Datasheet SHT3x-DIS: Humidity and Temperature Sensor
Datasheet SHT3x-DIS: Humidity and Temperature Sensor
Product Summary
SHT3x-DIS is the next generation of Sensirion’s package has a footprint of 2.5 x 2.5 mm2 while keeping
temperature and humidity sensors. It builds on a new a height of 0.9 mm. This allows for integration of the
CMOSens® sensor chip that is at the heart of Sensirion’s SHT3x-DIS into a great variety of applications.
new humidity and temperature platform. The SHT3x-DIS Additionally, the wide supply voltage range of 2.4 V to
has increased intelligence, reliability and improved 5.5 V guarantees compatibility with diverse assembly
accuracy specifications compared to its predecessor. Its situations. All in all, the SHT3x-DIS incorporates 15
functionality includes enhanced signal processing, two years of knowledge of Sensirion, the leader in the
distinctive and user selectable I2C addresses and humidity sensor industry.
communication speeds of up to 1 MHz. The DFN
5 Packaging...........................................................15
Figure 1 Functional block diagram of the SHT3x-DIS. The
6 Shipping Package ..............................................17 sensor signals for humidity and temperature are factory
calibrated, linearized and compensated for temperature
7 Quality ................................................................18 and supply voltage dependencies.
8 Ordering Information...........................................18
www.sensirion.com March 2017 - Version 4 1/20
Datasheet SHT3x-DIS
1 Sensor Performance
Humidity Sensor Specification
Parameter Condition Value Units
Typ. 2 %RH
SHT30 Accuracy tolerance1
Max. Figure 2 -
Typ. 2 %RH
SHT31 Accuracy tolerance1
Max. Figure 3 -
Typ. ±1.5 %RH
SHT35 Accuracy tolerance1
Max. Figure 4 -
Low 0.25 %RH
Repeatability2 Medium 0.15 %RH
High 0.10 %RH
Resolution Typ. 0.01 %RH
Hysteresis at 25°C 0.8 %RH
Specified range3 extended4 0 to 100 %RH
Response time5 63% 86 s
Long-term drift Typ.7 <0.25 %RH/yr
Table 1 Humidity sensor specification.
1 For definition of typical and maximum accuracy tolerance, please refer to the document “Sensirion Humidity Sensor Specification Statement”.
2 The stated repeatability is 3 times the standard deviation (3σ) of multiple consecutive measurements at the stated repeatability and at constant ambient conditions. It
is a measure for the noise on the physical sensor output. Different measurement modes allow for high/medium/low repeatability.
3 Specified range refers to the range for which the humidity or temperature sensor specification is guaranteed.
4 For details about recommended humidity and temperature operating range, please refer to section 1.1.
5 Time for achieving 63% of a humidity step function, valid at 25°C and 1m/s airflow. Humidity response time in the application depends on the design-in of the sensor.
6 With activated ART function (see section 4.7) the response time can be improved by a factor of 2.
7 Typical value for operation in normal RH/T operating range, see section 1.1. Maximum value is < 0.5 %RH/yr. Higher drift values might occur due to contaminant
environments with vaporized solvents, out-gassing tapes, adhesives, packaging materials, etc. For more details please refer to Handling Instructions.
8 Temperature response times strongly depend on the type of heat exchange, the available sensor surface and the design environment of the sensor in the final
application.
www.sensirion.com March 2017 - Version 4 2/20
Datasheet SHT3x-DIS
Humidity Sensor Performance Graphs
±4 ±4
±2 ±2
±0 ±0
0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100
SHT30 Relative Humidity (%RH) SHT31 Relative Humidity (%RH)
Figure 2 Tolerance of RH at 25°C for SHT30. Figure 3 Tolerance of RH at 25°C for SHT31.
DRH (%RH)
±6
maximal tolerance
typical tolerance
±4
±2
±0
0 10 20 30 40 50 60 70 80 90 100
SHT35 Relative Humidity (%RH)
SHT30 SHT31
RH (%RH) RH (%RH)
100 ±4 ±4 ±4 ±4 ±4 ±4 ±4 ±4 100 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
90 ±3 ±3 ±3 ±3 ±3 ±3 ±3 ±3 90 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
80 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 80 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
70 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 70 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
60 ±2 ±2 ±2 ±3 ±2 ±2 ±2 ±2 60 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
50 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 50 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
40 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 40 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
30 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 30 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
20 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 20 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
10 ±3 ±3 ±3 ±3 ±3 ±3 ±3 ±3 10 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
0 ±4 ±4 ±4 ±4 ±4 ±4 ±4 ±4 0 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Temperature (°C) Temperature (°C)
Figure 5 Typical tolerance of RH over T for SHT30. Figure 6 Typical tolerance of RH over T for SHT31.
SHT35
RH (%RH)
100 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
90 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2 ±2
80 ±2 ±2 ±2 ±2
70 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2 ±2
60 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2 ±2
50 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2 ±2
40 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2
30 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2
20 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2
10 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2
0 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±1.5 ±2
0 10 20 30 40 50 60 70 80
Temperature (°C)
Figure 7 Typical tolerance of RH over T for SHT35.
±0.5 ±0.5
±0.0 ±0.0
-40 -20 0 20 40 60 80 100 120 -40 -20 0 20 40 60 80 100 120
Figure 8 Temperature accuracy of the SHT30 sensor. Figure 9 Temperature accuracy of the SHT31 sensor.
SHT35
DT (°C)
±1.5
maximal tolerance
typical tolerance
±1.0
±0.5
±0.0
-40 -20 0 20 40 60 80 100 120
Temperature (°C)
2 Specifications
2.1 Electrical Specifications
Parameter Symbol Condition Min. Typ. Max. Units Comments
Supply voltage VDD 2.4 3.3 5.5 V
Power-up/down level VPOR 2.1 2.3 2.4 V
Voltage changes on the
VDD line between
VDD,min and VDD,max
Slew rate change of the
VDD,slew - - 20 V/ms should be slower than
supply voltage
the maximum slew rate;
faster slew rates may
lead to reset;
Current when sensor is
idle state - not performing a
0.2 2.0 A
(single shot mode) measurement during
single shot mode
Current when sensor is
idle state not performing a
(periodic data - 45 - A measurement during
acquisition mode) periodic data acquisition
mode
Supply current IDD
Current consumption
Measuring - 800 1500 A while sensor is
measuring
Current consumption
(operation with one
- measurement per
Average 2 - A
second at lowest
repeatability, single shot
mode)
Alert Output driving
IOH 1.5x VDD mA See also section 3.5
strength
Depending on the
Heater power PHeater Heater running 4.5 - 33 mW
supply voltage
Table 4 System timing specification, valid from -40 °C to 125 °C and 2.4 V to 5.5 V.
7 R
No electrical function; to be connected RP RP
100nF
to VSS nRESET(6) VDD(5)
8 VSS Ground
ALERT(3) SCL(4)
1 8 ADDR(2) SDA(1)
2 7 die
VSS(8) pad R(7)
3 6
4 5 Figure 11 Typical application circuit. Please note that the
positioning of the pins does not reflect the position on the
real sensor. This is shown in Table 6.
Table 6 SHT3x-DIS pin assignment (transparent top view).
Dashed lines are only visible if viewed from below. The die 3.3 Die Pad (center pad)
pad is internally connected to VSS.
The die pad or center pad is visible from below and
located in the center of the package. It is electrically
3.1 Power Pins (VDD, VSS) connected to VSS. Hence electrical considerations do
The electrical specifications of the SHT3x-DIS are shown not impose constraints on the wiring of the die pad.
in Table 3. The power supply pins must be decoupled However, due to mechanical reasons it is recommended
with a 100 nF capacitor that shall be placed as close to to solder the center pad to the PCB. For more
the sensor as possible – see Figure 11 for a typical information on design-in, please refer to the document
application circuit. “SHTxx Design Guide”.
3.2 Serial Clock and Serial Data (SCL, SDA) 3.4 ADDR Pin
SCL is used to synchronize the communication between Through the appropriate wiring of the ADDR pin the I2C
microcontroller and the sensor. The clock frequency can address can be selected (see Table 7 for the respective
be freely chosen between 0 to 1000 kHz. Commands addresses). The ADDR pin can either be connected to
with clock stretching according to I2C Standard11 are logic high or logic low. The address of the sensor can be
supported. changed dynamically during operation by switching the
level on the ADDR pin. The only constraint is that the
The SDA pin is used to transfer data to and from the level has to stay constant starting from the I2C start
sensor. Communication with frequencies up to 400 kHz condition until the communication is finished. This allows
must meet the I2C Fast Mode11 standard. to connect more than two SHT3x-DIS onto the same bus.
11 http://www.nxp.com/documents/user_manual/UM10204.pdf
12 http://www.nxp.com/documents/user_manual/UM10204.pdf
ACK
ACK
ACK
High 37 S I2C Address W Command MSB Command LSB
I2C write header 16-bit command
Medium 10 0x27 21
Low 2A Table 11 Command for a periodic data acquisition with
e.g. 0x2130: 1 high repeatability mps - measurement per the ART feature (Clear blocks are controlled by the
second microcontroller, grey blocks by the sensor).
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ACK
ACK
ACK
4.9 Reset
A system reset of the SHT3x-DIS can be generated
externally by issuing a command (soft reset) or by
sending a pulse to the dedicated reset pin (nReset pin).
Additionally, a system reset is generated internally
during power-up. During the reset procedure the sensor
will not process commands.
Table 10 Fetch Data command (Clear blocks are controlled In order to achieve a full reset of the sensor without
by the microcontroller, grey blocks by the sensor). removing the power supply, it is recommended to use the
nRESET pin of the SHT3x-DIS.
www.sensirion.com March 2017 - Version 4 11/20
Datasheet SHT3x-DIS
Interface Reset
If communication with the device is lost, the following Command Code
signal sequence will reset the serial interface: While Address byte 0x00
leaving SDA high, toggle SCL nine or more times. This Second byte 0x06
must be followed by a Transmission Start sequence Reset command using the
0x0006
preceding the next command. This sequence resets the general call address
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
interface only. The status register preserves its content.
ACK
ACK
S General Call Address Reset Command
Soft Reset / Re-Initialization General Call 1st byte General Call 2nd byte
Table 16 Command to read out the status register (Clear 4.12 Checksum Calculation
blocks are controlled by the microcontroller, grey blocks by
the sensor). The 8-bit CRC checksum transmitted after each data
word is generated by a CRC algorithm. Its properties are
displayed in Table 19. The CRC covers the contents of
the two previously transmitted data bytes. To calculate
Bit Field description Default the checksum only these two previously transmitted data
value bytes are used.
15 Alert pending status ‘1’
Property Value
'0': no pending alerts
'1': at least one pending alert Name CRC-8
14 Reserved ‘0’
Width 8 bit
13 Heater status ‘0’
‘0’ : Heater OFF Protected data read and/or write data
‘1’ : Heater ON Polynomial 0x31 (x8 + x5 + x4 + 1)
12 Reserved ‘0’ Initialization 0xFF
11 RH tracking alert ‘0
Reflect input False
‘0’ : no alert
‘1’ . alert Reflect output False
10 T tracking alert ‘0’ Final XOR 0x00
‘0’ : no alert Examples CRC (0xBEEF) = 0x92
‘1’ . alert
9:5 Reserved ‘xxxxx’ Table 19 I2C CRC properties.
4 System reset detected ‘1’
'0': no reset detected since last ‘clear 4.13 Conversion of Signal Output
status register’ command Measurement data is always transferred as 16-bit values
'1': reset detected (hard reset, soft reset
(unsigned integer). These values are already linearized
command or supply fail) and compensated for temperature and supply voltage
3:2 Reserved ‘00’ effects. Converting those raw values into a physical
1 Command status ‘0’ scale can be achieved using the following formulas.
'0': last command executed successfully Relative humidity conversion formula (result in %RH):
'1': last command not processed. It was
either invalid, failed the integrated S RH
command checksum RH 100
2 16 1
0 Write data checksum status ‘0’
'0': checksum of last write transfer was Temperature conversion formula (result in °C & °F):
correct
ST
'1': checksum of last write transfer failed T C 45 175
2 116
Table 17 Description of the status register.
S
T F 49 315 16 T
Clear Status Register 2 1
All flags (Bit 15, 11, 10, 4) in the status register can be SRH and ST denote the raw sensor output for humidity
cleared (set to zero) by sending the command shown in and temperature, respectively. The formulas work only
Table 18. correctly when SRH and ST are used in decimal
representation.
Table 20 Communication timing specifications for I2C fm (fast mode), specifications are at 25°C and typical VDD. The numbers above
are values according to the I2C Specification (UM10204, Rev. 6, April 4, 2014).
1/fSCL
tHIGH tLOW tR tF
70%
SCL 30%
tSU;DAT tHD;DAT
DATA IN
70%
SDA 30%
tR
tVD;DAT tF
DATA OUT
70%
SDA 30%
Figure 12 Timing diagram for digital input/output pads. SDA directions are seen from the sensor. Bold SDA lines are
controlled by the sensor, plain SDA lines are controlled by the micro-controller. Note that SDA valid read time is triggered
by falling edge of preceding toggle.
2.35 2.55
0.5
0.5
0.25
0.25
0.5
1.6
1.7
0.5
0.5
0.5
Figure 15 Recommended metal land pattern (left) and stencil apertures (right) for SHT3x-DIS. The dashed lines represent the outer
dimension of the DFN package. The PCB pads (left) and stencil apertures (right) are indicated through the shaded areas.
6 Shipping Package
Ø1.5 +.1 /-0.0
4.00
2.00 ±.05 SEE Note 2 Ø1.00 MIN
4.00 SEE Note 1 1.75 ±.1
0.30 ±.05
A
5.50 ±.05
R 0.2 MAX. SEE NOTE 2
B0
B
12.0 +0.3/-0.1
A
K0 R 0.25 TYP.
A0
A0 = 2.75
B0 = 2.75
SECTION A - A K0 = 1.20
TOLERANCES - UNLESS
NOTED 1PL ±.2 2PL ±.10
NOTES:
1. 10 SPROCKET HOLE PITCH CUMULATIVE TOLERANCE ±0.2
2. POCKET POSITION RELATIVE TO SPROCKET HOLE MEASURED DETAIL B
AS TRUE POSITION OF POCKET, NOT POCKET HOLE
3. A0 AND B0 ARE CALCULATED ON A PLANE AT A DISTANCE "R"
ABOVE THE BOTTOM OF THE POCKET
Figure 16 Technical drawing of the packaging tape with sensor orientation in tape. Header tape is to the right and trailer tape to the
left on this drawing. Dimensions are given in millimeters.
9 Further Information
For more in-depth information on the SHT3x-DIS and its application please consult the documents in Table 23.
Parameter values specified in the datasheet overrule possibly conflicting statements given in references cited in
this datasheet.
Document Name Description Source
Revision History
Date Version Page(s) Changes
October 2015 1 -
March 2017 4 2-5 Updated RH&T accuracy specifications, see Table 1, Table 2, Figure 2,
Figure 5, Figure 8, Figure 9 and Figure 10
9 Table 7 updated
6 Table 3 updated
8 Figure 11 updated
15 Table 20 updated
17 Table 21 updated
18 Figure 15 land pattern drawing simplified (no parameter changed)
19 Inlcuded: “Parameter values specified in the datasheet overrule possibly
conflicting statements given in references cited in this datasheet.“
Important Notices
Warning, Personal Injury
Do not use this product as safety or emergency stop devices such defects shall be found, to SENSIRION’s reasonable
or in any other application where failure of the product could satisfaction, to have arisen from SENSIRION’s faulty
result in personal injury. Do not use this product for design, material, or workmanship;
applications other than its intended and authorized use. the defective product shall be returned to SENSIRION’s
Before installing, handling, using or servicing this product, factory at the Buyer’s expense; and
please consult the data sheet and application notes. Failure the warranty period for any repaired or replaced product
to comply with these instructions could result in death or shall be limited to the unexpired portion of the original
serious injury. period.
This warranty does not apply to any equipment which has not
If the Buyer shall purchase or use SENSIRION products for any been installed and used within the specifications recommended
unintended or unauthorized application, Buyer shall defend, by SENSIRION for the intended and proper use of the
indemnify and hold harmless SENSIRION and its officers, equipment. EXCEPT FOR THE WARRANTIES EXPRESSLY
employees, subsidiaries, affiliates and distributors against all SET FORTH HEREIN, SENSIRION MAKES NO WARRANTIES,
claims, costs, damages and expenses, and reasonable attorney EITHER EXPRESS OR IMPLIED, WITH RESPECT TO THE
fees arising out of, directly or indirectly, any claim of personal PRODUCT. ANY AND ALL WARRANTIES, INCLUDING
injury or death associated with such unintended or unauthorized WITHOUT LIMITATION, WARRANTIES OF
use, even if SENSIRION shall be allegedly negligent with respect MERCHANTABILITY OR FITNESS FOR A PARTICULAR
to the design or the manufacture of the product. PURPOSE, ARE EXPRESSLY EXCLUDED AND DECLINED.
SENSIRION is only liable for defects of this product arising under
ESD Precautions the conditions of operation provided for in the data sheet and
The inherent design of this component causes it to be sensitive proper use of the goods. SENSIRION explicitly disclaims all
to electrostatic discharge (ESD). To prevent ESD-induced warranties, express or implied, for any period during which the
damage and/or degradation, take customary and statutory ESD goods are operated or stored not in accordance with the technical
precautions when handling this product. specifications.
See application note “ESD, Latchup and EMC” for more SENSIRION does not assume any liability arising out of any
information. application or use of any product or circuit and specifically
disclaims any and all liability, including without limitation
Warranty consequential or incidental damages. All operating parameters,
SENSIRION warrants solely to the original purchaser of this including without limitation recommended parameters, must be
product for a period of 12 months (one year) from the date of validated for each customer’s applications by customer’s
delivery that this product shall be of the quality, material and technical experts. Recommended parameters can and do vary in
workmanship defined in SENSIRION’s published specifications different applications.
of the product. Within such period, if proven to be defective, SENSIRION reserves the right, without further notice, (i) to
SENSIRION shall repair and/or replace this product, in change the product specifications and/or the information in this
SENSIRION’s discretion, free of charge to the Buyer, provided document and (ii) to improve reliability, functions and design of
that: this product.
notice in writing describing the defects shall be given to
SENSIRION within fourteen (14) days after their Copyright © 2017, by SENSIRION.
appearance; CMOSens® is a trademark of Sensirion