Job Card-3173-Al Saad Sport Club-August-Chiller-2
Job Card-3173-Al Saad Sport Club-August-Chiller-2
Details of work
CARRIED OUT MONTHLY SERVICING OF CHILLER # 2, CHECKED AND CLEANED ELECTRICAL PANEL WITH AIR BLOWER, CLEANED ALL THE CONDENSER
COILS WITH WATER PUMP, STARTED THE CHILLER, CHECKED ALL PARAMETERS, LEFT THE CHILLER CIRCUIT B IN RUNNING CONDITION.
Customer comments
Sign Sign
DESCRIPTION
NOTE:
DISCHARGE PRESSURE OF BOTH CIRCUITS ARE VERY HIGH AND TEMPERATURE OF COMPRESSORS ARE VERY HIGH DUE TO 4 FAN MOTORS NOT
WORKING.
NEED TO REPAIR AND REPLACE THE FAN MOTORS ASAP SO AS TO PREVENT FURTHER ELECTRICAL AND MECHANICAL DAMAGE OF COMPRESSORS
P.O Box 37405, Doha – Qatar
Email:info@teamcoolqatar.com
CHECK LIST
TEMPERATURES / PRESSURES
COOLER ENTERING FLUID EWT 10.9 ˚C
COOLER LEAVING FLUID LWT 6.6 ˚C
CONTROL POINT CTPT 6.4˚C
CAPACITY CAP 70%
OUTSIDE AIR TEMPERATURE OAT 38 ˚C
COMMENTS:
1. NEED TO REPAIR AND REPLACE 2 FAN MOTOR IN CKT A
2. NEED TO REPAIR AND REPLACE 2 FAN MOTOR IN CKT B
SIGN: SIGN:
the job can be completed without specific risk for working heights? X
Height
all steps,platforms or scaffolding are safe? X
Others:
how do you evaluate the total risk for this job site? 0
0 = Low
Risk
1 = Avg
2 = High Need customer support
COMMENTS: