Professional Documents
Culture Documents
Ex Prob Composite
Ex Prob Composite
Given: An interior floor beam as shown in BGSCM Figure 10.8.1.1. The W16x26 beams are spaced 4'-0" O.C. and span 40
An interior floor beam as shown in BGSCM Figure 10.8.1.1. The W16x26 beams are spaced 4'-0" O.C. and span 4
The beams are simply supported. The 4" thick normal weight concrete slab has a 28-day compressive strength, f'c, o
The beams are simply supported. The 4" thick normal weight concrete slab has a 28-day compressive strength, f'c,
ksi. The studs are 1/2" diameter and have Fu = 65 ksi. The floor live load is taken as 50 psf and the floor dead load
ksi. The studs are 1/2" diameter and have Fu = 65 ksi. The floor live load is taken as 50 psf and the floor dead loa
(including beam, slab, and other items) is 75 psf.
(including beam, slab, and other items) is 75 psf.
Part a) Compute bE
Left Side 2 ft
Right Side 2 ft
bE 4 ft
48 in
Compute ITR:
y relative to:
Area Io top of slab ENA y2*A ITR
(in2) (in )
4
(in) (in) (in3) (in4)
Block 21.33 28.44 2.00 -2.61 145.03 173.47
W16 7.68 301 11.85 7.24 402.86 703.86
Total ITR = 877.34
Compute Deflection
wL 200.0 plf
DLL 0.453 in = L / 1060.1
DLL,allow = L / 360
Allow/Act 0.340 Good!
d 4'-0" O.C. and span 40 ft.
ed 4'-0" O.C. and span 40 ft.
mpressive strength, f'c, of 3.5
ompressive strength, f'c, of 3.5
and the floor dead load
sf and the floor dead load
p
A Beginners Guide to the Steel Construction Manual last modified: 28 July 2008
Example Problem 10.2 by: TBQ
Given: A floor system similar to that shown in BGSCM Figure 10.1.1. The slab is 4" thick and is made from concrete with f'c
A floor system similar to that shown in BGSCM Figure 10.1.1. The slab is 4" thick and is made from concrete with f
3,000 psi. The floor beams span 50 ft and are spaced 5 ft apart. Assume that the beams are shored at third points
3,000 psi. The floor beams span 50 ft and are spaced 5 ft apart. Assume that the beams are shored at third points
during construction. The beams only have lateral support at shoring and the ends during the initial construction. The
during construction. The beams only have lateral support at shoring and the ends during the initial construction. Th
imposed floor dead load is 25 psf , the construction live load is 20 psf, and the occupancy floor live load is 50 psf.
imposed floor dead load is 25 psf , the construction live load is 20 psf, and the occupancy floor live load is 50 psf.
Consider studs of 1/2", 5/8", 3/4", and 7/8" diameter.
Consider studs of 1/2", 5/8", 3/4", and 7/8" diameter.
Wanted:
Select the lightest I-shaped section for the application considering both ASD and LRFD. Also determine
Select
the the lightest
number I-shaped
and spacing section
of shear forneeded
studs the application considering
for full composite both ASD and LRFD. Also determine
action.
the number and spacing of shear studs needed for full composite action.
Solution:
Current Section W16X26 <----- Change this value until the best solution is found!
Determine bE
Left Right Total
(in) (in) (in)
L/8 75 75
(C-C)/2 30 30
bE : 30 30 60 in
Assume yna<ts
T=C= 384 k
a= 2.51 in
y(pna) = a/beta1 = 2.95 in measured from the top
yna/ts 0.74 ... Assumption O.K.
arm 10.60 in
Mn 4068.52 in-k
Mn 339.04 ft-k ... USE THIS ONE
Capacity Check
ASD LRFD
Modifier 1.67 0.9
Mcx 203.02 305.14
Mrx 203.44 275.38
Mrx/Mcx 1.002 0.902
Shear Capacity
Capacity Check
lp 59.2 ASD LRFD
lr 73.8 Modifier 1.67 0.9
Vn 117.75 Vc 70.51 105.98
Equation G2-5 Vr 16.28 22.03
Vr/Vc 0.231 0.208
Shear Connectors
Design Load
.85f'cAc 612 kips <- Max Concrete Force
AsFy 384 kips <- Max Steel Force
Deflection Calculation
Transformed bE 6.67 in
Area y(top) Ay Io y(na) Ay^2 Ix
(in^2) (in) (in^3) (in^4) (in) (in^4) (in^4)
Concrete 26.67 -2.00 -53.33 35.56 2.20 129.36 164.91
Steel 7.68 -11.85 -91.01 301.00 -7.65 449.16 750.16
CoverPL 0.00 -19.70 0.00 0.00 -15.50 0.00 0.00
34.35 -4.20 -144.34 915.07
Note at the "y" terms are computed relative to the centroidal axis of the stl section
ksi
ksi
so determine
lso determine