Actuator Lifting Test
Actuator Lifting Test
Events happened
1. While giving opening command from 20 to 40 % or from 40 to 60 %, stand by COP got
auto started.
2. During giving command from 0 to 100 %, COP got auto started but still ESV closed.
Date: - 01.06.2016
Note: The same readings observed in both coupled and decoupled condition
Note: The same readings observed in both coupled and decoupled condition
Remarks:-
1. When command given from 0% to 25% directly, the standby COP auto started as control
oil pr low. Pr switch acted.
2. When command given from 75% to 100%, both COP-1&2 were in service, still then
control oil pr low. Pr switch acted.
100% command
Remarks:- In all above cases Control Oil Pump was not getting started in auto.
1. When command given from 0% to 100% directly, the standby COP auto started as
control oil pr low(12.75ksc DCS value. Pr switch acted
1. When command given from 0% to 100% directly, the standby COP auto started as
control oil pr low& ESV closed.
Actuator lifting test on 30.05.2019
1. When command given from 0% to 20% directly, Control oil pr. was dropping from 13.88
ksc. to 13.65 ksc. and normalized.
Actuator lifting test on 26.06.2019
1. When command given from 0% to 100% directly, Control oil pr. was dropping from
13.90 ksc. to 11.32 ksc. and Turbine trip ,COP-02 auto start.