Protective Device Settings
Protective Device Settings
Max Phase Fault Current (kA) 33.99 Earth Fault Current (kA) 23.93 Design Current Ib (A) 1536.7
Device Terasaki ACB standard AR325S -21BL-PG LSIG Rating In (A) 2500 Breaking Capacity Icu (kA) 85
Add-On AFDD N/A
Settings:
Id PFC-LVP-01 Name
Max Phase Fault Current (kA) 29.94 Earth Fault Current (kA) 13.48 Design Current Ib (A) 313.1
Device Terasaki TemBreak2 MCCB S630-CE LSI Rating In (A) 630 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id KEF-W1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id DEF-E1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.88 Design Current Ib (A) 11.3
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id DEF-W1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.52 Design Current Ib (A) 16.4
Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id DEF-E1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.88 Design Current Ib (A) 11.3
Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 1 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=10.0
Id DEF-W1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.52 Design Current Ib (A) 16.4
Device Generic MCCB 25kA Electronic I Rating In (A) 32 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-4 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.17 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-3 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.25 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-2 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.61 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.21 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id SPF-4 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.20 Design Current Ib (A) 49.1
Device Generic MCCB 36kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 2 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=7.1
Id SPF-3 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.63 Design Current Ib (A) 49.1
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=7.1
Id KEF-W1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id SPF-2 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 2.11 Design Current Ib (A) 49.1
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=7.1
Id SPF-1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.41 Design Current Ib (A) 49.1
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=7.3
Id EF-W1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 5.5
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id EF-W1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 5.5
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 3 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=10.0
Id EF-E1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id EF-E1 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.34 Design Current Ib (A) 4.7
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id CP-03 Name
Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 1.98 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 26.6
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 22.6
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 29.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 4 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.26 Earth Fault Current (kA) 2.15 Design Current Ib (A) 25.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 2.69 Design Current Ib (A) 33.9
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id HWCP-MF-02-A Name
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 0.47 Design Current Ib (A) 1
Device Terasaki TemBreak2 MCCB S160-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id HWCP-MF-02-B Name
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 0.47 Design Current Ib (A) 1
Device Terasaki TemBreak2 MCCB S160-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 3.59 Design Current Ib (A) 6.2
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.66 Design Current Ib (A) 3.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 5 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.63
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.66 Design Current Ib (A) 2.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 1.24 Design Current Ib (A) 2.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 25 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Max Phase Fault Current (kA) 22.61 Earth Fault Current (kA) 3.19 Design Current Ib (A) 16.7
Device Terasaki TemBreak2 MCCB S250-NJ TMD Rating In (A) 200 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 6 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=6
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 20 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 4.68 Design Current Ib (A) 32
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 7 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 18.51 Earth Fault Current (kA) 2.35 Design Current Ib (A) 20
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.80 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 32
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 8 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L) Instantaneous(I)
Ir=0.80 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 20
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 26
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.80 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 12
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 32 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 4.84 Design Current Ib (A) 32
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 19.78 Earth Fault Current (kA) 2.39 Design Current Ib (A) 18
Device Terasaki TemBreak2 MCCB H125-NJ TMD Rating In (A) 50 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=8
Id LPF-4A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.17 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 9 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=10.0
Id LPF-3A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.27 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-2A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.56 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id LPF-1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.22 Design Current Ib (A) 1.6
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id SPF-4A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.24 Design Current Ib (A) 48.8
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=6.7
Id SPF-3A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.68 Design Current Ib (A) 48.8
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=7.4
Id SPF-2A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 2.01 Design Current Ib (A) 48.8
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 10 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=7.4
Id SPF-1A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 1.46 Design Current Ib (A) 48.8
Device Generic MCCB 25kA Electronic I Rating In (A) 50 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=7.5
Id EF-E2A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 5.5
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id DEF-E2 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 10.4
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id DEF-E2A Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 10.4
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id EF-E2 Name
Max Phase Fault Current (kA) 16.98 Earth Fault Current (kA) 0.28 Design Current Ib (A) 5.5
Device Generic MCCB 25kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=10.0
Id SMDB-01-2F-W Name
Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 120.2
Device Terasaki TemBreak2 MCCB H400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 125
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 11 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id SMDB-01-3F-W Name
Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.5
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id SMDB-01-4F-W Name
Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.1
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id SMDB-01-5F-W Name
Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.3
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id SMDB-01-6F-W Name
Max Phase Fault Current (kA) 19.45 Earth Fault Current (kA) 9.72 Design Current Ib (A) 124.5
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id DB-01-2F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 28.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 12 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Settings:
Overload(L)
Ir=1.0
Id DB-01-2F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 28.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id DB-02-2F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id DB-02-2F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id IDB-01-2F Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id LP-01-2F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id LP-02-2F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 10.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 13 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id DB-01-3F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id DB-01-3F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id DB-02-3F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id DB-02-3F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id IDB-01-3F Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 14 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.63
Id LP-01-3F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id LP-02-3F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id DB-01-4F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-01-4F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-02-4F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 15 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.8
Id DB-02-4F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id IDB-01-4F Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id LP-01-4F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id LP-02-4F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 10.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id DB-01-5F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 16 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.8
Id DB-01-5F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-02-5F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.6
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-02-5F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id IDB-01-5F Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id LP-01-5F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id LP-02-5F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 17 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=1.0
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id DB-01-6F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 26.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-01-6F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 36.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-02-6F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 24.9
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id DB-02-6F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 55.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id IDB-01-6F Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 0.73 Design Current Ib (A) 17.4
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 18 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=0.63
Id LP-01-6F-W Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 3.49 Design Current Ib (A) 15.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id LP-02-6F-C Name
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.25 Design Current Ib (A) 11
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Max Phase Fault Current (kA) 18.30 Earth Fault Current (kA) 2.74 Design Current Ib (A) 7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id SMP-NICU Name
Max Phase Fault Current (kA) 24.95 Earth Fault Current (kA) 3.78 Design Current Ib (A) 99
Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Id USMDP-2F Name
Max Phase Fault Current (kA) 21.96 Earth Fault Current (kA) 2.69 Design Current Ib (A) 42.9
Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 125 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Id USMDP-3F Name
Max Phase Fault Current (kA) 21.96 Earth Fault Current (kA) 2.61 Design Current Ib (A) 54.7
Device Terasaki TemBreak2 MCCB S250-NE LSI Rating In (A) 125 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 19 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id IDB-01-2F Name
Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 0.84 Design Current Ib (A) 8.7
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id UDB-01-2F Name
Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 0.95 Design Current Ib (A) 27.3
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.80 Ii=8
Id UDB-02-2F-C Name
Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 2.19 Design Current Ib (A) 12.8
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=8
Id UDB-03-2F-E Name
Max Phase Fault Current (kA) 10.24 Earth Fault Current (kA) 1.10 Design Current Ib (A) 15.8
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=8
Id 1 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 10 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 20 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 11 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 12 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 13 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 14 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 15 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 3.7
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 16 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 17 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 18 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 21 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 19 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 2 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 20 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 21 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 3 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 4 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 5 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 22 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 6 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 7 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 8 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 9 Name
Max Phase Fault Current (kA) 1.74 Earth Fault Current (kA) 0.67 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id Cbl_FC-12-IDB-01-3F Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.83 Design Current Ib (A) 8.7
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id Cbl_FC-13-IDB-01-4F Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.83 Design Current Ib (A) 8.7
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id UDB-01-2F Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 0.94 Design Current Ib (A) 16.7
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=6
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 23 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id UDB-02-3F-C Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 2.14 Design Current Ib (A) 12.8
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id UDB-02-4F-C Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 2.14 Design Current Ib (A) 16.6
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id UDB-03-3F-E Name
Max Phase Fault Current (kA) 10.00 Earth Fault Current (kA) 1.09 Design Current Ib (A) 15.8
Device Terasaki TemBreak2 MCCB S125-NJ TMD Rating In (A) 63 Breaking Capacity Icu (kA) 36
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=0.63 Ii=6
Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 2.08 Design Current Ib (A) 71.3
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 100 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 1.49 Design Current Ib (A) 10.6
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 40 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id ULTRASONIC Name
Max Phase Fault Current (kA) 17.34 Earth Fault Current (kA) 1.74 Design Current Ib (A) 30.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 24 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.37 Design Current Ib (A) 250
Device Terasaki TemBreak2 MCCB S630-CE LSI+LCD meter Rating In (A) 630 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id SMDB -6 Name
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 6.51 Design Current Ib (A) 36.6
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 7.57 Design Current Ib (A) 54.4
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 1.97 Design Current Ib (A) 7.3
Device Terasaki TemBreak2 MCCB S125-GJ TMD Rating In (A) 125 Breaking Capacity Icu (kA) 65
Add-On AFDD N/A
Settings:
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.62 Design Current Ib (A) 28
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 25 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 1.60 Design Current Ib (A) 89.3
Device Terasaki TemBreak2 MCCB S250-PE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.36 Design Current Ib (A) 39
Device Terasaki TemBreak2 MCCB S250-PE LSI Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.96 Design Current Ib (A) 86.2
Device Terasaki TemBreak2 MCCB S400-NE LSIG+LCD meter Rating In (A) 400 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.96 Design Current Ib (A) 70
Device Terasaki TemBreak2 MCCB S400-NE LSIG+LCD meter Rating In (A) 400 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A
Settings:
Id SMB-MOSQUE Name
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 6.09 Design Current Ib (A) 24.4
Device Terasaki TemBreak2 MCCB S125-GJ TMD Rating In (A) 125 Breaking Capacity Icu (kA) 65
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 26 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L) Instantaneous(I)
Ir=1.00 Ii=8
Id SMDB-2 Name
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.44 Design Current Ib (A) 90
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id SMDB-MG Name
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 3.10 Design Current Ib (A) 108.7
Device Terasaki TemBreak2 MCCB S400-NE LSI+LCD meter Rating In (A) 250 Breaking Capacity Icu (kA) 70
Add-On AFDD N/A
Settings:
Max Phase Fault Current (kA) 28.77 Earth Fault Current (kA) 12.59 Design Current Ib (A) 204.7
Device Terasaki TemBreak2 MCCB S400-NE LSI Rating In (A) 400 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Id 1 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 10 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 27 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 11 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 12 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 13 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 1.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 14 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 16 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 17 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 7.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 18 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.62 Design Current Ib (A) 7.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 19 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 28 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 2 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 20 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 21 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 22 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 23 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 24 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 25 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 29 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 26 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 0.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 3 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 4 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 5 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 6 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 7 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 8 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 9 Name
Max Phase Fault Current (kA) 4.24 Earth Fault Current (kA) 1.11 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 30 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 1 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 10 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 11 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 12 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 13 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 1.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 14 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 16 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 31 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 17 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 7.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 18 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 2.13 Design Current Ib (A) 7.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 19 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 2 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 20 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 21 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 22 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 23 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.6
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 32 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 24 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 25 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 3.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 26 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 0.8
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 3 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 4 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 5 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 6 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 33 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Id 7 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 8 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 4.2
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id 9 Name
Max Phase Fault Current (kA) 4.85 Earth Fault Current (kA) 1.32 Design Current Ib (A) 2.1
Device Terasaki TemDin 3 MCB M10 series Type C BSEN60947-2 Rating In (A) 32 Breaking Capacity Icu (kA) 15
Add-On AFDD N/A
Id CP-02 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 1.61 Design Current Ib (A) 2.1
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 25 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.63
Id DB-MG-M2 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 1.7
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id MAC-01 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.23 Design Current Ib (A) 41.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=0.8
Id MAC-02 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 34 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Overload(L)
Ir=1.0
Id MAC-03 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id MAC04 Name
Max Phase Fault Current (kA) 12.57 Earth Fault Current (kA) 2.51 Design Current Ib (A) 41.5
Device Terasaki TemBreak2 MCCB S160-SCJ ATFM Rating In (A) 63 Breaking Capacity Icu (kA) 25
Add-On AFDD N/A
Settings:
Overload(L)
Ir=1.0
Id EAF-M01 Name
Max Phase Fault Current (kA) 7.65 Earth Fault Current (kA) 0.86 Design Current Ib (A) 1.3
Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=2.0
Id EAF-M01A Name
Max Phase Fault Current (kA) 7.65 Earth Fault Current (kA) 0.86 Design Current Ib (A) 1.3
Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=2.0
Id AHU-1A Name
Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.99 Design Current Ib (A) 10
Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=2.0
Id EF-G-02 Name
Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.74 Design Current Ib (A) 1.8
Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Project Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 35 of 36 Printed on: 4/10/2020
:Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Protective Device Settings Report
Instantaneous(I)
I=2.0
Id SPF-5 Name
Max Phase Fault Current (kA) 9.02 Earth Fault Current (kA) 0.99 Design Current Ib (A) 10
Device Generic MCCB 50kA Electronic I Rating In (A) 16 Breaking Capacity Icu (kA) 50
Add-On AFDD N/A
Settings:
Instantaneous(I)
I=2.1