DS6 Soft Start Controllers

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

DS6 soft start controllers

The power of fusion.

1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1967 1976 1977 1983 1984 1989 1999

There’s a certain energy at Eaton. It’s the power of uniting some of the
world’s most respected names to build a brand you can trust to meet
every power management need. The energy created supports our
commitment to powering business worldwide.
Eaton is dedicated to ensuring that reliable, efficient and safe power is
available when it’s needed most. With unparalleled knowledge of
electrical power management across industries, experts at Eaton deliver
customized, integrated solutions to solve our customers’ most critical
challenges. www.eaton.com.cn/electrical

All of the above are trademarks of Eaton Corporation or its affiliates. Eaton has
a license to use the Westinghouse brand name in Asia Pacific. ©2012 Eaton Corporation.
DS6 Soft Start Controllers
Contents

DS6 Soft Start Controllers


DS6 Soft Start Controllers
Features and Benefits .............................................................................................................................. 2
Standards and Certifications..................................................................................................................... 2
Instructional Leaflets ................................................................................................................................ 2
Product Selection ..................................................................................................................................... 3
Technical Data and Specifications............................................................................................................. 4
Dimensions .............................................................................................................................................. 8

DS6 Soft Start Controllers


Product Description Application Description Operation
Eaton’s DS6 line of reduced With its small size, it can Voltage Ramp Start Start Ramp
voltage solid-state soft start easily fit in place of existing Bypass
This start method provides a
controllers is very compact, soft starters, wye-delta 100%
voltage ramp to the motor,
multi-functional, easy to starters, or across-the-line resulting in a constant torque

Speed
install, and easy to contactors. This feature increase. This most
commission. Designed to allows easy upgrades to commonly used form of soft
control the acceleration and existing systems. The start mode allows you to set Start Run
deceleration of three-phase product is designed to be the initial voltage value and Time (Seconds)
motors, the device is wired in the three-phase line the duration of the ramp to
available for current ranges feeding the three motor input full voltage conditions.
from 41 to 196 amperes. leads as is done for normal
across-the-line starting. The Bypass contactor(s) close
starter uses silicon controlled after ramp time has elapsed.
rectifiers (SCRs) to ramp the Adjustable initial voltage
voltage to the motor, providing 30–92% of full voltage
smooth acceleration and Adjustable ramp time
deceleration of the load. After 1–30 seconds
the motor is started, the
internal run bypass contactor Soft Stop Stop Ramp
closes, resulting in the motor Allows for a controlled 100% 1
running directly across-the- stopping of load. Used when 2
Speed

line.Internal run bypass a stop-time that is greater


significantly reduces the heat
than the coast-to-stop time is
generated as compared to 3
desired. Often used with high
non-bypass starters. The soft Run Soft Stop
friction loads where a sudden
stop option allows for a ramp Time (Seconds)
stop may cause system or
stop time that may be longer
product damage. Setting the Coast to Stop (Speed)
than the coast-to-stop time.
soft stop time to a value of Soft Stop Ramp (Voltage)
An external over-load
0 turns off this feature. Soft Stop Time
protection is needed.
Soft stop time =
0–30 seconds
DS6 Soft Start Controllers
Standards and Certifications

Features and Benefits


Run bypass mode greatly Soft stop control suits Protective Features
reduces internal heating applications where an Heat sink over/under
There are two auxiliary
created by the power abrupt stop of the load temperature—High
relays—
dissipation across the is not acceptable. ambient temperatures,
SCRs. The bypass Soft acceleration and First relay is a TOR relay
which closes when the extended ramp times, and
contactor directly connects deceleration reduces high duty cycle conditions
the motor to the line and wear on belts, gears, TOR is achieved (internal
bypass relays close) may cause the DS6 to
improves system efficiency chains, clutches, shafts, exceed its thermal rating.
by reducing internal power and bearings The second relay is a When temperature goes
losses Minimizes the peak inrush RUN relay which closes under –5°C, unit will trip as
Less heat minimizes current’s stress on the when the RUN signal is well. The DS6 is equipped
enclosure size and cooling power system initiated and opens with sensors that monitor
requirements, and when RUN signal is the temperature of the
Manages peak starting
maximizes the life of all removed. It remains device. The soft starter will
torque to diminish
devices in the enclosure closed during stop ramp trip in over/under
mechanical system wear
time, if set to a value temperature conditions,
LED displays device status and damage
greater than 0. The RUN preventing device failure
and provides fault 24 Vdc control module relay will also open if a
indication enhances personnel and Bypass relay—The DS6
fault occurs
Variable ramp times and equipment safety can detect if the bypass
voltage control (torque Mains connection— relay fails to close after the
control) settings provide The mains connection ramp start or opens while
unlimited starting is monitored for an the motor is running. The
configurations, allowing open condition and/or DS6 will trip on a bypass
for maximum application undervoltage dropout fault if either of
flexibility Motor connection— these conditions occur. The
The motor connection device does not start when
is monitored for an bypass relay is closed and
open condition start signal is applied
SCR faults—SCR 24 Vdc low voltage—
performance is monitored If the control voltage falls
during the ramp cycle for below 20 Vdc at any time
proper operation during operation, the unit
will fault

Standards and Certifications


IEC 60947-4-2
EN 60947-4-2
UL listed (E251034)
CSA certified
CE marked
C-Tick
CCC

Instructional Leaflets
Instruction Leaflet IL03901001E

2 
DS6 Soft Start Controllers
Product Selection

DS6 Soft Start kW Ratings

Please refer to Application Note AP03900001E for additional information


on proper size selection.

DS6 Soft Start Controllers—kW Ratings According to IEC 60947-4-2—


10 Second Ramp, 1 Start per Hour, 300% Current Limit at 40°C
Motor Power (kW) Maximum Maximum
Rated Allowable Allowable Recommended
Current (A) 230V 400V Breaker Size Fuse Size Overload Catalog Number
41 11 22 NZMS1-A160 150A Class RK5 ZB65-57 DS6-340-22K-MX
55 15 30 NZMS2-A200 200A Class RK5 ZB65-57 DS6-340-30K-MX
68 15 37 NZMS2-A250 200A Class RK5 ZB150-70 DS6-340-37K-MX
81 22 45 NZMH3-A320 300A Class RK5 ZB150-100 DS6-340-45K-MX
99 30 55 NZMH3-A320 350A Class RK5 ZB150-100 DS6-340-55K-MX
134 30 75 NZMH3-A400 500A Class RK5 ZB150-150/KK DS6-340-75K-MX
160 45 90 NZMH3-A500 500A Class RK5 Z5-160/FF250 DS6-340-90K-MX
196 55 110 NZMH3-A500 500A Class RK5 Z5-220/FF250 DS6-340-110K-MX

10 Second Ramp, 1 Start per Hour, 400% Current Limit at 40°C


Motor Power (kW) Maximum Maximum
Rated Allowable Allowable Recommended
Current (A) 230V 400V Breaker Size Fuse Size Overload Catalog Number
28.8 7.5 11 NZMS1-A160 150A Class RK5 ZB65-40 DS6-340-22K-MX
37.5 11 18.5 NZMS2-A200 200A Class RK5 ZB65-40 DS6-340-30K-MX
46 11 22 NZMS2-A250 200A Class RK5 ZB65-57 DS6-340-37K-MX
56 15 30 NZMH3-A320 300A Class RK5 ZB65-65 DS6-340-45K-MX
68 18.5 37 NZMH3-A400 350A Class RK5 ZB150-100 DS6-340-55K-MX
90 22 45 NZMH3-A400 500A Class RK5 ZB150-100 DS6-340-75K-MX
106 30 55 NZMH3-A500 500A Class RK5 Z5-160/FF250 DS6-340-90K-MX
134 37 75 NZMH3-A500 500A Class RK5 Z5-160/FF250 DS6-340-110K-MX

Power Supply Selection


Description Catalog Number
85–264V input and 24V output ELC-PS01

3
DS6 Soft Start Controllers
Technical Data and Specifications

Technical Data and Specifications


DS6 Soft Start Controllers
Description Unit DS6-340-22K-MX DS6-340-30K-MX DS6-340-37K-MX DS6-340-45K-MX
General
Standards IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2
Certifications UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC
Ambient temperature °C 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate
(operation) linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per
Celsius to 60°C Celsius to 60°C Celsius to 60°C Celsius to 60°C
Ambient temperature °C –25 to +55°C –25 to +55°C –25 to +55°C –25 to +55°C
(storage)
Altitude 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate
linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per
100m to a maximum of 2000m 100m to a maximum of 2000m 100m to a maximum of 2000m 100m to a maximum of 2000m
Installation Vertical Vertical Vertical Vertical
Protection degree IP 20 IP 20 IP 20 IP 20
Protection against contact Back of hand and finger-proof Back of hand and finger-proof Back of hand and finger-proof Back of hand and finger-proof
(from front face) (from front face) (from front face) (from front face)
Overvoltage category/ II/2 II/2 II/2 II/2
pollution degree
Shock resistance 8g/11 ms 8g/11 ms 8g/11 ms 8g/11 ms
Vibration resistance 2M2 2M2 2M2 2M2
according to EN 60721-3-2
Dimensions in inches (mm) 3.66 x 6.89 x 5.47 3.66 x 6.89 x 5.47 3.66 x 6.89 x 5.47 3.66 x 6.89 x 5.47
(W x H x D) (93.0 x 175.0 x 138.9) (93.0 x 175.0 x 138.9) (93.0 x 175.0 x 138.9) (93.0 x 175.0 x 138.9)
Weight in lbs (kg) 4.00 (1.8) 4.00 (1.8) 4.00 (1.8) 4.00 (1.8)
Main Circuit
Rated operation voltage V 200–460 Vac 200–460 Vac 200–460 Vac 200–460 Vac
Mains frequency Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse Uimp 1.2/ 4 kV 4 kV 4 kV 4 kV
withstand voltage 50 μs
Rated operation current Ie 41 55 68 81
Motor Power Ratings
230V kW 11 15 15 22
400V kW 22 30 37 45
Overload cycle according 40A: AC53a; 3–5; 75–10 52A: AC53a; 3–5; 75–10 65A: AC53a; 3–5; 75–10 77A: AC53a; 3–5; 75–10
to EN 60947-4-2

4 
DS6 Soft Start Controllers
Technical Data and Specifications

DS6 Soft Start Controllers, continued


Description Unit DS6-340-22K-MX DS6-340-30K-MX DS6-340-37K-MX DS6-340-45K-MX
Wire Specifications
Power terminals (box terminals)
1
Single conductor AWG 12–2/0 12–2/0 12–2/0 12–2/0
Terminal torque lb-in 53–80 53–80 53–80 53–80
1
Control-signals

1
Single conductor AWG 16 min. 16 min. 16 min. 16 min.
Terminal torque lb-in 3.5 3.5 3.5 3.5

1
Powerpart
Rated impulse Uimp 1.2/ 4 kV 4 kV 4 kV 4 kV
1
withstand voltage
Control Commands
50 μs

1
Supply voltage control board Us
Nominal voltage Vdc +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%
1
Nominal current ramp, TOR mA 65 65 65 65
Current peak 600 mA/50 ms 600 mA/50 ms 600 mA/50 ms 600 mA/50 ms
1(closing shorting
contactors)

1
Voltage to the control terminals (rated control voltage)
DC driven +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%

1
Input current at 24 Vdc mA 14 14 14 14
Relay Outputs
1
Number of relays 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready)

1
Maximum voltage V 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc
Maximum current A 3 amps, resistive 3 amps, resistive 3 amps, resistive 3 amps, resistive

1
Soft Start Functions
Ramp times
1
Start ramp s 1–30 1–30 1–30 1–30
Stop ramp s 0–30 0–30 0–30 0–30
1
Initial voltage % line voltage 30–92% 30–92% 30–92% 30–92%

1
1

5
DS6 Soft Start Controllers
Technical Data and Specifications

DS6 Soft Start Controllers, continued


Description Unit DS6-340-55K-MX DS6-340-75K-MX DS6-340-90K-MX DS6-340-110K- MX
General
Standards IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2
Certifications/marking UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC UL/CE/C-Tick/CSA/CCC
Ambient temperature °C 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate 0 to 40°C, above 40°C de-rate
(operation) linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per
Celsius to 60°C Celsius to 60°C Celsius to 60°C Celsius to 60°C
Ambient temperature °C –25 to +55°C –25 to +55°C –25 to +55°C –25 to +55°C
(storage)
Altitude 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate 0–1000m, above 1000m de-rate
linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per linearly by 1% of rated current per
100m to a maximum of 2000m 100m to a maximum of 2000m 100m to a maximum of 2000m 100m to a maximum of 2000m
Installation Vertical Vertical Vertical Vertical
Protection degree IP 20 IP 20 IP 20 IP 20
Protection against contact Back of hand and finger-proof Back of hand and finger-proof Back of hand and finger-proof Back of hand and finger-proof
(from front face) (from front face) (from front face) (from front face)
Overvoltage category/ II/2 II/2 II/2 II/2
pollution degree
Shock resistance 8g/11 ms 8g/11 ms 8g/11 ms 8g/11 ms
Vibration resistance 2M2 2M2 2M2 2M2
according to EN 60721-3-2
Dimensions in inches (mm) 3.66 x 6.89 x 5.47 4.25 x 8.46 x 7.01 4.25 x 8.46 x 7.01 4.25 x 8.46 x 7.01
(W x H x D) (93.0 x 175.0 x 138.9) (108.0 x 214.9 x 178.1) (108.0 x 214.9 x 178.1) (108.0 x 214.9 x 178.1)
Weight in lbs (kg) 4.00 (1.8) 8.16 (3.7) 8.16 (3.7) 8.16 (3.7)
Main Circuit
Rated operation voltage V 200–460 Vac 200–460 Vac 200–460 Vac 200–460 Vac
Mains frequency Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse Uimp 1.2/ 4 kV 4 kV 4 kV 4 kV
withstand voltage 50 μs
Rated operation current Ie 99 134 161 192
Motor Power Ratings
230V kW 30 30 45 55
400V kW 55 75 90 110
1
Overload cycle according 96A: AC53a; 3–5; 75–10 124A: AC53a; 3–5; 75–10 156A: AC53a; 3–5; 75–10 180A: AC53a; 3–5; 75–10
to EN 60947-4-2
1

1
1
1
1
1
1
1
1
1

6 
DS6 Soft Start Controllers
Technical Data and Specifications

DS6 Soft Start Controllers, continued


Description Unit DS6-340-55K-MX DS6-340-75K-MX DS6-340-90K-MX DS6-340-110K-MX
Wire Specifications
Power terminals (box terminals)
Single conductor AWG 12–2/0 12 AWG–350 kcmil 12 AWG–350 kcmil 12 AWG–350 kcmil
Terminal torque lb-in 53–80 44–123 44–123 44–123
Control-signals
Single conductor AWG 16 min. 16 min. 16 min. 16 min.
Terminal torque lb-in 3.5 3.5 3.5 3.5
Powerpart
Rated impulse Uimp 1.2/ 4 kV 4 kV 4 kV 4 kV
withstand voltage 50 μs
Control Commands
Supply voltage control board Us
Nominal voltage Vdc +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%
Nominal current ramp, TOR mA 65 65 65 65
Current peak 600 mA/50 ms 600 mA/50 ms 600 mA/50 ms 600 mA/50 ms
(closing shorting
contactors)
Voltage to the control terminals (rated control voltage)
DC driven +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%
Input current at 24 Vdc mA 14 14 14 14
Relay Outputs
Number of relays 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready)
Maximum voltage V 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc
Maximum current A 3 amps, resistive 3 amps, resistive 3 amps, resistive 3 amps, resistive
Soft Start Functions
Ramp times
Start ramp s 1–30 1–30 1–30 1–30
Stop ramp s 0–30 0–30 0–30 0–30
Initial voltage % line voltage 30–92% 30–92% 30–92% 30–92%

7
DS6 Soft Start Controllers
Dimensions

Dimensions
Approximate Dimensions in Inches (mm)

22-55kw Models
1.18
(30.0) 1.18
0.88 (30.0) PE
(22.5)

6.34
(161.0)

6.89
(175.0)
5.08
(129.0)

0.88 1.38
PE (22.5)
3.66 (35.0)
5.47
(93.0) (139.0)

75-110kw Models
1.38
(35.0) 1.38
0.59 (35.0)
(15.0) PE

7.87
(200.0)

6.22 8.47
(158.0) (215.0)

0.59 2.07
PE (15.0) (52.5)
4.25 7.01
(108.0) (178.0)

8 
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to
solve our customers’ most critical challenges.

Our focus is on delivering the right solution for the application.


But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eaton.com.cn/electrical.

Eaton Corporation
Asia Pacific Headquarter
No.3, Lane 280, Linhong Road,
Changning District,
Shanghai 200335
Tel: 86-21-52000099
Fax: 86-21-52000200
Eaton is a registered trademark
© 2011 Eaton Corporation of Eaton Corporation.
All Rights Reserved
Printed in China All trademarks are property of their
DS6-EN(02-2012) respective owners.

You might also like