Sitarama SFC & Marshalling Control Schedule

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 27

TAG Cable Size C NO FROM M TB S TB TO

LT AUX SUPPLY FEDEER TO SFC 1


14F-R
14F-Y
LCI-1001 4CX4SQMM CU LT SAB-3 SFC 1
14F-B

UPS SUPPLY TO SFC 1

COMMON
LCI-1002 4CX 4SQMM CU UPS 1 ACDB-1 SFC 1

AUXILIARY SUPPLY TO SFC 1


AUX COMMON
LCI-1003 3CX6SQMM CU SFC 1
SUPPLY ACDB-1
TLS TRANSFORMER TO SFC 1
1 TLS 1 TB 5 SFC 1
2 TLS 1 TB 6 SFC 1
3 TLS 1 TB 7 SFC 1
4 TLS 1 TB 8 SFC 1
5 TLS 1 TB 9 SFC 1
6 TLS 1 TB 10 SFC 1
7 TLS 1 TB 11 SFC 1
24CX1.5SQMM

8 TLS 1 TB 12 SFC 1
17 TLS 1 TB SFC 1
LCI-1004
18 TLS 1 TB SFC 1
9 TLS 1 TB 1 SFC 1
10 TLS 1 TB 2 SFC 1
11 TLS 1 TB 3 SFC 1
12 TLS 1 TB 4 SFC 1
13 TLS 1 TB 13 SFC 1
14 TLS 1 TB 14 SFC 1
15 TLS 1 TB 15 SFC 1
16 TLS 1 TB 16 SFC 1
TMS TRANSFORMER TO SFC 1
TMS 1 TB 5 SFC 1
TMS 1 TB 6 SFC 1
TMS 1 TB 7 SFC 1
TMS 1 TB 8 SFC 1
TMS 1 TB 9 SFC 1
TMS 1 TB 10 SFC 1
TMS 1 TB 11 SFC 1
24CX1.5SQMM

TMS 1 TB 12 SFC 1
TMS 1 TB SFC 1
LCI1005
TMS 1 TB SFC 1
TMS 1 TB 1 SFC 1
TMS 1 TB 2 SFC 1
TMS 1 TB 3 SFC 1
TMS 1 TB 4 SFC 1
TMS 1 TB 13 SFC 1
TMS 1 TB 14 SFC 1
TMS 1 TB 15 SFC 1
TMS 1 TB 16 SFC 1
ICB 1 TO SFC 1 ( Master Relay NC )
XO5 16
LCI1006 3CX2.5SQMM CU ICB 1 SFC 1
X05 18
OCB 1 TO SFC 1 ( Master Relay NC )
X05 21
LCI1008 3CX2.5SQMM CU OCB 1 SFC 1
X05 22
SFC 1 TO ICB 1
X03 3
LCI1007 3CX2.5SQMM CU ICB-1 SFC-1
X03 4
MARSHALING TO SFC 1 INTERFACE FOR MOTOR AND EXCITATION SIGNALS
1 K_LCI1 1
LCI009 2CX2.5SQMM ISC SFC 1
2 K_LCI1 2
1 K_LCI1 13
2 K_LCI1 14
7CX2.5SQMM

5
LCI1010 6 ISC SFC 1
3 K_LCI1 10
4 K_LCI1 11
7
1 K_LCI1 4
2 K_LCI1 5
7CX2.5SQMM

3 K_LCI1 7
3 PAIR X1.5SQMM

LCI1011 4 ISC K_LCI1 8 SFC 1


5
6
7
LCI1012 1 ISC K_LCI1 19 SFC 1
2 K_LCI1 20
1 K_LCI1 16
2 K_LCI1 17
1
SFC-1 TO
COMMON 2
PLC
1 X06 1
2 X06 2
3 X06 3
4 X06 4
5 X06 5
6 X06 6
7 X06 7
17C*1.5 SQMM

8 X06 8
LCI1013 9 SFC 1 X06 9 CM PLC
10 X06 10
11 X06 13
12 X06 14
13 X06 15
14 X06 16
15
16
17
1 X05 1
2 X05 2
3 X05 3
4 X05 4

12C*1.5 SQMM
5 X05 47
6 X05 48
LCI1014 SFC 1 CM PLC
7
8
9
10
11
12
ISC to SFC 1
1
2
3
4

X_LCI1_DO
LCI1015 5
12C*1.5 SQMM ISC
6
7
SFC 1
8
9
10

SFC 1 to ISC
11
SFC 2 X06 ISC
12
Manual Synchronization Marshalling Panel to SFC 1

Manaul
Synchroni
zation SFC 1
Marshalli
ng Panel
M TB SUB TB Cable ferrul no
From To
XO1 1 SAB-3 14F R-PH/SFC-1 X01-1 LCI-1 X01-1/SAB-3 14F R-PH
XO1 2 SAB-3 14F Y-PH/SFC-1 X01-2 LCI-1 X01-2/SAB-3 14F Y-PH
XO1 3 SAB-3 14F B-PH/SFC-1 X01-3 LCI-1 X01-3/SAB-3 14F B-PH

XO1 4
XO1 5

XO1 6
XO1 7

X05 17 SFC-1 X05:17/TLS-1 X0:05 TLS-1 X0:05/SFC-1 X05:17


X05 18 SFC-1 X05:18/TLS-1 X0:06 TLS-1 X0:06/SFC-1 X05:18
X05 19 SFC-1 X05:19/TLS-1 X0:07 TLS-1 X0:07/SFC-1 X05:19
X05 20 SFC-1 X05:20/TLS-1 X0:08 TLS-1 X0:08/SFC-1 X05:20
X05 21 SFC-1 X05:21/TLS-1 X0:09 TLS-1 X0:09/SFC-1 X05:21
X05 22 SFC-1 X05:22/TLS-1 X0:10 TLS-1 X0:10/SFC-1 X05:22
X05 23 SFC-1 X05:23/TLS-1 X0:11 TLS-1 X0:11/SFC-1 X05:23
X05 24 SFC-1 X05:24/TLS-1 X0:12 TLS-1 X0:12/SFC-1 X05:24
X05 25 SFC-1 X05:25/SPARE TB-1 SPARE TB-1/SFC-1 X05:25
X05 26 SFC-1 X05:26/ SPARE TB-2 SPARE TB-2/SFC-1 X05:26
X05 27 SFC-1 X05:27/TLS-1 X0:1 TLS-1 X0:1/SFC-1 X05:27
X05 28 SFC-1 X05:28/TLS-1 X0:2 TLS-1 X0:2/SFC-1 X05:28
X05 29 SFC-1 X05:29/TLS-1 X0:3 TLS-1 X0:3/SFC-1 X05:29
X05 30 SFC-1 X05:30/TLS-1 X0:4 TLS-1 X0:4/SFC-1 X05:30
X05 49 SFC-1 X05:49/TLS-1 X0:13 TLS-1 X0:13/SFC-1 X05:49
X05 50 SFC-1 X05:50/TLS-1 X0:14 TLS-1 X0:14/SFC-1 X05:50
X05 51 SFC-1 X05:51/TLS-1 X0:15 TLS-1 X0:15/SFC-1 X05:51
X05 52 SFC-1 X05:52/TLS-1 X0:16 TLS-1 X0:16/SFC-1 X05:52

X05 31 SFC-1 X05:31/TMS-1 XO:5 TMS-1 XO:5/SFC-1 X05:31


X05 32 SFC-1 X05:32/TMS-1 XO:6 TMS-1 XO:6/SFC-1 X05:32
X05 33 SFC-1 X05:33/TMS-1 XO:7 TMS-1 XO:7/SFC-1 X05:33
X05 34 SFC-1 X05:34/TMS-1 XO::8 TMS-1 XO:8/SFC-1 X05:34
X05 35 SFC-1 X05:35/TMS-1 XO:9 TMS-1 XO:9/SFC-1 X05:35
X05 36 SFC-1 X05:36/TMS-1 XO:10 TMS-1 XO:10/SFC-1 X05:36
X05 37 SFC-1 X05:37/TMS-1 XO:11 TMS-1 XO:11/SFC-1 X05:37
X05 38 SFC-1 X05:38/TMS-1 XO:12 TMS-1 XO:12/SFC-1 X05:38
X05 39 SFC-1 X05:39/TMS-1 X0:SPARE TMS-1 XO:SPARE/SFC-1 X05:39
X05 40 SFC-1 X05:40/TMS-1 X0:SPARE TMS-1 XO:SPARE/SFC-1 X05:40
X05 41 SFC-1 X05:41/TMS-1 XO:1 TMS-1 XO:1/SFC-1 X05:41
X05 42 SFC-1 X05:42/TMS-1 XO:2 TMS-1 XO:2/SFC-1 X05:42
X05 43 SFC-1 X05:43/TMS-1 XO:3 TMS-1 XO:3/SFC-1 X05:43
X05 44 SFC-1 X05:44/TMS-1 XO:4 TMS-1 XO:4/SFC-1 X05:44
X05 53 SFC-1 X05:53/TMS-1 XO:13 TMS-1 XO:13/SFC-1 X05:53
X05 54 SFC-1 X05:54/TMS-1 XO:14 TMS-1 XO:14/SFC-1 X05:54
X05 55 SFC-1 X05:55/TMS-1 XO:15 TMS-1 XO:15/SFC-1 X05:55
X05 56 SFC-1 X05:56/TMS-1 XO:16 TMS-1 XO:16/SFC-1 X05:56

45 SFC-1 X05:45/ ICB-1 X05:16 ICB-1 X05:16/SFC-1 X05:45


X05
46 SFC-1 X05:46/ICB-1 X05:18 ICB-1 X05:18/SFC-1 X05:46

spare TB 13 SFC-1 SPARE XO3:13/OCB-1 X05:21 OCB-1 X05:21/SFC-1 SPARE XO3:13


X03 14 SFC-1 SPARE XO3:14/OCB-1 X05:22 OCB-1 X05:22/SFC-1 SPARE XO3:14

17 SFC-1 X06:17/ICB-1 X03:3 ICB-1 XO3:3/SFC-1 X06:17


X06
18 SFC-1 X06:18/ICB-1 X03:4 ICB-1 XO3:4/SFC-1 X06:18

21 SFC-1 X06:21/ISC K_LCI1:1 ISC K_LCI1:1/SFC-1 X06:21


X06
22 SFC-1 X06:22/ISC K_LCI1:2 ISC K_LCI1:2/SFC-1 X06:22
11 SFC-1 X05:11/ISC K_LCI1:13 ISC K_LCI1:13/SFC-1 X05:11
X05
12 SFC-1 X05:12/ ISC K_LCI1:14 ISC K_LCI1:14/SFC-1 X05:12
spare TB SPARE SPARE

7 SFC1 X05:7/ISC K_LCI1:10 ISC K_LCI1:10/SFC1 X05:7


X05
8 SFC1 X05:8/ISC K_LCI1:11 ISC K_LCI1:11/SFC1 X05:8

X03 7 SFC1 X03:7/ISC K_LCI1:4 ISC K_LCI1:4/SFC1 X03:7


X03 8 SFC1 X03:8/ISC K_LCI1:5 ISC K_LCI1:5/SFC1 X03:8
X03 10 SFC1 X03:9/ISC K_LCI1:7 ISC K_LCI1:7/SFC1 X03:9
X03 11 SFC1 X03:10/ISC K_LCI1:8 ISC K_LCI1:8/SFC1 X03:10

X03 1 SFC-1 X03:1/K_LCI1:19 K_LCI1:19/SFC-1 X03:1


2 SFC-1 X03:2/K_LCI1:20 K_LCI1:20/SFC-1 X03:2
X03 4 SFC1 XO3:4/K_LCI1:16 K_LCI1:16/SFC1 XO3:4
5 SFC1 XO3:5/K_LCI1:17 K_LCI1:17/SFC X03:5

DI

DI

DI

DI

DI

DI

DI
DO

DO

DO

59
60
X05
9
10

61
X05
62
57
X05
58
63
X05
64

13
X05
14
1
2
3
4
5
6
X38
7
8
9
10
11
12
Describtion

415 V THREE PHASE SUPPLY (SAB-3 32A SPARE)

230VAC SOURCE 1

230VAC SOURCE 1

WINDING TEMP ALARM

WINDING TEMP TRI

*BUCHHOLZ ALARM

OIL LEVEL MAX ALARM

OIL LEVEL MIN TRI

*OIL TEMP ALARM

OIL TEMP TRIP

TLS BUCHHOLZ TRIP

TLS PRESS RELIEF TRI

WINDING TEMP ALARAM

WINDING TEMP TRIP

BUCHHOLZ ALARM

OIL LEVEL MAX ALAR

OIL LEVEL MIN TRI

OIL TEMP ALARM

*OIL TEMP TRI

TMS BUCHHOLZ TRIP

TMS PRESS RELIEF TRI


TMS PRESS RELIEF TRI

ICB IS TRIPPING

OCB IS TRIPPING

TRIP ICB

RCB CLOSE CMD

TRIP FROM EXCITATION

SCB is Tripping

Excitation is ON

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL (AI)

EXC REFERANCE(AO)

LCI IS HEALTHY

MV ON FEEDBACK

OPERATION ON FEEDBACK

OPERATION OFF FEEDBACK

SFC IN REMOTE MODE

COMMON ALARM FROM SFC

COMMON TRIP FROM SFC


OPERATION ON COMMAND FOR SFC

OPERATION OFF COMMAND

TRIP FROM EXTERNAL

SCB IS CLOSED

RCB IS CLOSED

OPERATION READY

Alarm

FAULT

OCB is Closed

Spare

OPERATION READY

86c Trip contact from MPP

Frequency lower

Frequency Raise

Voltage lower

Voltage Raise

Manual Synchronisation panel selected in Local

RCB Closing feedback from Manual


synchronization panel (52cx -MPP)
TAG Cable C NO FROM M TB S TB TO M TB SUB TB
Size
230VAC
1
ISC PTB3
3

220VDC
1
ISC PTB1
3
PLC to ISC
3
X_LCI1_DI
4
3
X_LCI2_DI
4
3
X_CUSTOMER_DI
4
7
X_CUSTOMER_DI
8
PLC ISC
11
X_CUSTOMER_DI
12
15
X_CUSTOMER_DI
16
19
X_CUSTOMER_DI
20
23
X_CUSTOMER_DI
24
RCB Close FB Direct from Breaker
5
RCB1 X_CUSTOMER_DI
6
9
RCB2 X_CUSTOMER_DI
10
13
RCB3 X_CUSTOMER_DI
14
ISC
17
RCB4 X_CUSTOMER_DI
18
21
RCB5 X_CUSTOMER_DI
22
25
RCB6 X_CUSTOMER_DI
26

ISC to PLC
1
2
3
4
M

ER
5
6
7

24C*1.5 SQMM

X_CUSTOMER
8
9

_DO
ISC PLC
10
11
12
13
14
15
16
17
18
ISC TO RCB 1
15 K_M1 1
RCB 1/MPP TB07 ISC
16 K_M1 2
EXC 1 TO ISC
bkr 33 K_M1 10
EXC 1 ISC
bkr 34 K_M1 11
X5 25 K_M1 13
EXC 1 ISC
X5 26 K_M1 14
SCB 1 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
XO5 13 K_M1 spare
SCB 1 ISC
X05 15 K_M1 spare
BUS PT TO ISC
K_M1 4
BUS PT ISC
K_M1 5
LAVT 1 TO ISC
K_M1 7
LAVT 1 ISC
K_M1 8
EXC 1 TO ISC
X10 48 K_M1 19
EXC 1
X10 47 K_M1 20
ISC
X5 71 K_M1 16
EXC 1
X5 72 K_M1 17
ISC TO RCB 2
K_M2 1
RCB 2 ISC
K_M2 2
EXC 2 TO ISC
K_M2 10
EXC 2 ISC
K_M2 11
K_M2 13
EXC 2 ISC
K_M2 14
SCB 2 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M2
SCB 2 ISC
SCB 2 ISC
K_M2
BUS PT TO ISC
K_M2 4
BUS PT ISC
K_M2 5
LAVT 2 TO ISC
K_M2 7
LAVT 2 ISC
K_M2 8
EXC 2 TO ISC
K_M2 19
EXC 2
K_M2 20
ISC
K_M2 16
EXC 2
K_M2 17
ISC TO RCB 3
K_M3 1
RCB 3 ISC
K_M3 2
EXC 3 TO ISC
K_M3 10
EXC 3 ISC
K_M3 11
K_M3 13
EXC 3 ISC
K_M3 14
SCB 3 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M3
SCB 3 ISC
K_M3
BUS PT TO ISC
K_M3 4
BUS PT ISC
K_M3 5
LAVT 3 TO ISC
K_M3 7
LAVT 3 ISC
K_M3 8
EXC 3 TO ISC
K_M3 19
EXC 3
K_M3 20
ISC
K_M3 16
EXC 3
K_M3 17
ISC TO RCB 4
K_M4 1
RCB 4 ISC
K_M4 2
EXC 4 TO ISC
K_M4 10
EXC 4 ISC
K_M4 11
K_M4 13
EXC 4 ISC
K_M4 14
SCB 4 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M4
SCB 4 ISC
K_M4
BUS PT TO ISC
K_M4 4
BUS PT ISC
K_M4 5
LAVT 4 TO ISC
K_M4 7
LAVT 4 ISC
K_M4 8
EXC 4 TO ISC
K_M4 19
EXC 4
K_M4 20
ISC
K_M4 16
EXC 4
K_M4 17
ISC TO RCB 5
K_M5 1
RCB 5 ISC
K_M5 2
EXC 5 TO ISC
K_M5 10
EXC 5 ISC
K_M5 11
K_M5 13
EXC 5 ISC
K_M5 14
SCB 5 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M5
SCB 5 ISC
K_M5
BUS PT TO ISC
K_M5 4
BUS PT ISC
K_M5 5
LAVT 5 TO ISC
K_M5 7
LAVT 5 ISC
K_M5 8
EXC 5 TO ISC
K_M5 19
EXC 5
K_M5 20
ISC
K_M5 16
EXC 5
K_M5 17
ISC TO RCB 6
K_M6 1
RCB 6 ISC
K_M6 2
EXC 6 TO ISC
K_M6 10
EXC 6 ISC
K_M6 11
K_M6 13
EXC 6 ISC
K_M6 14
SCB 6 TO ISC ( TAKE FROM SCB MASTER TRIP: NC )
K_M6
SCB 6 ISC
K_M6
BUS PT TO ISC
K_M6 4
BUS PT ISC
K_M6 5
LAVT 6 TO ISC
K_M6 7
LAVT 6 ISC
K_M6 8
EXC 6 TO ISC
K_M6 19
EXC 6
K_M6 20
ISC
K_M6 16
EXC 6
K_M6 17
For PLC Describtion

230 VAC Aux Supply

220VDC

OCB 1 is Closed

OCB 2 is closed

SCB 1 is Closed

SCB 2 is Closed

SCB 3 is Closed

SCB 4 is Closed

SCB 5 is Closed

SCB 6 is Closed

RCB1 is Closed

RCB2 is Closed

RCB3 is Closed

RCB4 is Closed

RCB5 is Closed

RCB6 is Closed

Motor 1 Selected

Motor 2 Selected
Motor 3 Selected

Motor 4 Selected

Motor 5 Selected

Motor 6 Selected

Operation Ready

ALARM

FAULT

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping
SCB is Tripping

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping
LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE

RCB CLOSE CMD

EXCITATION is ON

TRIP FROM EXCITATION

SCB is Tripping
LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL

EXC REFERANCE
TAG Cable C NO FROM M TB S TB TO M TB SUB TB For PLC
Size
LT AUX SUPPLY FEDEER TO SFC 2
XO1 1
4CX6SQM XO1 2
LT SFC 2
M CU XO1 3

UPS SUPPLY TO SFC 2


XO1 4
3CX6SQM XO1 5
UPS 1 SFC 2
M CU

AUXILIARY SUPPLY TO SFC 2


3CX6SQM AUX XO1 6
SFC 2
M CU SUPPLY XO1 7
TLS TRANSFORMER TO SFC 2
1 TLS 2 TB 5 SFC 2 X05 17
2 TLS 2 TB 6 SFC 2 X05 18
3 TLS 2 TB 7 SFC 2 X05 19
4 TLS 2 TB 8 SFC 2 X05 20
5 TLS 2 TB 9 SFC 2 X05 21
6 TLS 2 TB 10 SFC 2 X05 22
7 TLS 2 TB 11 SFC 2 X05 23
8 TLS 2 TB 12 SFC 2 X05 24
9 TLS 2 TB SFC 2 X05 25
10 TLS 2 TB SFC 2 X05 26
24CX1.5SQMM

11 TLS 2 TB 1 SFC 2 X05 27


12 TLS 2 TB 2 SFC 2 X05 28
13 TLS 2 TB 3 SFC 2 X05 29
14 TLS 2 TB 4 SFC 2 X05 30
15 TLS 2 TB 13 SFC 2 X05 49
16 TLS 2 TB 14 SFC 2 X05 50
17 TLS 2 TB 15 SFC 2 X05 51
18 TLS 2 TB 16 SFC 2 X05 52
19
20
21
22
23
24
TMS TRANSFORMER TO SFC 2
TMS 2 TB 5 SFC 2 X05 31
TMS 2 TB 6 SFC 2 X05 32
TMS 2 TB 7 SFC 2 X05 33
TMS 2 TB 8 SFC 2 X05 34
TMS 2 TB 9 SFC 2 X05 35
TMS 2 TB 10 SFC 2 X05 36
TMS 2 TB 11 SFC 2 X05 37
TMS 2 TB 12 SFC 2 X05 38
TMS 2 TB SFC 2 X05 39
24CX1.5SQMM TMS 2 TB SFC 2 X05 40
TMS 2 TB 1 SFC 2 X05 41
TMS 2 TB 2 SFC 2 X05 42
TMS 2 TB 3 SFC 2 X05 43
TMS 2 TB 4 SFC 2 X05 44
TMS 2 TB 13 SFC 2 X05 53
TMS 2 TB 14 SFC 2 X05 54
TMS 2 TB 15 SFC 2 X05 55
TMS 2 TB 16 SFC 2 X05 56

ICB 1 TO SFC 2 ( Master Relay NC )


3CX2.5SQ 45
ICB 2 SFC 2 X05
MM CU 46
OCB 1 TO SFC 2 ( Master Relay NC )
3CX2.5SQ
MM CU OCB 2 SFC 2

SFC 1 TO ICB 1
3CX2.5SQ 17
SFC 2 ICB 2 X06
MM CU 18
MARSHALING TO SFC 2 INTERFACE FOR MOTOR AND EXCITATION SIGNALS
2CX2.5SQ 1 K_LCI2 1 21
MM ISC SFC 2 X06
2 K_LCI2 2 22
1 K_LCI2 13 11
X05
2 K_LCI2 14 12
7CX2.5SQMM

3
spareTB
4 ISC SFC 2
5 K_LCI2 10 7
X05
6 K_LCI2 11 8
7
1 K_LCI2 4 X03 7
2 K_LCI2 5 X03 8
7CX2.5SQMM

3 K_LCI2 7 X03 10
4 ISC K_LCI2 8 SFC 2 X03 11
5
6
7
1 K_LCI2 19 1
IR X1.5SQMM

X03 AI

ISC SFC 2
3 PAIR X1.5SQMM
X03 AI
2 K_LCI2 20 2
1 K_LCI2 16 4
ISC SFC 2 X03 AO
2 K_LCI2 17 5
1
2
SFC-2 TO COMMON PLC
1 X06 1
DI
2 X06 2
3 X06 3
DI
4 X06 4
5 X06 5
DI
6 X06 6
7 X06 7
17C*1.5 SQMM

DI
8 X06 8
9 SFC 2 X06 9 CM PLC
DI
10 X06 10
11 X06 13
DI
12 X06 14
13 X06 15
DI
14 X06 16
15
16
17
1 X05 1
DO
2 X05 2
3 X05 3
DO
4 X05 4
12C*1.5 SQMM

5 X05 47
DO
6 X05 48
SFC 2 CM PLC
7
8
9
10
11
12
ISC to SFC 2
1 59
2 60
X05
3 9
4 10
X_LCI2_DO

5
12C*1.5 SQMM ISC
6
7
SFC 2
8
9 61
X05
10 62
57
X05
X05
58
63
X05
64
SFC 2 to ISC
11
SFC 2 X06 ISC
12
Manual Synchronization Marshalling Panel to SFC 2
13
X05
14
1
2
3
Manaul 4
Synchroni 5
zation SFC 2
Marshalli 6
X38
ng Panel 7
8
9
10
11
12
Describtion

415 V THREE PHASE SUPPLY

230VAC SOURCE 1

230VAC SOURCE 1

WINDING TEMP ALARM

WINDING TEMP TRI

*BUCHHOLZ ALARM

OIL LEVEL MAX ALARM

OIL LEVEL MIN TRI

*OIL TEMP ALARM

OIL TEMP TRIP

TLS BUCHHOLZ TRIP

TLS PRESS RELIEF TRI

WINDING TEMP ALARAM

WINDING TEMP TRIP

BUCHHOLZ ALARM
BUCHHOLZ ALARM

OIL LEVEL MAX ALAR

OIL LEVEL MIN TRI

OIL TEMP ALARM

*OIL TEMP TRI

TMS BUCHHOLZ TRIP

TMS PRESS RELIEF TRI

ICB IS TRIPPING

OCB IS TRIPPING

TRIP ICB

RCB CLOSE CMD

TRIP FROM EXCITATION

SCB is Tripping

Excitation is ON

LINE SYN VOLTAGE

MACHINCE VOLTAGE

EXC ACTUAL
EXC ACTUAL

EXC REFERANCE

LCI IS HEALTHY

MV ON FEEDBACK

OPERATION ON FEEDBACK

OPERATION OFF FEEDBACK

SFC IN REMOTE MODE

COMMON ALARM FROM SFC

COMMON TRIP FROM SFC

OPERATION ON COMMAND FOR SFC

OPERATION OFF COMMAND

TRIP FROM EXTERNAL

SCB IS CLOSED

RCB IS CLOSED

OPERATION READY

Alarm

FAULT

OCB is Closed
OCB is Closed

Spare

OPERATION READY

86c Trip contact from MPP

Frequency lower

Frequency Raise

Voltage lower

Voltage Raise

Manual Synchronisation panel selected in


Local
RCB Closing feedback from Manual
synchronization panel (52cx -MPP)