Professional Documents
Culture Documents
Procedures
Procedures
5
5-1
P ROCEDURES
T
his chapter covers various procedures
and topics and is presented to offer
examples of typical rig activities. Please
note that generalities are covered, not specifics.
Procedures must Procedures must be written on a per-well basis
and detailed for the type of rig and operation.
be written on a Crew assignments may also change on different
wells or activities and must be individually
per-well basis and addressed.
Shut-in
with Pipe on
In Bottom
Close
2 Close
1
Open
3 Monitor & record
Well
Modified
Shut In
Close
1 Close Closed Closed
Shut-in
3 Monitor & record
Open procedures
2 Open
vary from job
to job but the
basics do not
change:
• protect the
Soft Shut crew
In • stop the flow
• gain time
Close while
monitoring pressure • read pressures
2 Close 3
1. Open choke line valve on stack 1. Close designated BOP 1. Open choke line valve on stack
2. Close designated BOP 2. Open choke line valve on stack 2. Close designated BOP
3. Notify company personnel 3. Notify company personnel 3. Close choke, watching casing
4. Read and record SIDPP 4. Notify company personnel 4. Read and record SIDPP pressure
and SICP each minute and SICP each minute to ensure limitations are
not exceeded or pressure trapped
5. Read and record SIDPP
and SICP each minute
C HAPTER 5
5-4
Shut-In
Procedures
Hard Shut In
1
Shut-in
While Tripping
Close
3 4 Monitor &
Well
Close
record
Open
2
Modified Shut
1 In
Close
2 Close Closed Closed
Open
3 Open
Soft Shut In
1
Close while
monitoring
3 Close 4 4 Monitor &
Top drive record
systems employ 5 Once choke
Open closed monitor
a remotely 2
operated FOSV & record
which is always
made up on
the drive.
Typically the upper annular is used to shut An important consideration on any trip
in the well. Once shut in, if exact spacing is is the location of collars in the derrick. They
unknown due to a trip or above factors, pull should be racked in a manner not blocking
pipe slowly and monitor the weight indicator the drillpipe in the event pipe must be run
and accumulator flow meter. Weight should back in the hole.
increase slightly as the tool joint is stripped
through the annular. As it goes through, the
If a well is shut annular will use more fluid to maintain closure KICKS WHILE OUT OF HOLE
in with drill pressure against the pipe body. Spacing can
collars in the then be calculated.
Once spacing has been verified, close the There are many philosophies as to what to
rotary, it is
hang off rams. Hang off using the drillstring do with regard to kick detection when out of
possible that
well pressure compensator and close the ram locks. If the hole. Possibilities include closing the blind
will force the possible, bleed off pressure between the closed ram (choke closed or open), closing a pipe ram
pipe out of ram and annular, then open the annular. and covering the rotary. All present different
the well. problems in kick detection while out of the hole,
but these problems can be solved by monitoring
the hole or pressure gauges and implementing
SHUT IN ON COLLARS contingency procedures. Generally:
1. If the blind rams are closed and choke
One of the more critical shut-in situations open: monitor the choke for flow.
develops when collars are pulled through the 2. If the blind rams and choke are closed:
rotary. The annular preventer is typically used, monitor the casing (annulus) pressure gauge
but situations complicating the shut-in process for pressure buildup. Some operators have
must be considered, such as the use of spiral a policy, when the bit clears the rotary,
collars or the lack of a float or backpressure of opening the HCR, closing the remote
valve. In addition, there is the possibility the choke, filling the hole and closing the blind
influx may be close to surface; if pressure on rams. If gas was swabbed into the well
shut in acting upwards is greater than the during a trip, then there will be an increase
weight of the collars acting downward, the well in surface pressure after a period of time
may try to eject the collars when shut in is depending on migration rates.
attempted. 3. If the pipe rams are closed: monitor the
Often the collars have a different thread flowline for flow.
size and/or type. The proper crossover subs Note: Just because there is no flow from
must be available on the rig floor, made up the wellbore does not mean that there is not a
with a safety valve and ready for installation. kick in the well. If technique 2 above is used in
The procedures for making and picking up this areas where temperatures drop below freezing,
assembly must be addressed. lining up on a choke could freeze the mud and
A plan of action should be decided upon and plug the choke, giving a false reading. Prior
questions, such as the following, answered. to opening the blinds in techniques 1 and 2
above, ensure that the choke is open to vent
w Is it safer to pull the remaining collars or
the stack and check that personnel are clear
install the crossover/safety valve assembly?
of the wellbore. Gauges have been known to
w On shut in, if the collars begin to be ejected be inaccurate or not register low pressure. If
from the well, will a choke be used to relieve technique 3 above is used, closing pipe rams on
pressure below the annular? (Remember that an open hole may keep large junk from falling
this may also allow more influx to enter the into the well and allow you to see if the well is
well.) flowing, but may also damage ram front-packer
w If drill collars must be dropped, how will this seals or reduce the operating life of the pipe
be done? rams.
P ROCEDURES
5-7
If a kick is
detected while
out of the hole,
most operators
Kicks taken
will use stripping
while running
casing are techniques to
extremely run pipe to
dangerous.
bottom.
When flow is detected while out of the several stands of pipe back into the hole may
hole, the well should be shut in. This stops be considered. It must be understood that
the influx, allows pressures to be determined running pipe back into an open and active well
and provides time to decide the next course is dangerous and has lead to several disasters.
of action. Most operators will use stripping It can result in significantly higher surface
and volumetric techniques to run pipe to pressure than if the well were shut originally. If
bottom while maintaining bottomhole pressure an underbalanced condition exists, additional
control. influx will continue entering the well and
Where formation characteristics are well will accelerate the rate of flow as more mud
known (i.e., a tight formation not exhibiting a is displaced. Also, gas migration and upward
high flow rate), and where the danger of gas displacement of the kick by stinging the
to the surface is minimal, the decision to run pipe into the influx may reduce the effective
C HAPTER 5
5-8
Flaring gas
on a floating
operation.
hydrostatic pressure, thereby accelerating or the annulus, and is usually shut off first. The
allowing additional influx to enter. And, if the opposite situation exists while running casing,
well has to be shut in while running pipe, there when the annulus should be shut in first.
may not be enough pipe weight to overcome Prior to running casing, BOPs should be
the force of the kick. Pipe rams should be equipped with casing rams and pressure tested.
closed to prevent the well from forcing pipe A circulating swage with a high pressure/low
out of the hole. If collars were run, pipe rams torque valve must be made up, positioned
will not prevent the collars from unloading near the rotary table and installed immediately
from the well. Under no circumstances should after the BOPs have closed, in case the float
pipe be run into the well (BOPs open) if a equipment fails during a well control event.
Under no significant flow is present or if there is gas
circumstances
Floating rigs should have a crossover from
at surface. the casing to drillpipe to allow the string to
should pipe
be run into an be hung off if necessary. Closing pressure on
open well if annular preventers should be checked against
a significant SHUT IN WHILE RUNNING CASING the collapse pressure of the casing and adjusted
flow is present. if necessary before running casing. An alternate
The main objective in a closing sequence to this on surface stack rigs is to lower a joint of
is to close off the smallest and most vulnerable casing into the annular, bleed all pressure off
flow path first. The inner diameter of the string the annular pressure regulator and gradually
is typically the smaller diameter compared with increase the closing pressure 100 psi (6.89 bar)
P ROCEDURES
5-9
at a time until closure around the casing is 5. There must be a means to cut the
obtained. From this point an additional 100 to wireline should the need arise. This can
200 psi (6.89 to 13.79 bar) should be sufficient be accomplished with wireline shear rams
to form a seal. Again, before adding the seal and a hydraulic hand pump (on the rig
pressure, check against the collapse pressure. If floor) or a set of shear or blind/shear Close
additional pressure is required to obtain a seal, rams in the BOPs. Safety valves (FOSV and cooperation
adjust the pressure regulator. Master) should not be used, as they are not between the
designed for this type of service. rig crew and
the wireline
crew is important
SHUT IN WITH if kicks are to
BRAIDED WIRELINE HANDLING GAS be handled
AT THE SURFACE properly during
Wireline operations typically employ a wireline
lubricator if there is a possibility of pressure at Until the nature of the kick has been operations.
the surface during the operation. The lubricator determined, the entire rig should be alerted to
assembly typically consists of a stuffing box, the possibility of the presence of toxic and/or
grease injectors, lubricator joints or tube bodies, explosive gases. All assigned personnel should
blowout preventers and a bleed or pump-in valve check gas detectors, breathing and warning
(high pressure/low torque). The equipment devices for proper operation. Once the well
may be nippled differently, depending on the has been shut in, the responsible personnel
application. Equipment may be: should immediately check out the wellhead,
BOPs, manifolds, choke and kill lines, etc.,
w Flanged up to an annular preventer for possible leaks. Offshore rigs should post a
w Secured inside annular preventer or rams watch for signs of gas around the rig. Should
w Made up to a gauge flange (crown valve) leaks be detected, report them immediately.
on a Christmas tree. In addition, during the kill operation the
above items need to be checked frequently. If a
Close cooperation between the rig crew
gas leak is observed, report it immediately – do
and the wireline crew is essential if kicks are to
not try to stop it before notifying supervisors.
be detected and handled properly. A suggested
Make sure that the gas is not toxic. If tightening
shut in sequence follows.
a connection to repair leaks, a brass hammer
1. Notify the wireline operator to cease should be used to prevent sparks.
operations. On shut in, align the choke to the gas
2. The driller closes the bleed or pump in separator. Make certain that the separator
valve. is functioning properly. During circulation,
monitor the separator for pressure buildup and
3. Wireline BOPs are closed manually or by
blowby. Ascertain that the degasser is operating
a hydraulic hand pump. The driller should
correctly and the pits are aligned correctly.
designate the floorhand(s) to perform this
Confirm that the downwind vent and flare
task. It should be noted that two wireline
lines are open and the igniter is operational. If
ram type BOPs can be used, the bottom
a derrick flare line must be used, then caution
preventer inverted. The bottom ram in
must be exercised to ensure that any liquids
this situation is used as a high-pressure seal or heavy gases, which could be toxic and/or
against grease that will be injected between explosive, do not settle on the rig.
the two closed rams to provide a viscous Extinguish all potential sources of ignition,
grease seal against the braided wireline. including welding activities, engines and
4. Notify supervisors that the well is shut in. equipment not necessary to the operation.
C HAPTER 5
5-10
EXAMPLE PROCEDURE
DIVERTER PROCEDURE
WHILE DRILLING 1. Do not shut pump(s) down. (Loss of
mud volume as the well unloads will
Diverters are BOPs (usually of the annular result in loss of equivalent circulating
type) which are designed to protect the rig density [ECD] and will reduce bottomhole
pressure, causing the well to unload at a
from shallow blowouts by closing off the well
higher rate.)
under the rig, while allowing the influx to
evacuate safely through the blooey line(s) below 2. Chain down the brake.
Diverter the preventer. Diverter procedures must be 3. Open downwind diverter line.
procedures implemented quickly because the time from 4. Close the diverter packer. Most rigs have
must be kick detection until the kick reaches surface coupled the diverter line and diverter
implemented may be minimal. The warning signs of a packer together to ensure a correct closing
quickly. shallow gas kick include: sequence.
w An increase in flow (usually quite dramatic) 5. Pump at maximum rate with drilling
fluid, seawater or heavy mud from reserve
w Mud coming over the bell nipple and/or
pits. Should you decide to continue using
the rig floor
drilling fluid, remember that it may soon
w Loss of standpipe pressure and increase in be depleted, forcing the switch to seawater
pump strokes. or another source of fluid.
Remember that all of the signs will happen 6. Set a watch observing the diverter system
rapidly, so the diverter procedure must be for signs of failure. Set a watch for signs of
known and undertaken quickly. broaching around the rig.
Wind direction is
an important
consideration
when gas is
vented at the
surface.
P ROCEDURES
5-11
Remember that the primary responsibility w Works with mud engineer to supervise
of each member is to keep the lines mixing crew and to ensure rig and mixing
of communication open. The individual pumps are functioning and aligned properly
responsibilities shown below are representative
of what must be done, and the person who ROUGHNECKS (DEPENDENT ON THEIR DESIGNATION)
typically performs the tasks during well control w Report to assigned well control station
events. The following list provides an example
(rig floor, pumproom, choke console, etc.)
only and does not in any way recommend or
represent policy. w Follow instructions of driller
DRILLER ELECTRICIAN/MECHANIC
w Primary responsibility is kick detection w Assists mechanic/motorman if required
and verification w Stands by for orders
w Shut in the well
w Notify supervisor
MUD ENGINEER
w Organize crew for kill operation w Goes to pits
w Remains at drilling console to run rig and w Supervises weighting operations
rig pump during kill operation w Maintains constant properties and
fluid density
TOOLPUSHER/RIG MANAGER
w Responsible for rig and personnel
ROUSTABOUTS
w Verifies proper on and off tour crew w Go to mud or pump room and follow
deployment, notifies barge engineer or instructions of supervisor
vessel captain of well control operations
w May be responsible for operating the choke
MOTORMAN
or to designate choke operator w Shuts off all non-essential equipment
w Coordinates kill operation with company w Ensures rig power throughout operation
representative w Goes to assigned station for well control
operations
COMPANY REPRESENTATIVE w Stands by for orders and to shut down rig
w Organizes kill operation
Each crew w Has overall responsibility unless rig has CEMENTER
member must offshore installation manager (OIM) w Reports to cement unit
know his station w Briefs crew, oversees operations and makes w Lines up to pump cement
and duties for sure crew knows their responsibilities
well control w Stands by for orders
w Notifies and keeps communications open
activities and with office
keep the lines of
SUBSEA ENGINEER (FLOATING OPERATIONS)
w May be responsible for operating the choke
communication w Reports to rig floor to inspect subsea panel
or designating a choke operator
open. w Checks for possible problems
BALLAST/BARGE ENGINEER w Stands by for orders from rig manager
w Notifies support vessels of operations
SERVICE PERSONNEL
w Stands by in control room for instructions
w Monitor fluid transfers w Go to assigned stations for well control
operations
DERRICKHAND/ASSISTANT DRILLER w Stand by for orders
w Goes to pit area, aligns gas separator,
degasser and pits
P ROCEDURES
5-13
Carefully planned close-in procedures are an essential component of well control operations.
C HAPTER 5
5-14
changeover, personnel in supervisory roles are 3. If the pumps are powered by air, isolate
usually required to document or report on the rig air system from the pumps. A separate
day's activity. closing unit air storage tank or a bank of
Crew change is an especially important time nitrogen bottles should be used to power
for good changeover notes. Many companies the pumps during this test. If a dual power
have a staggered crew change policy to ensure source system is used, each power supply
If the that someone is on hand and familiar with the should be tested separately.
accumulator prior week's events at all times.
system is not 4. Simultaneously turn the control valve
functioning for the annular preventer to the closing
correctly, BOP position and turn the control for the
closure may not ACCUMULATOR AND BOP TEST hydraulically controlled (HCR) valve to
be possible. the open position.
The accumulator system is the key to
5. Record the time in seconds for the pumps
success in the control of a kick. Unless the
system is functioning correctly, the BOP closure to close the annular preventer, to open
sequence and operation of other well control the hydraulically controlled (HCR) valve
equipment may not be possible. Therefore a and record the pressure that is remaining.
thorough and successful test is essential. The API recommends that this time should not
following procedures (excerpts from API RP exceed two minutes.
53) are a general guideline only and should 6. Close the hydraulically controlled (HCR)
not be confused with any government, state valve and open the annular preventer. Open
or company policy. For specific test procedures
the accumulator system to the closing unit,
always refer to the manufacturer's procedures
and to appropriate regulations. charge the accumulator system to its proper
On surface preventers, the closing system operating pressure, and record the time
should be capable of closing each ram preventer required to do this.
within 30 seconds and should not exceed 30
seconds for annular preventers smaller than
20 inches (508 mm) or 45 seconds Testing the casing string
for ones larger than 20 inches (508
mm). For subsea preventers each
ram should close within 45 seconds
and annular preventers within 60
seconds.
REQUIREMENTS
Cement Unit Mud Pumps
BOP stack.
2. Close power supply to accumulator pumps. Annular
All wellhead
equipment
tests should be
documented.
(or per manufacturer procedures) and for accumulations of cuttings that might
apply pressure under rams of 200 to 300 prevent full movement of the piston.
psi (13.79 to 20.68 bar) with blowout w Packer element for wear, cracking, excessive
preventer test tool installed (if testing hardness, correct elastomer composition.
preventer containing pipe rams). Hold w Bolting – both studs and nuts for proper
for required time. Check for leaks. If type, size and condition.
ram packer leaks, check for worn packers
and replace if necessary. If preventer w Where possible, inspect ring joint gaskets
is equipped with an automatic locking for proper type, size and condition.
device, check it for proper adjustment HYDRAULIC TEST Always perform
according to specifications. Continue test
1. Connect closing line to preventer. low pressure
until successful result is obtained. tests prior to
2. Set test tool on drillpipe/tubing below
h. High pressure test: check for ram packer high pressure
preventer.
leaks by increasing pressure slowly to tests.
the rated working pressure of preventer. 3. Test seals between closing chamber and
Hold for required time while checking wellbore and between closing chamber
for leaks. If packer leaks, check worn and opening chamber by applying the
packers and replace as necessary. If recommended closing pressure. If other
preventer is equipped with automatic chambers are located between wellbore
locking devices, check them for proper and operating chamber, these seals should
adjustment in accordance with also be tested.
specifications. Continue testing until a 4. If pressure holds, proceed to step 13.
successful result is obtained. a. If pressure does not hold and no fluid
i. Test connecting rod for adequate strength is running out of the opening chamber,
by applying pressure as recommended by the seal between the closing chamber
the manufacturer with rams closed and and the wellbore or other operating
BOP rated working pressure under rams. chamber is leaking. Proceed to step 11.
b. If fluid is coming out of the opening
j. Release opening pressure and release
chamber, indicating the seal between the
pressure under rams.
closing chamber and opening chamber
k. Repeat steps a - j for each set of rams. is leaking, proceed to step 5.
l. Test blind rams in the same manner as 5. Release closing pressure.
pipe rams with test plug installed and 6. Install plug in opening chamber, or if
test joint removed. opening line is equipped with a valve,
install opening line and close valve.
7. Test seals between the closing chamber,
ANNULARS AND DIVERTERS operating chambers, and wellbore by
applying recommended closing pressure.
Inspections and tests should include visual Observe to see that pressure holds.
inspections and hydraulic tests. 8. Release closing pressure.
9. Remove plug in opening chamber and
THOROUGH VISUAL INSPECTION install opening line or open valve in
w Face of preventer head/cap for off-center opening line.
wear, pitting and damage, especially in ring 10. Apply 1,500 psi (103.42 bar) closing
grooves and bolt/stud holes. pressure.
w Body for wear and damage. 11. Apply 1,500 psi (103.42 bar) wellbore
w Vertical bore for wear and damage from pressure. (Use lower pressure for lower
pipe and tools. rated equipment.)
w Slotted body sleeve for pitting and damage. 12. Bleed closing pressure to 1,000 psi
Look through slots in base of inner liner (68.95 bar).
C HAPTER 5
5-18
13. To test the seal between the wellbore and bottom annular preventer if two annular
closing chamber, close the valve on the preventers are being used when a stack is
closing line and disconnect the closing nippled up on an annular preventer (for
line from the valve on closing unit side of snubbing, etc.). It can be tested to rated
valve. Install pressure gauge on closing working pressure by running a test joint
unit side of valve and open valve. If this and plug, closing an upper preventer,
seal is leaking, the closing line will have removing the opening line, and pressuring
pressure greater than 1,000 psi (68.95 bar). the preventer stack up to 1,500 psi
Testing should Caution: if the closing line does not have (103.42 bar) maximum or by closing an
be methodical, a valve installed, the closing line should upper preventer and annular preventer,
performed to not be disconnected with pressure trapped removing the opening line, and pressuring
specifications and in the closing chamber. up between preventers.
documented. 14. Release wellbore pressure. Once systems have passed all the required
15. Release closing pressure. tests, make sure to check manifold and annular
16. To test the seals between the opening pressure regulators. Most systems require 1,500
chamber and the closing chamber and psi (103.42 bar) manifold pressure. The initial
between the opening chamber and the closing pressure regulated to the annular
piston, apply the recommended opening depends on several factors. If either pressure
pressure. If the pressure holds, proceed is incorrect the regulators must be adjusted,
to step 21. either remotely or manually.
a. If pressure does not hold and no fluid
is running out of the closing chamber
opening, the seal between the opening
chamber and piston is leaking. Verify
CHRISTMAS TREE TESTING
this visually. Proceed to step 21.
b. If fluid is coming out of the closing Trees are classified according to various
chamber opening, indicating the seal factors, such as rated working pressure,
between the opening and the closing corrosion, H2S gas and their proximity to
chamber is leaking, proceed to step 17. other pressure equipment. Depending upon the
17. Release opening pressure. classification, hydrostatic or gas and hydrostatic
tests may be required prior to putting the well
18. Install closing line and block flow (close
valve in closing line, if available). on line. If mixed pressure rated components
are used, the tree should be tested to the
19. Apply 1,500 psi (103.42 bar) opening
lower rated pressure. Testing usually consists
pressure. If the pressures do not hold,
of several pressure holding periods with test
the seal between the opening chamber
time requirements varying according to the
and the preventer head is leaking. Verify
tree classification, as well as regulations and
this visually.
policies. The tree body, inlets and outlets – as
20. Release opening pressure and replace
well as all seals – must be tested. Both sides
necessary seals. Refer to step 22.
of bi-directional valves should be tested, one
21. Release opening pressure, replace closing side at a time.
line, and replace necessary seals. For plug valves, when test pressure is on
22. If the closing line has a valve installed, each side of the plug, the plug should be
make certain that the valve is open at the moved at least two times. Unidirectional valves
end of the test. NOTE: This procedure should have pressure applied in the direction
tests all seals except the seal between indicated on the body, except for check valves
the wellbore and the opening chamber. which would be tested on the downstream side
This seal should be tested in the with the opposite end open to the atmosphere.
P ROCEDURES
5-19
Wellhead
equipment
should be tested
according to its
lowest rated
component.