Ans#1: Front View of 630kva Distribution Transformer

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

ANS#1: FRONT VIEW OF 630KVA DISTRIBUTION TRANSFORMER

TOP VIEW OF 630KVA DISTRIBUTION TRANSFORMER

SIDE VIEW OF 630KVA DISTRIBUION TRANSFORMER


ANS#2:
SYMBOL VALUES DESCRIPTIONS
VPT 15.396mm Volts per turn (V/turn)
EU 96mm Thickness of core leg (mm).
turnsLV 15 Number of turns of LV
FDmax 17000 Magnetic induction (Gauss)
CSF 0.965 Core stacking factor
D 220mm Width of core leg
CCEE 3mm Core to coil each end
DHV-C 39mm Distance between HV winding and core
DLV-C 6.5mm Distance between LV winding and core
LDSPLV 0.909 Layer direction space factor of LV winding
t LV 0.79mm Thickness of LV conductor
Diameter of HV conductor
dHV 1.8mm
∆ dHV 0.111mm Insulation of HV conductor
BILHV 125kv Basic insulation level of HV winding
BILLV 10kv Basic insulation level of LV winding
gMM 7650kg/m3 Mass density of magnetic steel
SNLLTF 1.87w/kg Specific no-load loss
NLLg 1100w Guaranteed no-load loss
D3 271.34 mm Coil equivalent external diameter immediately after the tube
paper (mm)
D7 333.29 mm Coil equivalent external diameter immediately after the LV
winding, including the LV cooling ducts (mm)
D9 347.13 mm Coil equivalent external diameter immediately after the
I HV −LV insulation (mm)
LGHV 250.16 mm Dimension of cooling ducts of HV winding (mm)
DuctsHV 12 Number of ducts of HV winding
DuctsLV 10 Number of ducts of LV winding
G 261mm Height of core window (mm)
F1 69.19 Window width of small individual core (mm)
F2 138mm Window width of large individual core (mm)
EU 96mm Thickness of core leg (mm)
SPLD HV 43.11mm total thickness of the LV winding
SPLD LV 26.08mm total thickness of the HV winding
BLD HV 46.47mm Thickness of HV winding (mm)
B LD LV 17.66mm Thickness of LV winding (mm)
I HV −HV 6.92mm Insulation outside HV winding (mm)
I HV −LV 6.64mm Insulation between LV and HV winding (mm)
I LV −C 1.5mm Insulation between LV winding and core (mm)
TD HV 177mm Width of HV layer (mm)
TD LV 242mm Width of LV layer (mm)
D HV −C 39mm Distance between HV winding and core (mm)
D LV −C 6.5mm Distance between LV winding and core (mm)
HCP 800mm Height of corrugated panel (mm).
TH 1015mm Tank height (mm)
K 9mm Distance between two adjacent cores (mm)
MW 201mm Width of the mould of the coil (mm)
ML 226mm Length of the mould of the coil.
MT HV 1251.11mm Mean turn length of HV winding (mm)
MT LV 949.75mm Mean turn length of LV winding (mm)
TurnsMainLV 15 Width of LV conductor with insulation
TurnsMainH 1299 Number of turns of HV winding at voltage V HV
V
TurnWidthLV 242mm Width of LV conductor with insulation (mm)
TurnWidthHV 1.911mm Width of HV conductor with insulation (mm)