Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id Trans. No. G Name

Max Phase Fault Current (kA) 33.99 Earth Fault Current (kA) 23.93 Design Current Ib (A) 1536.7

Device Terasaki ACB standard AR325S -21BL-PG LSIG Rating In (A) 2500 Breaking Capacity Icu (kA) 85
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I) Earth Fault(G)


In=0.80 Isd=10.0 I=NON Ig=1.00
Ir=0.90 Isd*t=FLAT I*t=FLAT
tr=30.00 tsd=0.80 tg=0.1
Temp=Cold

Id PFC-LVP-01 Name

Max Phase Fault Current (kA) 29.94 Earth Fault Current (kA) 13.48 Design Current Ib (A) 313.1

Device Terasaki TemBreak2 MCCB S630-CE LSI Rating In (A) 630 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=6

Id KEF-W1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id DEF-E1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.88 Design Current Ib (A) 11.3

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id DEF-W1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.52 Design Current Ib (A) 16.4

Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id DEF-E1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.88 Design Current Ib (A) 11.3

Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 1 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=10.0

Id DEF-W1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.52 Design Current Ib (A) 16.4

Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-4 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.17 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-3 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.25 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-2 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.61 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.21 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id SPF-4 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.20 Design Current Ib (A) 49.1

Device Generic MCCB 36kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 2 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=7.1

Id SPF-3 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.63 Design Current Ib (A) 49.1

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=7.1

Id KEF-W1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id SPF-2 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 2.11 Design Current Ib (A) 49.1

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=7.1

Id SPF-1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.41 Design Current Ib (A) 49.1

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=7.3

Id EF-W1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 5.5

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id EF-W1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 5.5

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 3 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=10.0

Id EF-E1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id EF-E1 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id CP-03 Name

Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 1.98 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id LIFT no. 5 _ISOLATOR Name

Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 26.6

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id LIFT no. 6 _ISOLATOR Name

Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 22.6

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id LIFT no. 7 _ISOLATOR Name

Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 29.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 4 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.8

Id LIFT no. 8 _ISOLATOR Name

Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 25.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id AHU-T (MSCP-24) Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 2.69 Design Current Ib (A) 33.9

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id HWCP-MF-02-A Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 0.47 Design Current Ib (A) 1

Device Terasaki TemBreak2 MCCB S160-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id HWCP-MF-02-B Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 0.47 Design Current Ib (A) 1

Device Terasaki TemBreak2 MCCB S160-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id LINK CORRIDOR Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 3.59 Design Current Ib (A) 6.2

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id LP-MF -01 Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.66 Design Current Ib (A) 3.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 5 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.63

Id LP-MF -02 Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.66 Design Current Ib (A) 2.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id LV-ROOM -MF Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.24 Design Current Ib (A) 2.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 25 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id SMP _ PODIUM CIS Name

Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 3.19 Design Current Ib (A) 16.7

Device Terasaki TemBreak2 MCCB S250-NJ TMD Rating In (A) 200 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 2ND FLOOR ( STANDBY)_EF-2E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 2ND FLOOR (STANDBY) AHU-2E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 3RD FLOOR ( STANDBY)_EF-2E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 6 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 3RD FLOOR_(STANDBY)_AHU-3E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 4TH FLOOR ( STANDBY)_AHU-4E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 4TH FLOOR ( STANDBY)_EF-4E-L1,L2,L3 Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=6

Id 5TH FLOOR ( STANDBY)_AHU-5E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 5TH FLOOR ( STANDBY)_EF-5E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 6TH FLOOR ( STANDBY)_AHU-6E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 32

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 7 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 6TH FLOOR ( STANDBY)_EF-6E Name

Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 20

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.80 Ii=8

Id 2ND FLOOR AHU-2W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 2ND FLOOR EF-2W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 3RD FLOOR _EF-2W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 3RD FLOOR_AHU-3W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 4TH FLOOR _AHU-4W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 32

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 8 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Instantaneous(I)
Ir=0.80 Ii=8

Id 4TH FLOOR EF-4W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 20

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 5TH FLOOR AHU-5W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.80 Ii=8

Id 5TH FLOOR EF-5W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 6TH FLOOR AHU-6W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 32

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id 6TH FLOOR EF-6W Name

Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 18

Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=8

Id LPF-4A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.17 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 9 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=10.0

Id LPF-3A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.27 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-2A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.56 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id LPF-1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.22 Design Current Ib (A) 1.6

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id SPF-4A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.24 Design Current Ib (A) 48.8

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=6.7

Id SPF-3A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.68 Design Current Ib (A) 48.8

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=7.4

Id SPF-2A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 2.01 Design Current Ib (A) 48.8

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 10 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=7.4

Id SPF-1A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.46 Design Current Ib (A) 48.8

Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=7.5

Id EF-E2A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 5.5

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id DEF-E2 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 10.4

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id DEF-E2A Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 10.4

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id EF-E2 Name

Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 5.5

Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=10.0

Id SMDB-01-2F-W Name

Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 120.2

Device Terasaki TemBreak2 MCCB H400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 11 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=4

Id SMDB-01-3F-W Name

Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.5

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id SMDB-01-4F-W Name

Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.1

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id SMDB-01-5F-W Name

Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.3

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id SMDB-01-6F-W Name

Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.5

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id DB-01-2F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 28.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 12 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-01-2F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 28.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-02-2F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-02-2F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id IDB-01-2F Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id LP-01-2F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id LP-02-2F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 10.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 13 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.8

Id NEW MECH DB-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id DB-01-3F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-01-3F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-02-3F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id DB-02-3F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id IDB-01-3F Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 14 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.63

Id LP-01-3F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id LP-02-3F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id NEW MECH DB-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id DB-01-4F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-01-4F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-02-4F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 15 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.8

Id DB-02-4F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id IDB-01-4F Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id LP-01-4F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id LP-02-4F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 10.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id NEW MECH DB-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id DB-01-5F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 16 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.8

Id DB-01-5F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-02-5F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.6

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-02-5F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id IDB-01-5F Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id LP-01-5F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id LP-02-5F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 17 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=1.0

Id NEW MECH DB-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id DB-01-6F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-01-6F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-02-6F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id DB-02-6F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id IDB-01-6F Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 18 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=0.63

Id LP-01-6F-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id LP-02-6F-C Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id NEW MECH DB-W Name

Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id SMP-NICU Name

Max Phase Fault Current (kA) 24.95 Earth Fault Current (kA) 3.78 Design Current Ib (A) 99

Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=1

Id USMDP-2F Name

Max Phase Fault Current (kA) 21.96 Earth Fault Current (kA) 2.69 Design Current Ib (A) 42.9

Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 125 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=5

Id USMDP-3F Name

Max Phase Fault Current (kA) 21.96 Earth Fault Current (kA) 2.61 Design Current Ib (A) 54.7

Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 125 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 19 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=5

Id IDB-01-2F Name

Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 0.84 Design Current Ib (A) 8.7

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id UDB-01-2F Name

Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 0.95 Design Current Ib (A) 27.3

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.80 Ii=8

Id UDB-02-2F-C Name

Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 2.19 Design Current Ib (A) 12.8

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=8

Id UDB-03-2F-E Name

Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 1.10 Design Current Ib (A) 15.8

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=8

Id 1 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 10 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 20 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 11 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 12 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 13 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 14 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 15 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 3.7

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 16 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 17 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 18 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 21 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings: Fixed device - no settings

Id 19 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 2 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 20 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 21 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 3 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 4 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 5 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 22 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 6 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 7 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 8 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 9 Name

Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id Cbl_FC-12-IDB-01-3F Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.83 Design Current Ib (A) 8.7

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id Cbl_FC-13-IDB-01-4F Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.83 Design Current Ib (A) 8.7

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id UDB-01-2F Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.94 Design Current Ib (A) 16.7

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=6

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 23 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id UDB-02-3F-C Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 2.14 Design Current Ib (A) 12.8

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id UDB-02-4F-C Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 2.14 Design Current Ib (A) 16.6

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id UDB-03-3F-E Name

Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 1.09 Design Current Ib (A) 15.8

Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=0.63 Ii=6

Id OUTPATIENT DEPT. & MF Name

Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 2.08 Design Current Ib (A) 71.3

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id SITE LIGHTING SOUTH Name

Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 1.49 Design Current Ib (A) 10.6

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id ULTRASONIC Name

Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 1.74 Design Current Ib (A) 30.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 24 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id LMSB-1(NON ESS) Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.37 Design Current Ib (A) 250

Device Terasaki TemBreak2 MCCB S630-CE LSI+LCD meter Rating In (A) 630 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=0.50 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id SMDB -6 Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 6.51 Design Current Ib (A) 36.6

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=13.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.30
Temp=Cold

Id SMDB -SH Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 7.57 Design Current Ib (A) 54.4

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=13.0
IR=1.00 Isd*t=FLAT
tr=30.00 tsd=0.30
Temp=Cold

Id SMP NICU & LABOR WARD Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 1.97 Design Current Ib (A) 7.3

Device Terasaki TemBreak2 MCCB S125-GJ TMD Rating In (A) 125 Breaking Capacity Icu (kA) 65
Add-On AFDD N/A

Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id SMP OPD & LABOR WARD Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.62 Design Current Ib (A) 28

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 25 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id SMP OPD EXT. MEZZ. Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 1.60 Design Current Ib (A) 89.3

Device Terasaki TemBreak2 MCCB S250-PE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S)


IR=1.00 Char=1

Id LABOUR & DELIVERY Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.36 Design Current Ib (A) 39

Device Terasaki TemBreak2 MCCB S250-PE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S)


IR=0.40 Char=1

Id MCC-RF-01 (ROOF /PENTHOUSE) Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.96 Design Current Ib (A) 86.2

Device Terasaki TemBreak2 MCCB S400-NE LSIG+LCD meter Rating In (A) 400 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I) Earth Fault(G)


In=1.00 Isd=10.0 I=13.0 Ig=0.20
IR=1.00 Isd*t=FLAT I*t=FLAT
tr=30.00 tsd=0.20 tg=0.1
Temp=Cold

Id MCC-RF-02 (ROOF /PENTHOUSE) Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.96 Design Current Ib (A) 70

Device Terasaki TemBreak2 MCCB S400-NE LSIG+LCD meter Rating In (A) 400 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I) Earth Fault(G)


In=1.00 Isd=10.0 I=12.0 Ig=0.20
IR=1.00 Isd*t=FLAT I*t=FLAT
tr=20.00 tsd=0.10 tg=0.1
Temp=Cold

Id SMB-MOSQUE Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 6.09 Design Current Ib (A) 24.4

Device Terasaki TemBreak2 MCCB S125-GJ TMD Rating In (A) 125 Breaking Capacity Icu (kA) 65
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 26 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L) Instantaneous(I)
Ir=1.00 Ii=8

Id SMDB-2 Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.44 Design Current Ib (A) 90

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=13.0
IR=1.00 Isd*t=FLAT
tr=30.00 tsd=0.30
Temp=Cold

Id SMDB-MG Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.10 Design Current Ib (A) 108.7

Device Terasaki TemBreak2 MCCB S400-NE LSI+LCD meter Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=12.0
IR=1.00 Isd*t=FLAT
tr=20.00 tsd=0.10
Temp=Cold

Id UPS-MAIN SUPPLY Name

Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 12.59 Design Current Ib (A) 204.7

Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Overload(L) Selective Short-circuit(S) Instantaneous(I)


In=1.00 Isd=10.0 I=13.0
IR=1.00 Isd*t=FLAT
tr=30.00 tsd=0.30
Temp=Cold

Id 1 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 10 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 27 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 11 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 12 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 13 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 1.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 14 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 16 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 17 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 7.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 18 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.62 Design Current Ib (A) 7.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 19 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 28 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings: Fixed device - no settings

Id 2 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 20 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 21 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 22 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 23 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 24 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 25 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 29 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 26 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 0.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 3 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 4 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 5 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 6 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 7 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 8 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 9 Name

Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 30 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings: Fixed device - no settings

Id 1 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 10 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 11 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 12 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 13 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 1.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 14 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 16 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 31 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 17 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 7.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 18 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 2.13 Design Current Ib (A) 7.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 19 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 2 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 20 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 21 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 22 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 23 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.6

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 32 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings: Fixed device - no settings

Id 24 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 25 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 26 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 0.8

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 3 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 4 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 5 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 6 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 33 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A

Id 7 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 8 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id 9 Name

Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1

Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A

Settings: Fixed device - no settings

Id CP-02 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 1.61 Design Current Ib (A) 2.1

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 25 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.63

Id DB-MG-M2 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 1.7

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id MAC-01 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.23 Design Current Ib (A) 41.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=0.8

Id MAC-02 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 34 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Overload(L)
Ir=1.0

Id MAC-03 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id MAC04 Name

Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5

Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A

Settings:

Overload(L)
Ir=1.0

Id EAF-M01 Name

Max Phase Fault Current (kA) 7.65 Earth Fault Current (kA) 0.86 Design Current Ib (A) 1.3

Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=2.0

Id EAF-M01A Name

Max Phase Fault Current (kA) 7.65 Earth Fault Current (kA) 0.86 Design Current Ib (A) 1.3

Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=2.0

Id AHU-1A Name

Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.99 Design Current Ib (A) 10

Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=2.0

Id EF-G-02 Name

Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.74 Design Current Ib (A) 1.8

Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 35 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: Revised By:
SWAMINATHAN GNANESWARAN VAIBHAV KANTHE Revision: REV-A
Settings:

Instantaneous(I)
I=2.0

Id SPF-5 Name

Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.99 Design Current Ib (A) 10

Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A

Settings:

Instantaneous(I)
I=2.1

Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 36 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.