarm and detection system has been Please see the references against individual
found functional during the verification and sub-question
updated inspection, testing and maintenance
documents as per NFPA 72 are available at
the factory
16 High 5

Exit discharge is directly to the exterior of the Please see the references against individual
building, unless the requirements of Egress sub-question
Court.are met, at grade or provides direct
access to grade. Exit discharge shall not
reenter a building.
17 High 5

Means of egress are free from impediments, Please see the references against individual
obstructions, and stored materials. sub-question

18 High 5
Compliant guards are provided on the open
sides of egress components where the
elevation exceeds 760 mm (30 in) above the
ground or floor below.

19 Please see the references against individual Medium 3


sub-question

Stair treads are of nominal uniformity. BNBC Part 3 Section 1.12.5.2

20 Medium 3

Stairwells are free from stored materials and NFPA 101 (Edition 2018) Section 7.1.3
electrical appliances?

21 High 5
Emergency egress maps are posted at the Please see the references against individual
entrance to each exit stair or main point of sub-question
egress.

22 Medium 3

Are the required number of people trained and Bangladesh Labour Rules 2015
certified in fire fighting, first aid, and rescue
training by the appropriate authority.

23 High 5

All applicable permits are up to date including Fire license provided by the local authority
License & Boiler License.

24 Low 1
Approval documents are available for fire proof As per requirement
hybrid separation if constructed.

25 Medium 3

AHJ (Authorities Having Jurisdiction) approval As per requirement


documents are available if applicable for a certain
condition.

26 Medium 3

Occupant loads on each level (floor) do not Please see the references against individual
exceed the capacity of the available means of sub-question
egress.

27 High 5
Fire Department pre-planning has been BNBC Part 4 A 4.7 (Fire Safety Plan)
completed.

28 Low 1

Chemicals and other flammable materials are BNBC Part 3 Section 2.13
stored within approved enclosures.

29 Medium 3

Fire extinguishers are in good condition and Please see the references against individual
inspection, testing, maintenance documents sub-question
as per NFPA 10 are available at the factory.

30 Medium 3
Fire doors are in good condition and inspection,
testing, maintenance documents as per NFPA 80 NFPA 80 Edition 2019 Chapter 5
are available at the factory.

31 Medium 3

Hotwork has been conducted as per NFPA 51B NFPA 51B


and permission documents are available at the
factory.

32 Low 1

Housekeeping policy and procedures have been BNBC Part 4 D 20 (Housekeeping)


implemented.

33 Low 1
Factory is conducting fire drill under the BNBC Part 4 Section A 3 (FIRE DRILL)
appropriate authority and all records are BNBC Part 4 Section 1.4 (FIRE DRILL)
documented.

34 Medium 3

Maintenance & testing documents for Please see the references against individual
emergency lights and Exit Signages are sub-question
available at the factory.

35 Medium 3

Are all approved proposed and as- built design As per requirement
of fire protection system, detection system
and fire door checklists available at the
factory?

36 High 5
Flammable gas connections or gas cylinders As per requirement
are existed within the factory premises.

37 N/A
Photographic Evidence From QAF Team Category Action Status Justification of Severity
Factor
Explanation / Recommendation
Sl Issue Type Checklist questions Priority Level Main Reference Sub questions for Action Needed Sub Questions Reference Priority Level Remarks
1.1 All openings and penetrations through rated Please see the 1.1.1 Are openings and penetrations through rated walls and/or assemblies Openings & penetrations through Wall: High
walls and assemblies are protected with fire rated references against protected? BNBC Part 3 Table 3.2.3-Requirements for
construction/or certified fire rated opening individual sub- Opening Protection Assembly Rating of Exterior
protectives. question. 1.1.2 Are separations between hazards provided with fire-resistive rated BNBC
Walls Part 3 Table 3.3.1-Required Fire Medium
construction barriers. Resistance Ratings of Building Elements (in
hours) for Various
BNBC Part
Part 4 Table Types
Section of Construction
2.5-OPENINGS IN
1.1.3 Are shafts provided with the minimum fire-resistance rating? BNBC 3 3.3.1-Required Fire High
SEPARATING
Resistance WALL of Building Elements (in
BNBC Part 3Ratings
Table 3.2.1-Fire Resistance Rating
hours) for Various
Requirements Types of Construction
for Separating
1.1.4 Fire dampers installed on air-conditioning and ventilation ducts appear NFPA 101 (Edition
Installation as per 2012)90
NFPA A Walls
Chapter and
8 Section Medium
to be in good condition and operational. Floor/Ceiling Assemblies between Mixed
8.3.5 (Penetrations)
Occupancies
Opening (hours)
NFPA 101protection
(Edition 2018) Chapter 8 Section
as per:
1.1.5 If the building contains a vertical opening known as an atrium, have BNBC(Penetrations)
8.3.4
BNBC Part 3
Part 3 Section 3.1.17-Atria
Table 3.2.3-Requirements for Medium
provisions been made to comply with BNBC? Opening Protection Assembly Rating of Exterior
1.1.6 Is each floor separated with a fire-resistive rated construction barrier? Doors:
Walls Part 3 Table 3.3.1-Required Fire
BNBC High
1 Fire Protection Construction High NFPA 80 & Ratings
NFPA 252
Resistance of Building Elements (in
BNBC Part
hours) 4 Section
for Various 1.5.4-The
Types fire door
2.5-OPENINGS IN
of Construction
1.1.7 Is the fire resistance materials of structural members in good condition assemblies
BNBC Part 3shall
SEPARATING conform
WALL
Chapter 3 to the test Medium
and free of damage? requirements of ASTM E 152
NFPA 101 (Edition 2012) Chapter 8 Section
1.1.8 Doors along the path of egress have a minimum width and fire BNBC Part 4 Section 3.9.3 (For new building)
Windows:
8.3.5 (Penetrations) High
resistance rating as per standard. BNBC 101
NFPA Part(Edition
4 Section 1.5.5-The
2018) fire8windows
Chapter Section and
NTPA Sectionshall
fire shutters
8.3.4 2.9.7meet
(Penetrations) (Forthe
existing building)
test requirements
of ASTM E 163,
NFPA 257

Ducts & Fire Damper:


1.1.9 Exterior exit stairs are separated from the building with the required NFPA 101
90 A Edition 2018 Section 7.2.2.5.2 High
rating. The rating of the exterior wall shall extend 3.05 m (10 ft) beyond the (Exposures)
ends of the stair structure. BNBC Part 4 Section 3.10.8
2.1 Exit enclosures are provided with fire- resistive BNBC Part 3 Table 2.1.1 Are exit enclosures provided with fire-resistive rated construction BNBC Part 3 Table 3.3.1-Enclosure of fire Exits High
2 Means of Egress rated construction barrier. High 3.3.1-Enclosure of fire barriers?
Exits
3.1 All occupied roofs are provided with parapets or BNBC Part 3 Section 3.1.1 All occupied roofs are provided with parapets or guards with a minimum BNBC
Fire Part 3 Section
barriers shall be 1.12.14
constructed of materials Medium
guards with a minimum height as per standard. 1.12.14 height as per standard. meeting the testing requirements of ASTM E
3 Means of Egress Medium Fire barriers shall be 119
constructed of
4.1 Travel distance to reach an exit does not exceed materials
BNBC Partmeeting
4 Sectionthe 4.1.1 Travel distance to reach an exit does not exceed the maximum distance BNBC Part 4 Section 3.15.1 High
the maximum distance allowed by Occupancy Type. testing requirements allowed by Occupancy Type.
3.15.1 NFPA 101 Edition 2018 Section 7.5.4
4 Means of Egress High of ASTM
NFPA 101EEdition
119 (Accessible Means of Egress)
2018 Section 7.5.4 NFPA 101 Table 40.2.6 (Maximum Travel
5.1 Exit access corridors serving an occupant load (Accessible
NFPA Means of 5.1.1 Exit access corridors serving an occupant load exceeding 30 are
101 Edition Distance
NFPA 101toEdition
Exits) 2018 Section 7.1.3.1 (Exit High
exceeding 30 are separated by walls having a fire- Egress)
2018 Section 7.1.3.1 separated by walls having a fire-resistance rating of 1 hr. NFPA 101
Access Edition 2018 Table 40.2.6.1
Corridors)
5 Means of Egress resistance rating of 1 hr. High NFPAAccess
(Exit 101 Table
Corridors) (Maximum Travel Distance to Exits)
40.2.6 (Maximum NFPA 101 Edition 2018 Table 42.2.6 (Maximum
6.1 All paths of egress are provided with compliant TravelPart
BNBC Distance to
4 Section 6.1.1 All paths of egress are provided with compliant means of illumination. TravelPart
BNBC Distance to Exits)
4 Section 3.16 (MEANS OF EXIT Medium
6 Means of Egress means of illumination. Medium Exits)(MEANS OF EXIT
3.16 SIGNS AND ILLUMINATION)
NFPA 101
SIGNS ANDEdition
7.1 Doors are not locked in the direction of egress 2018 Table
BNBC Part 440.2.6.1
ILLUMINATION) Section 7.1.1 Doors are not locked in the direction of egress under any conditions. All BNBC Part
BNBC Part 8
4 Section
Section 3.9.8
1.5 (ILLUMINATION OF High
under any conditions. All hasps, locks, slide bolts, (Maximum Travel
3.9.8 hasps, locks, slide bolts, and other locking devices have been removed where EXIT SIGNS AND MEANS OF ESCAPE)
and other locking devices have been removed Distance
BNBC Partto8Exits)
Section required.
where required. NFPA 101 Edition
7 Means of Egress High 1.5 (ILLUMINATION
2018 Table 42.2.6
OF EXIT SIGNS AND
(Maximum Travel
MEANS OF ESCAPE)
Distance to Exits)

8.1 All doors in a means of egress are of the side- BNBC Part 4 Section 8.1.1 All doors in a means of egress are of the side-hinged swinging type. High
8 Means of Egress hinged swinging type. High 3.9.5 BNBC Part 4 Section 3.9.5

9.1 Illuminated exit signs are provided with battery NFPA 101 Edition 9.1.1 Illuminated exit signs are provided with battery backup or emergency NFPA 101 Edition 2018 Section 7.10.5.2 High
backup or emergency power and are continuously 2018 Section 7.10.5.2 power and are continuously illuminated. (Continuous Illumination)
illuminated. (Continuous
9 Means of Egress High Illumination)

10.1 Walking surfaces along the path of egress are NFPA 101 Edition 2018 10.1.1 Walking surfaces along the path of egress are uniformly slip resistant. NFPA 101 Edition 2018 Section 7.1.6 (Walking Medium
10 Means of Egress uniformly slip resistant. Medium Section 7.1.6 (Walking Surface in the Means of Egress)
Surface in the Means of
11.1 Landings are provided on both sides of doors Egress)
IBC Edition 2015 11.1.1 Landings are provided on both sides of doors used along the path of IBC Edition 2015 Section 1010.1.5 (Floor High
11 Means of Egress used along the path of egress. Doors do not swing High Section 1010.1.5 egress. Doors do not swing out over stairs. Elevation)
out over stairs. (Floor Elevation)
12.1 Ramps do not have a running slope greater BNBC Part 4 Section 12.1.1 Ramps do not have a running slope greater than 1 in 8 (12.5 percent) BNBC Part 4 Section 3.11 RAMPS Medium
12 Means of Egress than 1 in 8 (12.5 percent) and have handrails on Medium 3.11 RAMPS and have handrails on both sides of the ramp. NFPA 101 Edition 2018 Section 7.2.2.4 (Guard
both sides of the ramp. NFPA 101 Edition and Handrails)
13.1 A Fire Safety Director position has been filled BNBC Part 4 A 4.8
2018 Section (Fire
7.2.2.4 13.1.1 A Fire Safety Director position has been filled. Low
with proper training from the appropriate Safety Plan)
13 Fire Safety Program Low (Guard and Handrails) BNBC Part 4 A 4.8 (Fire Safety Plan)
authority.

14.1 Storage areas underneath the cutting tables As per requirement 14.1.1 Storage areas underneath the cutting tables are clear of combustibles. Medium
14 Fire Safety Program are clear of combustibles. Medium
15.1 Fire protection system has been found Please see the 15.1.1 Aisles in storage areas are free of storage based on design criteria used NFPA 13 (Edition 2013) Chapter 16 (Protection Medium
functional during the verification and updated references against for the sprinkler system. of Rack Storage of Class I Through Class IV
inspection, testing and maintenance documents as individual sub- Commodities)
per NFPA 25 are available at the factory. question. 15.1.2 All storage is maintained with a 460 mm (18 in.) minimum clearance NFPA
NFPA 13
13 (Edition
(Edition 2013)
2019) Chapter
Chapter 825Section 8.5.6 Medium
from the top of storage to the sprinkler deflector. (Clearance from Deflector to Storage)
NFPA 13 (Edition 2019) Chapter 10 Section
10.2.8 (Clearance to storage (Standard pendent
and upright spray sprinklers))

15 Fire Protection System High


15.1 Fire protection system has been found Please see the
functional during the verification and updated references against
inspection, testing and maintenance documents as individual sub-
per NFPA 25 are available at the factory. question.

15.1.3 All valves controlling the automatic sprinkler systems are NFPA 13 (Edition 2013) Chapter 6 Section 6.9 Medium
electrically supervised by a listed fire alarm system control unit. (Waterflow Alarm Devices)
NFPA 13 (Edition 2019) Chapter 7 Section 7.7
15.1.4 Are fire department connections provided and clearly identified for the (Waterflow
NFPA 14 (Edition
Alarm2019) Chapter 4 Section 4.8
Devices) Medium
Fire Protection Systems? (Fire Department Connections)
15.1.5 Are hangers, bracing, and restraints properly installed and supporting NFPA 13 (Edition 2013) Chapter 9 Hanging, Medium
the system piping? NFPA 101and
Bracing, (Edition 2012)
Restraint of Chapter 9 Section
System Piping.
9.7(
NFPAAutomatic Sprinklers
13 (Edition and Other
2019) Chapter 17 Installation
15.1.6 Are hose connections and hoses, if required, provided for the standpipe Extinguishing
NFPA
requirements Equipment)
14 (Edition
for 2019) Chapter
Hanging 7
of supports and High
system at required locations based on system class? NFPA 101 (Edition
system piping. 2018) Chapter 9 Section
9.7( Automatic Sprinklers)
15.1.7 Are identification signs for the sprinkler system installed at the required NFPA 13 Low
locations?
15.1.8 Are inspection, maintenance, and testing procedures of the fire pump NFPA 25 Edtion 2017 Chapter 8 Fire Pumps Low
documented and up to date?
15.1.9 Are inspection, maintenance, and testing procedures of the sprinkler NFPA 25 Edtion 2017 Chapter 5 Sprinkler Low
system documented and up to date? Systems Table 5.1.1.2
15.1.10 Are inspection, maintenance, and testing procedures of the standpipe NFPA 25 Edtion 2017 Chapter 6 Standpipe and Low
and hose system documented and up to date? Including inspection and Hose Systems Table 6.1.1.2
testing of hoses if provided.
15.1.11 Are sprinklers spaced and installed at the required heights in order to NFPA 13 Edition 2019 High
provided required coverage and protection?
15.1.12 Are storage racks and shelves compliant based on class of commodity NFPA 13 (Edition 2019) Chapter 20, High
storage? 21,22,23,24,25
15.1.13 Are there any other fire suppression systems installed within the On basis of inspection High
building?
15 Fire Protection System High 15.1.14 Commodity Class used for the design of the sprinkler system? Low
NFPA 13 Chapter 5
NFPA 13 Edition 2019 Chapter 4
15.1.15 Design criteria of sprinkler system? Low
NFPA 13
15.1.16 Does the automatic sprinkler system have an approved audible device NFPA 13 (Edition 2013) Chapter 6 Section 6.9 Low
activated by waterflow equal to the flow of one sprinkler? (Waterflow Alarm Devices)
NFPA 13 (Edition 2019) Chapter 7 Section 7.7
15.1.17 Does the building have a listed & functional fire pump as per NFPA 20 Alarm Devices)
(Waterflow High
requirement?
15.1.18 Does the building have a Standpipe System? IBC (Edition 2015) Section 905, Art.905.3.1 - High
Applicable for new building construction
15.1.19 Does the Standpipe System Class comply with the type of Class NFPA 14 (Edition 2019) Chapter 5 and High
required for the building? requirements for Class I, Class II, or Class III
Standpipes
15.1.20 Is signage for the standpipe system installed at required locations and NFPA 14 (Edition 2019) Chapter 6 Low
on required components?
15.1.21 Is the building protected by an automatic sprinkler system? NFPA 101 (Edition 2018) Section 11.8.3.1 & High
Section 3.3.37.7 and NFPA 13
15.1.22 Sprinkler system piping is free of mechanical damage, leakage, and NFPA 25 Edition 2017 Chapter 5 Section 5.2.2 Medium
corrosion. Pipe and Fittings
15.1.23 Sprinkler system piping is not subjected to external loads by materials NFPA 25 Edition 2017 Chapter 5 Section 5.2.2.2 Low
either resting on the pipe or hung from the pipe?
15.1.24 Sprinklers do not show signs of leakage, are free of corrosion, have NFPA 25 Edition 2017 Chapter 5 Medium
not been painted, and are not physically damaged.
15.1.25 Standpipe system piping is free of mechanical damage, leakage, and NFPA 25 Edition 2017 Chapter 6 Standpipe and Medium
corrosion? Hose Systems
15.1.26 Occupancy Classification used for the design of the sprinkler system? NFPA 13 (Edition 2019)Chapter 4 General Low
Requirements
16.1 Fire alarm and detection system has been Please see the 16.1.1 Are notification and initiation devices for the fire alarm system installed NFPA 72 High
found functional during the verification and references against at required locations based on occupancy type?
updated inspection, testing and maintenance individual sub-
documents as per NFPA 72 are available at the question 16.1.2 Trouble or alarm notifications were not indicated on the fire alarm NFPA 72 High
factory. control panel.
16 Fire Protection System High 16.1.3 Is the fire alarm and detection system monitored by a central station NFPA 72 Section 3.3.284 (Supervising Station Medium
monitoring service or directly connected to the Fire Service and Civil Defense? Alarm Systems)
NFPA 72 Edition 2019 Section 3.3.291
16.1.4 Does the building have an automatic or manual fire alarm and NFPA 72 Edition
(Supervising 2019Alarm
Station Fire Alarm and Detection
Systems) High
detection system?
17.1 Exit discharge is directly to the exterior of the Please see the 16.1.4 Does the building have an automatic or manual fire alarm and NFPA
IBC 101 Edition
Edition 2018 Section
2015 Section 9.6.4Discharge)
1028 (Exit High
building, unless the requirements of Egress references against detection system? (Emergency Forces Notification)
17 Means of Egress Court.are met, at grade or provides direct access to High individual sub-
17.1.2 Interior exit stairways and ramps terminate at an exit discharge except NFPA 101 Edition 2018 7.7.2 (Exit Discharge High
grade. Exit discharge shall not reenter a building. question
where terminating at a rated exit passageway. Through Interior Building Areas)
18.1 Means of egress are free from impediments, Please see the 18.1.1 Landings are provided with the same width in the direction of egress NFPA 101 Edition 2018 Section 7.2.2.3.2 High
obstructions, and stored materials. references against travel as the stair clear width provided at each level and at intermediate (Landings)
individual sub- landings. Existing landings that are less than the stair width, shall reduce theBNBC Part 4 Section 3.10.2
question 18.1.2
overallMeans of capacity
available egress areoffree
the from
stair. impediments, obstructions, and stored NFPA 101 Edition 2018 Section 7.1.9 High
materials. (Impediments to egress)
NFPA 101 Edition 2018 Section 7.1.10 (Means
18.1.3 Means of egress have a minimum ceiling height of 2.3 m (7 ft 6 in.) with NFPA 101reliability)
of egress Edition 2018 Section 7.1.5 Medium
projections from the ceiling not less than 2.03 m (6 ft 8 in.). (Headroom)
18.1.4 Aisles are provided with the minimum unobstructed clear width of 0.9 NFPA 101 Chapter 23 Section 23.2.3.2 High
m (36 in) based on occupant loads. BNBC Part 4 Section 3.7 (CORRlDORS AND
PASSAGEWAYS)
BNBC Part 4 Table 4.3.2 (mentioned about
18 Means of Egress High corridors only)

18.1.5 The path of egress along the means of egress is not reduced at any BNBC Part 4 Table 4.3.2 High
point along the path of travel and is sufficient for the occupant load.
18.1.6 Ramps used in a means of egress do not reduce the overall means of BNBC Part 4 Section 3.11 RAMPS High
egress width. The
minimum width shall be 1.1 m (44 in.).
18.1.7 Changes in elevation of walking surfaces do not exceed 6.35 mm (1/4 NFPA 101 Edition 2018 Section 7.1.7 (Changes Medium
in) unless provided with a beveled slope of 1 in 2 that does not exceed 12.7 in Level in Means of Egress)
mm (1/2 in).
19.1 Compliant guards are provided on the open Please see the 19.1.1 Handrails are provided on both sides of each stairway. Intermediate NFPA 101 Section 7.2.2.4.4 (Handrail Details) Medium
sides of egress components where the elevation references against handrails are provided when the stair width exceeds 2.2 m (87 in.). Handrails NFPA 101 Edition 2018 Section 7.2.2.4.5
19 Means of Egress exceeds 760 mm (30 in) above the ground or floor Medium individual sub- are not mounted lower than 760 mm (30 in.) or higher than 1100 mm (44 in.). (Handrail Details)
19.1.2 Compliant guards are provided on the open sides of egress NFPA
below. question BNBC 101
PartEdition 2018
4 Section Section 7.1.8 (Guards)
3.10.5 Medium
components where the elevation exceeds 760 mm (30 in) above the ground or
floor below.
20.1 Stair treads are of nominal uniformity. BNBC Part 3 Section 20.1.1 Stair treads are of nominal uniformity. BNBC Part 3 Section 1.12.5.2 Medium
20 Means of Egress Medium 1.12.5.2
21.1 Stairwells are free from stored materials and NFPA 101 (Edition 21.1.1 Stairwell are free from any type of stored materials & electrical NFPA 101 (Edition 2018) Section 7.1.3 High
21 Means of Egress electrical appliances? High 2018) Section 7.1.3 appliances
22.1 Emergency egress maps are posted at the Please see the 22.1.1 An emergency evacuation plan has been developed and communicated BNBC Part 4 A 4.8 (Fire Safety Plan) Medium
entrance to each exit stair or main point of egress. references against to all employees.
individual sub- NFPA 101 Edition 2018 Section 4.8.2 (Plan
question Requirements)
NFPA 101 A.4.8.2.1

22 Means of Egress Medium


22.1.2 Emergency egress maps are posted at the entrance to each exit stair or As per requirement Medium
main point of egress.

23.1 Are the required number of people trained Bangladesh Labour 23.1.1 Are the required number of people trained and certified in fire fighting, Bangladesh Labour Rules 2015 High
and certified in fire fighting, first aid, and rescue Rules 2015 first aid, and rescue training by the appropriate authority.
training by the appropriate authority.
23 Fire Safety Program High

24.1 All applicable permits are up to date including license provided by 24.1.1 Are all applicable permits up to date including Fire License & Boiler license provided by the local authority Low
24 Fire Safety Program Fire License & Boiler License. Low the local authority License.
25.1 Approval documents are available for fire As per requirement 25.1.1 Approval documents are available for fire proof hybrid separation if As per requirement Medium
25 Fire Safety Program proof hybrid separation if constructed. Medium constructed.

26.1 AHJ (Authorities Having Jurisdiction) approval As per requirement 26.1.1 AHJ (Authorities Having Jurisdiction) approval documents are available As per requirement Medium
documents are available if applicable for a certain if applicable for a certain condition.
26 Fire Safety Program condition. Medium

27.1 Occupant loads on each level (floor) do not Please see the 27.1.1 Occupant loads are posted for every assembly and production floor in a NFPA Section Edition 2018 12.7.9.3 (Occupant Medium
exceed the capacity of the available means of references against conspicuous space near the main point of egress. Load Posting)
egress. individual sub-
question 27.1.2 Occupant loads on each level (floor) do not exceed the capacity of the BNBC Part 4 Section 3.6 (CAPACITY OF EXIT High
available means of egress. COMPONENTS) Table 4.3.2
27.1.3 Occupied roofs are provided with the minimum number of exits BNBC Part 4 Section 3.5.5 (Roofs) & Table 4.3.2 High
required as a story.
27.1.4 The number of means of egress from any floor or story is not less than BNBC Part 4 Section 3.14.3 High
2 except where a single exit is permitted or where a greater number is
required.
27.1.5 The number of means of egress from any floor or story is not less than BNBC Part 4 Section 3.14.3 High
27 Means of Egress High 3 when the occupant load exceeds 500 per story and not less than 4 when the
occupant load exceeds 1000 per story.

27.1.6 Exit stairs have a minimum width as per standard. NTPA Section 2.5.2 (For existing RMG building) High
BNBC Part 4 Table 4.3.4 (For new building)

27.1.7 Stair designation signs are provided at each floor entrance from the BNBC Part 4 Section A 4.3 (Stair and Elevator Low
stair to the floor in English and Bengali. Signs indicate the name of the stair Identification)
and the floor level. Signs are posted adjacent to the door. NFPA 101 Edition 2018 Section 7.2.2.5.4
27.1.8 Every door in a stair enclosure serving more than 4 stories is provided BNBC PartIdentification)
(Stairway 4 Appendix A 4.4 (Stair re-entry Low
with re-entry provisions? Provision)
NFPA 101 Edition 2018 Section 7.2.1.5.8
28.1 Fire Department pre-planning has been BNBC Part 4 A 4.7 (Fire 28.1.1 Fire Department pre-planning has been completed. BNBC Part 4 A 4.7 (Fire Safety Plan) Low
28 Fire Safety Program completed. Low Safety Plan)

29.1 Chemicals and other flammable materials are BNBC Part 3 Section 29.1.1 Chemicals and other flammable materials are stored within approved BNBC Part 3 Section 2.13, Table 3.2.1 and Table Medium
stored within approved enclosures. 2.13, Table 3.2.1 and enclosures. 3.2.7
29 Fire Protection Construction Medium Table 3.2.7

30.1 Fire extinguishers are in good condition and Please see the 30.1.1 Are portable fire extinguishers installed throughout the building at BNBC Part 4 Section 4.10 and NFPA 10 Edition Medium
inspection, testing, maintenance documents as per references against required locations and mounted at the correct height? 2018
NFPA 10 are available at the factory. individual sub-
question 30.1.2 Fire extinguishers are inspected, tested, and maintained as required. NFPA 10 Edition 2018 Chapter 7 Medium
30 Fire Safety Program Medium
30.1.3 Portable fire extinguishers have been selected based on potential fire NFPA 10 Edtion 2018 Chapter 5 Medium
class and hazards?
31.1 Fire doors are in good condition and 31.1.1 Fire doors are inspected and tested on a quarterly basis. NFPA 80 Edition 2019 Chapter 5 Medium
inspection, testing, maintenance documents as per NFPA 80 Edition 2019
NFPA 80 are available at the factory. Chapter 5
31 Fire Safety Program Medium

32.1 Hotwork has been conducted as per NFPA 51B NFPA 51B 32.1.1 A hot-work permit program has been established. NFPA 51B Low
32 Fire Safety Program and permission documents are available at the Low
factory.
33.1 Housekeeping policy and procedures have BNBC Part 4 D 20 33.1.1 A written housekeeping policy is established and enforced. BNBC Part 4 D 20 (Housekeeping) Low
33 Fire Safety Program been implemented. Low (Housekeeping)

34.1 Factory is conducting fire drill under the BNBC Part 4 Section A 3 34.1.1 Fire Drills are conducted at required intervals based on building use BNBC Part 4 Section A 3 (FIRE DRILL) Medium
appropriate authority and all records are (FIRE DRILL) type. BNBC Part 4 Section 1.4 (FIRE DRILL)
documented. BNBC Part 4 Section 1.4
34 Fire Safety Program Medium (FIRE DRILL)

35.1 Maintenance & testing documents for Please see the 35.1.1 Emergency power for exit signs is tested at least once per year. If NFPA 101 Edition 2018 Section 7.9.3 (Periodic Medium
emergency lights and Exit Signages are available at references against battery operated, these lights are tested on a monthly basis. Functional Testing of Emergency Lighting Equipment)
the factory. individual sub- testing of battery powered signs is provided for a minimum 90 min once per NFPA 101 Edition 2018 Section 7.10.9 (Testing
question 35.1.2
year. Emergency power for means of egress illumination is verified at least NFPA 101 Edition 2018 Section 7.9.3 (Periodic
and Maintenance) Medium
once per year. If battery operated lights are used, these lights are tested on a Testing of Emergency Lighting Equipment)
35 Fire Safety Program Medium monthly basis. Functional testing of battery powered lights is provided for a
35.1.3 Exit90
signs
NFPA 101 Edition 2018 Section 7.10.9 (Testing
minimum minhave
onceappropriate
per year. illumination levels and contrasting graphics. BNBC Part 8 Section 1.5 (ILLUMINATION OF
and Maintenance) Low
EXIT SIGNS AND MEANS OF ESCAPE)
35.1.4 Illuminated exit signs are placed at entrances to exits and along the NFPA 101 Edition 2018 Section 7.10.1.2.2 Medium
path of egress anywhere the continuation of egress is not obvious or there is a BNBC Part 4 Section 3.16.1.1 (Location)
change in the direction of the path of travel. NFPA 170
36.1 Are all approved proposed and as- built design As per requirement 36.1.1 Are all approved proposed and as- built design of fire protection As per requirement High
of fire protection system, detection system and fire system, detection system and fire door checklists available at the factory?
36 Fire Safety Program door checklists available at the factory? High

37.1 Flammable gas connections or gas cylinders As per requirement


are existed within the factory premises.
37 Fire Safety Program N/A

You might also like