PLC

Allen Bradley Micrologix


www.nfiautomation.org

nfi
This is a PLC

Output Terminals
Input Terminals

Programming Cable
Power 24 VDC
Understanding PLC
Understanding PLC
Wiring PLC
Wiring PLC
Wiring PLC
Wiring PLC
Wiring PLC
Wiring PLC
Wiring PLC
PLC Ladder Logic
Addressing the PLC
Inputs
I: 0/0 First Input I: 0/1 Second Input
Addressing the PLC
Outputs
O: 0/0 First Output O: 0/1 Second Output
Addressing the PLC
Internal Bits
B3: 0/0
Addressing the PLC
Timers
T4: 0
Addressing the PLC
Counters
C5: 0
Addressing the PLC
Control Registers
R6: 0
Addressing the PLC
Data Register
N7: 0
Addressing the PLC
Instruction Palette
Programming PLC
Add new Rung
Programming PLC
Parallel Rung at Input

Parallel Rung at Output


Programming PLC
Normally Open/ Normally Close/
Examine if Open Examine if Close

Output Energize Output Latched Output Unlatched

One Shot Rising


Programming PLC
Timer – ON DELAY
Timer Reset

Timer – OFF DELAY

Timer – Retentive Type


Programming PLC
Counter – Up

Done bit is ON when Acc. >= Preset

Counter - Down

Done bit is ON when Acc. >= Preset

Counter Reset
Programming PLC
Limit Test

Example:
Programming PLC
Equalizer

Example:
Programming PLC
Not Equal to

Example:
Programming PLC
Less Than <

Example:
Programming PLC
Less Than or Equal to <=

Example:
Programming PLC
Greater Than >

Example:
Programming PLC
Greater Than or equal to >=

Example:
Programming PLC
Greater Than or equal to >=

Example:
Programming PLC
MEQ = Masked Equal to

Example:

Output will be energized when N7:0 “AND” with N7:1 equals N7:5
Bit wise multiplication
Programming PLC
Scale

N7:9= {N7:0 x (Rate/10000)} + offset


N7:9 = {44 x (5000/10000)} + 5
N7:9 = 27

Example:

When Input is energized, Scaling will be done


Programming PLC
Square Root

N7:1= 49
N7:8 = 7 (after command executed)

Example:

When Input is energized, Square root function will be performed


Programming PLC
Negate

N7:0= 44
N7:0 = -44 (after command executed)

Example:

When Input is energized, Negate function will be performed


Programming PLC
MVM = Masked Move

N7:5 = N7:0 bit wise AND with N7:2

Example:

When Input is energized, MVM will be performed


Programming PLC
Copy File

N7:0 ------------ N7:10


N7:1 ------------ N7:11
N7:2 ------------ N7:12
N7:3 ------------ N7:13
N7:4 ------------ N7:14

Example:

When Input is energized, Copy Function will be performed


Programming PLC
Fill File

N7:0 ------------ N7:10


N7:0 ------------ N7:11
N7:0 ------------ N7:12
N7:0 ------------ N7:13
N7:0 ------------ N7:14
N7:0 ------------ N7:15

Example:

When Input is energized, Fill Function will be performed


Math Error

Note:
In Allen Bradley, Fault occurs when calculation value exceeds

32767
Programming PLC
Flow Control Instructions
Case 1: When Jump is not enabled
Jump & Label When I:0/5 is True/False B3:0 is On/Off
When I:0/4 is True/False B3:1 is On/Off
When I:0/3 is True/False O:0/2 is On/Off

Case 2: When Jump is Enabled


When I:0/5 is True/False B3:0 will be at last state – No effect
When I:0/4 is True/False B3:1 will be at last state – No effect
When I:0/3 is True/False O:0/2 is On/Off
Example:
Programming PLC
Flow Control Instructions
Case 1: When Subroutine is not called
Jump Subroutine & Return U:3 i.e. Subroutine program wont be scanned by CPU

Main Program

Case 2: When Subroutine is called


U:3 i.e. Subroutine program starts getting scanned by CPU
Subroutine

Case 3: When Return is executed


Ouput of U:3 ladder get freezed & remain at that state
Programming PLC
Temporary END

Example:

When I:0/5 is energized ladder below TND is not scanned by CPU


Programming PLC
Temporary END

Example:

When I:0/5 is energized ladder below TND is not scanned by CPU


Programming PLC
Sequencer Output

Example:

File is the address of the sequencer file. Make sure to use the file indicator (#). This file stores the reference data for
monitoring inputs.
Mask is a hexadecimal code or the address of the mask word or file through which the instruction moves data. If
the mask is a file, its length will be equal to the length of the sequencer file. The two files track automatically.
You can enter the code in binary, decimal, or hexadecimal.
Destination is the address of the output word or file for a SQO to which the instruction moves data from its
sequencer file.
Control is the instruction’s address and control element (3 words) that stores the status byte of the instruction, the
length of the file, and the position in the file. Do not use this address for any other instruction. Status bits in the
control file include
Length is the number of steps of the sequencer file starting at position 1. Maximum = 255 words (104 words when
using the MicroLogix controller). Position 0 is the startup position. The instruction resets (wraps) to position 1 at each
cycle completion.
Position is the word location or step in the sequencer file from/to which the instruction moves data. A position value
that points past the end of the programmed file causes a runtime major error to occur.
Programming PLC
Sequencer Output

Example:
Programming PLC
Sequencer Compare

Example:

R6:3/FD is bit which is ON when comparison is TRUE


i.e. When I:0.0 masked with B3:1 & result equals B3:0

This command can be used for diagnostic purpose such that to check
Whether specified inputs are ON or OFF at various stages of sequence
Ex Homing, Station 1, Station 2 etc.
Programming PLC
Sequencer Load

Example:

This command stores the status of Inputs at N7:0 till number of position
mentioned. In this case upto N7:4

Position 1  N7:1
Position 2  N7:2
Position 3  N7:3
Position 4  N7:4 Values get over rite when cycle completes
Thanks