Sitarama SFC & Marshalling Control Schedule
Sitarama SFC & Marshalling Control Schedule
Sitarama SFC & Marshalling Control Schedule
COMMON
LCI-1002 4CX 4SQMM CU UPS 1 ACDB-1 SFC 1
8 TLS 1 TB 12 SFC 1
17 TLS 1 TB SFC 1
LCI-1004
18 TLS 1 TB SFC 1
9 TLS 1 TB 1 SFC 1
10 TLS 1 TB 2 SFC 1
11 TLS 1 TB 3 SFC 1
12 TLS 1 TB 4 SFC 1
13 TLS 1 TB 13 SFC 1
14 TLS 1 TB 14 SFC 1
15 TLS 1 TB 15 SFC 1
16 TLS 1 TB 16 SFC 1
TMS TRANSFORMER TO SFC 1
TMS 1 TB 5 SFC 1
TMS 1 TB 6 SFC 1
TMS 1 TB 7 SFC 1
TMS 1 TB 8 SFC 1
TMS 1 TB 9 SFC 1
TMS 1 TB 10 SFC 1
TMS 1 TB 11 SFC 1
24CX1.5SQMM
TMS 1 TB 12 SFC 1
TMS 1 TB SFC 1
LCI1005
TMS 1 TB SFC 1
TMS 1 TB 1 SFC 1
TMS 1 TB 2 SFC 1
TMS 1 TB 3 SFC 1
TMS 1 TB 4 SFC 1
TMS 1 TB 13 SFC 1
TMS 1 TB 14 SFC 1
TMS 1 TB 15 SFC 1
TMS 1 TB 16 SFC 1
ICB 1 TO SFC 1 ( Master Relay NC )
XO5 16
LCI1006 3CX2.5SQMM CU ICB 1 SFC 1
X05 18
OCB 1 TO SFC 1 ( Master Relay NC )
X05 21
LCI1008 3CX2.5SQMM CU OCB 1 SFC 1
X05 22
SFC 1 TO ICB 1
X03 3
LCI1007 3CX2.5SQMM CU ICB-1 SFC-1
X03 4
MARSHALING TO SFC 1 INTERFACE FOR MOTOR AND EXCITATION SIGNALS
1 K_LCI1 1
LCI009 2CX2.5SQMM ISC SFC 1
2 K_LCI1 2
1 K_LCI1 13
2 K_LCI1 14
7CX2.5SQMM
5
LCI1010 6 ISC SFC 1
3 K_LCI1 10
4 K_LCI1 11
7
1 K_LCI1 4
2 K_LCI1 5
7CX2.5SQMM
3 K_LCI1 7
3 PAIR X1.5SQMM
8 X06 8
LCI1013 9 SFC 1 X06 9 CM PLC
10 X06 10
11 X06 13
12 X06 14
13 X06 15
14 X06 16
15
16
17
1 X05 1
2 X05 2
3 X05 3
4 X05 4
12C*1.5 SQMM
5 X05 47
6 X05 48
LCI1014 SFC 1 CM PLC
7
8
9
10
11
12
ISC to SFC 1
1
2
3
4
X_LCI1_DO
LCI1015 5
12C*1.5 SQMM ISC
6
7
SFC 1
8
9
10
SFC 1 to ISC
11
SFC 2 X06 ISC
12
Manual Synchronization Marshalling Panel to SFC 1
Manaul
Synchroni
zation SFC 1
Marshalli
ng Panel
M TB SUB TB Cable ferrul no
From To
XO1 1 SAB-3 14F R-PH/SFC-1 X01-1 LCI-1 X01-1/SAB-3 14F R-PH
XO1 2 SAB-3 14F Y-PH/SFC-1 X01-2 LCI-1 X01-2/SAB-3 14F Y-PH
XO1 3 SAB-3 14F B-PH/SFC-1 X01-3 LCI-1 X01-3/SAB-3 14F B-PH
XO1 4
XO1 5
XO1 6
XO1 7
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
59
60
X05
9
10
61
X05
62
57
X05
58
63
X05
64
13
X05
14
1
2
3
4
5
6
X38
7
8
9
10
11
12
Describtion
230VAC SOURCE 1
230VAC SOURCE 1
*BUCHHOLZ ALARM
BUCHHOLZ ALARM
ICB IS TRIPPING
OCB IS TRIPPING
TRIP ICB
SCB is Tripping
Excitation is ON
MACHINCE VOLTAGE
EXC REFERANCE(AO)
LCI IS HEALTHY
MV ON FEEDBACK
OPERATION ON FEEDBACK
SCB IS CLOSED
RCB IS CLOSED
OPERATION READY
Alarm
FAULT
OCB is Closed
Spare
OPERATION READY
Frequency lower
Frequency Raise
Voltage lower
Voltage Raise
220VDC
1
ISC PTB1
3
PLC to ISC
3
X_LCI1_DI
4
3
X_LCI2_DI
4
3
X_CUSTOMER_DI
4
7
X_CUSTOMER_DI
8
PLC ISC
11
X_CUSTOMER_DI
12
15
X_CUSTOMER_DI
16
19
X_CUSTOMER_DI
20
23
X_CUSTOMER_DI
24
RCB Close FB Direct from Breaker
5
RCB1 X_CUSTOMER_DI
6
9
RCB2 X_CUSTOMER_DI
10
13
RCB3 X_CUSTOMER_DI
14
ISC
17
RCB4 X_CUSTOMER_DI
18
21
RCB5 X_CUSTOMER_DI
22
25
RCB6 X_CUSTOMER_DI
26
ISC to PLC
1
2
3
4
M
ER
5
6
7
24C*1.5 SQMM
X_CUSTOMER
8
9
_DO
ISC PLC
10
11
12
13
14
15
16
17
18
ISC TO RCB 1
15 K_M1 1
RCB 1/MPP TB07 ISC
16 K_M1 2
EXC 1 TO ISC
bkr 33 K_M1 10
EXC 1 ISC
bkr 34 K_M1 11
X5 25 K_M1 13
EXC 1 ISC
X5 26 K_M1 14
SCB 1 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
XO5 13 K_M1 spare
SCB 1 ISC
X05 15 K_M1 spare
BUS PT TO ISC
K_M1 4
BUS PT ISC
K_M1 5
LAVT 1 TO ISC
K_M1 7
LAVT 1 ISC
K_M1 8
EXC 1 TO ISC
X10 48 K_M1 19
EXC 1
X10 47 K_M1 20
ISC
X5 71 K_M1 16
EXC 1
X5 72 K_M1 17
ISC TO RCB 2
K_M2 1
RCB 2 ISC
K_M2 2
EXC 2 TO ISC
K_M2 10
EXC 2 ISC
K_M2 11
K_M2 13
EXC 2 ISC
K_M2 14
SCB 2 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M2
SCB 2 ISC
SCB 2 ISC
K_M2
BUS PT TO ISC
K_M2 4
BUS PT ISC
K_M2 5
LAVT 2 TO ISC
K_M2 7
LAVT 2 ISC
K_M2 8
EXC 2 TO ISC
K_M2 19
EXC 2
K_M2 20
ISC
K_M2 16
EXC 2
K_M2 17
ISC TO RCB 3
K_M3 1
RCB 3 ISC
K_M3 2
EXC 3 TO ISC
K_M3 10
EXC 3 ISC
K_M3 11
K_M3 13
EXC 3 ISC
K_M3 14
SCB 3 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M3
SCB 3 ISC
K_M3
BUS PT TO ISC
K_M3 4
BUS PT ISC
K_M3 5
LAVT 3 TO ISC
K_M3 7
LAVT 3 ISC
K_M3 8
EXC 3 TO ISC
K_M3 19
EXC 3
K_M3 20
ISC
K_M3 16
EXC 3
K_M3 17
ISC TO RCB 4
K_M4 1
RCB 4 ISC
K_M4 2
EXC 4 TO ISC
K_M4 10
EXC 4 ISC
K_M4 11
K_M4 13
EXC 4 ISC
K_M4 14
SCB 4 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M4
SCB 4 ISC
K_M4
BUS PT TO ISC
K_M4 4
BUS PT ISC
K_M4 5
LAVT 4 TO ISC
K_M4 7
LAVT 4 ISC
K_M4 8
EXC 4 TO ISC
K_M4 19
EXC 4
K_M4 20
ISC
K_M4 16
EXC 4
K_M4 17
ISC TO RCB 5
K_M5 1
RCB 5 ISC
K_M5 2
EXC 5 TO ISC
K_M5 10
EXC 5 ISC
K_M5 11
K_M5 13
EXC 5 ISC
K_M5 14
SCB 5 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M5
SCB 5 ISC
K_M5
BUS PT TO ISC
K_M5 4
BUS PT ISC
K_M5 5
LAVT 5 TO ISC
K_M5 7
LAVT 5 ISC
K_M5 8
EXC 5 TO ISC
K_M5 19
EXC 5
K_M5 20
ISC
K_M5 16
EXC 5
K_M5 17
ISC TO RCB 6
K_M6 1
RCB 6 ISC
K_M6 2
EXC 6 TO ISC
K_M6 10
EXC 6 ISC
K_M6 11
K_M6 13
EXC 6 ISC
K_M6 14
SCB 6 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M6
SCB 6 ISC
K_M6
BUS PT TO ISC
K_M6 4
BUS PT ISC
K_M6 5
LAVT 6 TO ISC
K_M6 7
LAVT 6 ISC
K_M6 8
EXC 6 TO ISC
K_M6 19
EXC 6
K_M6 20
ISC
K_M6 16
EXC 6
K_M6 17
For PLC Describtion
220VDC
OCB 1 is Closed
OCB 2 is closed
SCB 1 is Closed
SCB 2 is Closed
SCB 3 is Closed
SCB 4 is Closed
SCB 5 is Closed
SCB 6 is Closed
RCB1 is Closed
RCB2 is Closed
RCB3 is Closed
RCB4 is Closed
RCB5 is Closed
RCB6 is Closed
Motor 1 Selected
Motor 2 Selected
Motor 3 Selected
Motor 4 Selected
Motor 5 Selected
Motor 6 Selected
Operation Ready
ALARM
FAULT
EXCITATION is ON
SCB is Tripping
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
EXCITATION is ON
SCB is Tripping
SCB is Tripping
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
EXCITATION is ON
SCB is Tripping
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
EXCITATION is ON
SCB is Tripping
LINE SYN VOLTAGE
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
EXCITATION is ON
SCB is Tripping
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
EXCITATION is ON
SCB is Tripping
LINE SYN VOLTAGE
MACHINCE VOLTAGE
EXC ACTUAL
EXC REFERANCE
TAG Cable C NO FROM M TB S TB TO M TB SUB TB For PLC
Size
LT AUX SUPPLY FEDEER TO SFC 2
XO1 1
4CX6SQM XO1 2
LT SFC 2
M CU XO1 3
SFC 1 TO ICB 1
3CX2.5SQ 17
SFC 2 ICB 2 X06
MM CU 18
MARSHALING TO SFC 2 INTERFACE FOR MOTOR AND EXCITATION SIGNALS
2CX2.5SQ 1 K_LCI2 1 21
MM ISC SFC 2 X06
2 K_LCI2 2 22
1 K_LCI2 13 11
X05
2 K_LCI2 14 12
7CX2.5SQMM
3
spareTB
4 ISC SFC 2
5 K_LCI2 10 7
X05
6 K_LCI2 11 8
7
1 K_LCI2 4 X03 7
2 K_LCI2 5 X03 8
7CX2.5SQMM
3 K_LCI2 7 X03 10
4 ISC K_LCI2 8 SFC 2 X03 11
5
6
7
1 K_LCI2 19 1
IR X1.5SQMM
X03 AI
ISC SFC 2
3 PAIR X1.5SQMM
X03 AI
2 K_LCI2 20 2
1 K_LCI2 16 4
ISC SFC 2 X03 AO
2 K_LCI2 17 5
1
2
SFC-2 TO COMMON PLC
1 X06 1
DI
2 X06 2
3 X06 3
DI
4 X06 4
5 X06 5
DI
6 X06 6
7 X06 7
17C*1.5 SQMM
DI
8 X06 8
9 SFC 2 X06 9 CM PLC
DI
10 X06 10
11 X06 13
DI
12 X06 14
13 X06 15
DI
14 X06 16
15
16
17
1 X05 1
DO
2 X05 2
3 X05 3
DO
4 X05 4
12C*1.5 SQMM
5 X05 47
DO
6 X05 48
SFC 2 CM PLC
7
8
9
10
11
12
ISC to SFC 2
1 59
2 60
X05
3 9
4 10
X_LCI2_DO
5
12C*1.5 SQMM ISC
6
7
SFC 2
8
9 61
X05
10 62
57
X05
X05
58
63
X05
64
SFC 2 to ISC
11
SFC 2 X06 ISC
12
Manual Synchronization Marshalling Panel to SFC 2
13
X05
14
1
2
3
Manaul 4
Synchroni 5
zation SFC 2
Marshalli 6
X38
ng Panel 7
8
9
10
11
12
Describtion
230VAC SOURCE 1
230VAC SOURCE 1
*BUCHHOLZ ALARM
BUCHHOLZ ALARM
BUCHHOLZ ALARM
ICB IS TRIPPING
OCB IS TRIPPING
TRIP ICB
SCB is Tripping
Excitation is ON
MACHINCE VOLTAGE
EXC ACTUAL
EXC ACTUAL
EXC REFERANCE
LCI IS HEALTHY
MV ON FEEDBACK
OPERATION ON FEEDBACK
SCB IS CLOSED
RCB IS CLOSED
OPERATION READY
Alarm
FAULT
OCB is Closed
OCB is Closed
Spare
OPERATION READY
Frequency lower
Frequency Raise
Voltage lower
Voltage Raise